CISA + leveranciers
ICS Advisories
Advisories specifiek gericht op industriële besturingssystemen — van CISA ICS-CERT en rechtstreeks van leveranciers (onder meer Siemens, ABB, Schneider Electric, WAGO en Phoenix Contact) — inclusief revisiegeschiedenis (initiële publicatie, Update A, Update B) en gekoppelde CVE's.
1
Gevonden
Advisorydata: live koppeling— laatst opgehaald: 7 november 2026 om 01:34.
Filters
1 actief1 advisories gevonden
Advisory2025-08_VDE-2025-070
CODESYS Control V3 - NULL pointer dereference
Gepubliceerd
4 augustus 2025
Laatste update
14 oktober 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
A vulnerability in the CODESYS Control runtime system's CmpDevice component allows unauthenticated attackers to cause a denial-of-service (DoS) via specially crafted communication requests. The issue is triggered by a NULL pointer dereference and also affects systems when outdated CODESYS clients attempt to log in. Only PLCs based on the CODESYS Runtime Toolkit containing the components CmpDevice, CmpAuditLog, and CmpSessionInformation are impacted. **Update 1.1.0, 01.09.2025:** Updated remediation category - fixed SL runtimes are now available.
Mitigatiesamenvatting
The vulnerability can be mitigated by restricting the allowed login authentication type "CmpUserMgr/UserLogin_AuthenticationType" to "ONLY_ASYMMETRIC". This can be configured either via the Device Security Settings dialog in the CODESYS Development System or directly in the configuration file of the CODESYS Control runtime system (CODESYSControl.cfg) by adding the following setting: [CmpUserMgr] SECURITY.UserLogin_AuthenticationType=ONLY_ASYMMETRIC With this configuration in place, both potential attackers and legacy CODESYS protocol clients (prior to version 3.5.16.0) will be blocked from logging in, thereby preventing execution of the vulnerable code path.
Revisiegeschiedenis (3)
Initiële publicatie — 4 augustus 2025
Initial revision.
Update A — 1 september 2025
Updated remediation category - fixed SL runtimes are now available.
Update B — 14 oktober 2025
List of affected and fixed products corrected regarding CODESYS HMI (SL) and CODESYS Runtime Toolkit