Direct naar inhoud
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + leveranciers

ICS Advisories

Advisories specifiek gericht op industriële besturingssystemen — van CISA ICS-CERT en rechtstreeks van leveranciers (onder meer Siemens, ABB, Schneider Electric, WAGO en Phoenix Contact) — inclusief revisiegeschiedenis (initiële publicatie, Update A, Update B) en gekoppelde CVE's.

1

Gevonden

Advisorydata: live koppeling— laatst opgehaald: 7 november 2026 om 00:02.

Filters

1 actief
Reset filters

1 advisories gevonden

Advisory2025-10_VDE-2025-100

CODESYS Control - Invalid type usage in visualization

CODESYS — CODESYS Control RTE (SL)

CODESYS PSIRThoog

Gepubliceerd

1 december 2025

Laatste update

12 februari 2026

Gekoppelde CVE's

Getroffen sectoren

Risk evaluation

A vulnerability in the CODESYS Control runtime system's CmpVisuServer component allows attackers to cause a denial-of-service (DoS) by sending special request to the CODESYS Web- or remote Target Visu. The issue is triggered by an internal read access using a pointer of wrong type. Only CODESYS Control runtime systems and PLCs based on the CODESYS Runtime Toolkit that include the CmpVisuServer component are impacted. In the case of CODESYS Web Visu, the vulnerability can only be exploited if the web server is running. When the web server starts depends on the startup configuration: By default, it is only running if the PLC executes application code that includes a visualization.

Mitigatiesamenvatting

Update the following products to version 3.5.21.40. * CODESYS Control RTE (SL) * CODESYS Control RTE (for Beckhoff CX) SL * CODESYS Control Win (SL) * CODESYS HMI (SL) * CODESYS Remote Target Visu * CODESYS Runtime Toolkit The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.

Revisiegeschiedenis (2)
  1. Initiële publicatie — 1 december 2025

    Initial revision.

  2. Update A — 12 februari 2026

    Updated remediation category - fixed SL runtimes are now available.

Officiële bron: CODESYS PSIRT