Direct naar inhoud
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + leveranciers

ICS Advisories

Advisories specifiek gericht op industriële besturingssystemen — van CISA ICS-CERT en rechtstreeks van leveranciers (onder meer Siemens, ABB, Schneider Electric, WAGO en Phoenix Contact) — inclusief revisiegeschiedenis (initiële publicatie, Update A, Update B) en gekoppelde CVE's.

1

Gevonden

Advisorydata: live koppeling— laatst opgehaald: 25 november 2026 om 00:04.

1 advisories gevonden

  • 7PAA025875DoS Vulnerability in System 800xA Batch Management - TCP Connection Resource ExhaustionABB · System 800xA Batch ManagementmiddelABB PSIRT1 CVE24 november 2026

    Risk evaluation

    ABB is aware of a vulnerability affecting the versions of 800xA Batch Management listed as affected in the advisory. Under specific network conditions, a malicious user with access to the control network could cause temporary service degradation or a temporary denial of service. Successful exploitation may cause affected services to become temporarily unavailable. The affected service automatically resumes normal operation after malicious traffic is stopped and stale network connections are cleared by the operating system. Information disclosure, unauthorized code execution, and integrity impacts have not been observed.

    Mitigatiesamenvatting

    Workarounds are specific measures that a user can take to help block an attack, for example, temporarily disabling the vulnerable feature may remove the exposure with well-known impact on functionality. ABB has tested the following workarounds. Although these workarounds will not correct the underlying vulnerability, they can help block known attack vectors. When a workaround reduces functionality, this is identified below as “Impact of workaround”. ABB has identified the following workarounds that can reduce exposure: - Network Segmentation: Restrict access to systems running 800xA Batch Management through firewalls and industrial network segmentation. - Access Control: Allow TCP connections to port 40061/TCP only from authorized systems and trusted communication partners. - Monitoring: Monitor systems for abnormal connection volumes and investigate excessive TCP connection attempts. Impact of Workaround: No loss of system functionality is expected when standard industrial network security practices are implemented.

    Gepubliceerd
    24 november 2026
    Laatste update
    24 november 2026
    Gekoppelde CVE's
    CVE-2026-78354
    Getroffen sectoren
    —

    Revisiegeschiedenis (2)

    1. Initiële publicatie — 24 november 2026

      Update in the Remediation Section.

    2. Update A — 24 november 2026

      Initial version.