Risk evaluation
The CmpWebServer component in the CODESYS Control Runtime allows users to create browser-based visualizations for monitoring and controlling industrial processes. Due to improper bounds checking, a specially crafted HTTP request from an unauthenticated remote attacker may lead to a size-limited out-of-bounds write, causing a denial of service of the affected device. The CODESYS Control runtime system is only affected if the web server is active, which by default requires a running application with an enabled Web Visualization.
Mitigatiesamenvatting
Update the following products to version 3.5.22.20. * CODESYS Control RTE (SL) * CODESYS Control RTE (for Beckhoff CX) SL * CODESYS Control Win (SL) * CODESYS HMI (SL) * CODESYS Runtime Toolkit The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.
Revisiegeschiedenis (2)
Initiële publicatie — 26 mei 2026
Initial revision.
Update A — 18 juni 2026
Updated remediation category - fixed SL runtimes are now available.