Direct naar inhoud
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + leveranciers

ICS Advisories

Advisories specifiek gericht op industriële besturingssystemen — van CISA ICS-CERT en rechtstreeks van leveranciers (onder meer Siemens, ABB, Schneider Electric, WAGO en Phoenix Contact) — inclusief revisiegeschiedenis (initiële publicatie, Update A, Update B) en gekoppelde CVE's.

1

Gevonden

Advisorydata: live koppeling— laatst opgehaald: 7 november 2026 om 14:22.

Filters

1 actief
Reset filters

1 advisories gevonden

VDE-2024-048

Beckhoff: Improper neutralization of input in IPC-Diagnostics-www package included in TwinCAT/BSD operating system

Beckhoff — IPC-Diagnostics-www package

Beckhoff PSIRThoog

Gepubliceerd

27 augustus 2024

Laatste update

22 mei 2025

Gekoppelde CVE's

Getroffen sectoren

Risk evaluation

By default, TwinCAT/BSD-based products have a device-specific web interface for web-based management (WBM) enabled, developed by Beckhoff and known as Beckhoff Device Manager UI. It can be accessed remotely or locally. When accessed locally, the user can bypass input validation by entering specially crafted inputs into the user interface for certain pages, which then allows local commands to be executed with administrative privileges.

Mitigatiesamenvatting

Avoid the existence of user accounts with login permission on the target other than administrator access. By default, TwinCAT/BSD has preconfigured user accounts with lower privileges, but none of them have a password, which results in them being denied login access. Avoid running third-party applications on the target that have not been properly audited, regardless of the user they are running as.

Revisiegeschiedenis (4)
  1. Initiële publicatie — 13 augustus 2024

    initial revision

  2. Update A — 6 november 2024

    Fix: correct certvde domain, added self-reference

  3. Update B — 16 januari 2025

    Fix: list of branches

  4. Update C — 11 april 2025

    Fix: version range

Officiële bron: Beckhoff PSIRT