VDE-2022-003
BECKHOFF: Null Pointer Dereference vulnerability in products with OPC UA technology
Risk evaluation
By tricking clients of the mentioned products into contacting malicious OPC UA servers and thereby acting as OPC UA clients, a crash of the component can be provoked.
Mitigatiesamenvatting
Have your applications configured to use other than SecurityMode=None for all OPC UA connections. Avoid that these connect to an unknown OPC UA server with SecurityMode=None. In particular, avoid that your applications connect to servers which they discover via mDNS, a Local Discovery Server (LDS), an untrusted Global Discovery Server (GDS) or even trusted GDS using SecurityMode=none. Especially in the latter case an adversary might be able to apply the 'man in the middle' pattern to attack the connection and inject a bad message which triggers the vulnerability.
Revisiegeschiedenis (2)
Initiële publicatie — 1 maart 2022
Initial revision.
Update A — 5 juni 2025
Fix: quotation mark