Direct naar inhoud
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + leveranciers

ICS Advisories

Advisories specifiek gericht op industriële besturingssystemen — van CISA ICS-CERT en rechtstreeks van leveranciers (onder meer Siemens, ABB, Schneider Electric, WAGO en Phoenix Contact) — inclusief revisiegeschiedenis (initiële publicatie, Update A, Update B) en gekoppelde CVE's.

1

Gevonden

Advisorydata: live koppeling— laatst opgehaald: 7 november 2026 om 13:21.

Filters

1 actief
Reset filters

1 advisories gevonden

SSA-794185

SSA-794185: RADIUS Protocol Susceptible to Forgery Attacks (CVE-2024-3596) - Impact to SIPROTEC, SICAM and Related Products

Siemens — CPC80 Central Processing/Communication

Siemens ProductCERTkritiek

Gepubliceerd

13 mei 2025

Laatste update

13 oktober 2026

Gekoppelde CVE's

Getroffen sectoren

Risk evaluation

This advisory documents the impact of CVE-2024-3596 (also dubbed "Blastradius"), a vulnerability in the RADIUS protocol, to SIPROTEC, SICAM and related products. The vulnerability could allow on-path attackers, located between a Network Access Server (the RADIUS client, e.g., a SICAM device) and a RADIUS server, to forge Access-Request packets in a way that enables them to modify the corresponding server response packet at will, e.g., turning an "Access-Reject" message into an "Access-Accept". This would cause the Network Access Server to grant the attackers access to the network with the attackers desired authorization (and without the need of knowing or guessing legitimate access credentials). Further details incl. external references can be found in the chapter "Additional Information". Siemens has released new versions for several affected products and recommends to update to the latest versions, and to configure the updated systems as recommended in the chapter "Additional Information". Siemens has released new versions for the affected products and recommends to update to the latest versions.See chapter "Additional Information" for details.

Mitigatiesamenvatting

Configure the RADIUS server to require the presence of a Message-Authenticator attribute in all Access-Request packets from RADIUS client devices that support it

Revisiegeschiedenis (4)
  1. Initiële publicatie — 13 mei 2025

    Publication Date

  2. Update A — 12 augustus 2025

    Added fix for affected firmware modules in SICAM A8000 (CPCI85 for CP-8031/CP-8050, CPC80 for CP-8000/CP-8021/CP-8022, SICORE for CP-8010/CP-8012), SICAM EGS (CPCI85) and SICAM S8000 (SICORE). Added fix for SICAM Q200, for SIPROTEC 5 - CP300 and CP150 Devices, and for SIPROTEC 5 Compact 7SX800 (CP050). Added SICAM AK 3, SICAM BC, SICAM TM, SICAM GridEdge and SIPROTEC 5 - CP200 Devices to the list of known not affected products

  3. Update B — 11 november 2025

    Added fix for SIPROTEC 5 - CP100 Devices

  4. Update C — 9 juni 2026

    Added fix for PowerLink IP

Officiële bron: Siemens ProductCERT