Direct naar inhoud
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + leveranciers

ICS Advisories

Advisories specifiek gericht op industriële besturingssystemen — van CISA ICS-CERT en rechtstreeks van leveranciers (onder meer Siemens, ABB, Schneider Electric, WAGO en Phoenix Contact) — inclusief revisiegeschiedenis (initiële publicatie, Update A, Update B) en gekoppelde CVE's.

1

Gevonden

Advisorydata: live koppeling— laatst opgehaald: 7 november 2026 om 00:32.

Filters

1 actief
Reset filters

1 advisories gevonden

Advisory2026-08_VDE-2026-056

CODESYS Control - Incorrect Authorization

CODESYS — CODESYS Control RTE (SL)

CODESYS PSIRThoog

Gepubliceerd

26 mei 2026

Laatste update

18 juni 2026

Gekoppelde CVE's

Getroffen sectoren

Risk evaluation

The CODESYS Control runtime system provides a user management mechanism with multiple privilege groups including the visualization administrators group, which is intended solely to manage visualization users. Due to insufficient authorization checks an authenticated remote user with low-privileged visualization administrator access can delete higher-privileged accounts. However, independent mechanisms protect the deletion of the last remaining device admin user, preventing a complete loss of administrative access to the device. The CODESYS Control runtime system is only affected if the optional visualization user management feature is enabled and a visualization administrator account has been configured.

Mitigatiesamenvatting

Update the following products to version 3.5.22.20. * CODESYS Control RTE (SL) * CODESYS Control RTE (for Beckhoff CX) SL * CODESYS Control Win (SL) * CODESYS HMI (SL) * CODESYS Runtime Toolkit The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.

Revisiegeschiedenis (2)
  1. Initiële publicatie — 26 mei 2026

    Initial revision.

  2. Update A — 18 juni 2026

    Updated remediation category - fixed SL runtimes are now available.

Officiële bron: CODESYS PSIRT