Advisory2026-12_VDE-2026-097
CODESYS Control Runtime - Improper Synchronization in Monitoring
Gepubliceerd
30 september 2026
Laatste update
22 oktober 2026
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
The monitoring functionality of affected CODESYS Control runtime systems processes read and write requests to PLC application data sent by the CODESYS Development System and other clients such as HMIs. Due to improper synchronization in the CmpMonitor2 component when processing concurrent requests from multiple clients, incorrect data may be read or written, potentially resulting in unexpected behavior of the affected product. PLCs based on the CODESYS Runtime Toolkit or CODESYS Safety SIL2 are affected if they allow simultaneous access by two or more clients via the CODESYS protocol. In CODESYS Development System 3, simultaneous access to the included Simulation Runtime can only occur when access by an external client, such as an HMI, has been explicitly enabled through dedicated configuration. The default configuration of CODESYS Development System 3 is not affected. The vulnerability can be exploited by an authenticated remote attacker with monitoring access by issuing concurrent requests to an affected product.
Mitigatiesamenvatting
Update the following products to version 3.5.22.40. * CODESYS Control RTE (SL) * CODESYS Control RTE (for Beckhoff CX) SL * CODESYS Control Win (SL) * CODESYS Runtime Toolkit * CODESYS Safety SIL2 * CODESYS HMI (SL) * CODESYS Development System 3 The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.
Revisiegeschiedenis (2)
Initiële publicatie — 30 september 2026
Initial revision.
Update A — 22 oktober 2026
Updated remediation category - fixed SL runtimes are now available, formal adaptions.