CISA + leveranciers
ICS Advisories
Advisories specifiek gericht op industriële besturingssystemen — van CISA ICS-CERT en rechtstreeks van leveranciers (onder meer Siemens, ABB, Schneider Electric, WAGO en Phoenix Contact) — inclusief revisiegeschiedenis (initiële publicatie, Update A, Update B) en gekoppelde CVE's.
20
Gevonden
Advisorydata: live koppeling— laatst opgehaald: 7 november 2026 om 00:32.
Filters
1 actief20 advisories gevonden
Gepubliceerd
2 november 2026
Laatste update
5 november 2026
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Festo Didactic FactoryViews and MES4 deployed along with xampp bundle an Apache web server with PHP. The bundled version of PHP is vulnerable to the two critical vulnerabilities CVE-2026-109618 and CVE-2026-109619 (commonly referred to as PHP2Shell). These vulnerabilities allow an attacker to remotely execute code on the FactoryViews or xampp host system.
Mitigatiesamenvatting
Install patch 1.12.2 through the "Versions" page of the FactoryViews control panel on version 1.12.0 or 1.12.1. Versions of FactoryViews prior to 1.12 must first be updated to 1.12 available for download here: https://www.festo.com/de/de/support-portal-specific?query=factoryviews&groupId=4&productName=factoryviews&documentId=659952
Revisiegeschiedenis (2)
Initiële publicatie — 2 november 2026
Initial Revision
Update A — 5 november 2026
Adjusted information about vendor fix for FactoryViews
Gepubliceerd
20 oktober 2026
Laatste update
20 oktober 2026
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Festo AX OS versions 25.0.1.46 and 25.9.2.4, which are based on PLCnext by Phoenix Contact, used by the Festo product CEPE are affected by multiple OpenSSL vulnerabilities. The vulnerabilities are identified as CVE-2025-15467 and CVE-2025-69419. Attacks may be possible when maliciously crafted firmware, key files, PKCS#12 files, CMS/PKCS#7 content, or digitally signed objects are uploaded and processed by the affected system. In the device context, exploitation typically requires a logged-in user with high privileges or the processing of attacker-supplied cryptographic objects.
Mitigatiesamenvatting
Update affected CEPE installations running Festo AX OS 25.0.1.46 or Festo AX OS 25.9.2.4 to Festo AX OS 26.3.1.4 or later.
Revisiegeschiedenis (1)
Initiële publicatie — 20 oktober 2026
Initial Revision
FSA-202601
Several CODESYS vulnerabilities in Festo Automation Suite
Gepubliceerd
26 februari 2026
Laatste update
26 februari 2026
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.
Mitigatiesamenvatting
Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.
Revisiegeschiedenis (1)
Initiële publicatie — 26 februari 2026
Initial version
Gepubliceerd
10 juli 2023
Laatste update
2 februari 2026
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
FactoryViews bundles many third-party applications which are used in background processes to provide the software's features. From time to time, vulnerabilities in these bundled applications are discovered. These are typically fixed in newer versions of FactoryViews by updating the bundled applications. FactoryViews versions up to and including 1.5.2 contain around 200 such vulnerabilities listed in this advisory.Version 1.6.0 is a security rollup release which includes updates to all bundled applications and fixes these vulnerabilities. At this time, FactoryViews Lite cannot be updated beyond version 1.1. FactoryViews 1.7 unifies the non-Lite and Lite versions and fixes these vulnerabilities for users of FactoryViews Lite.
Mitigatiesamenvatting
FactoryViews (non-Lite): Upgrade to FactoryViews 1.6.0. See the upgrade guide for information on how to upgrade. FactoryViews Lite: Upgrade to FactoryViews 1.7.0. See the upgrade guide for information on how to upgrade.
Revisiegeschiedenis (4)
Initiële publicatie — 10 juli 2023
Initial revision.
Update A — 11 januari 2024
Adjust link to VDE Advisory.
Update B — 31 juli 2025
Adjusted to VDE template. Changed title from "Several Vulnerabilities in FactoryViews <= 1.5.2" to "Festo: Several vulnerabilities in FactoryViews". Updated legal disclaimer to add references to special provisions. Included remediation for FactoryViews Lite
Update C — 2 februari 2026
Added missing CWE values
Gepubliceerd
27 februari 2024
Laatste update
8 december 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
MES PCs shipped with Windows 10 come pre-installed with XAMPP. XAMPP is a bundle of third-party open-source applications including the Apache HTTP Server, the MariaDB database and more. From time to time, vulnerabilities in these applications are discovered. These are fixed in newer versions of XAMPP by updating the bundled applications. MES PCs shipped with Windows 10 include a copy of XAMPP which contains around 140 such vulnerabilities listed in this advisory. They can be fixed by replacing XAMPP with Festo Didactic's Factory Control Panel application.
Mitigatiesamenvatting
Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities.
Revisiegeschiedenis (3)
Initiële publicatie — 27 februari 2024
Initial version
Update A — 4 november 2025
Adjust to VDE template. Add missing CWE-IDs if available. Updated legal disclaimer to add references to special provisions.
Update B — 8 december 2025
Add all missing CWE identifier and CVSS 3.x scores.
FSA-202405
Festo: Siemens S7-1500/ET200SP CPU used in Festo Didactic products contains a memory protection bypass vulnerability
Gepubliceerd
9 september 2024
Laatste update
5 november 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Siemens SIMATIC S7-1200 and S7-1500 CPUs contained in various Festo Didactic products contain a memory protection bypass vulnerability that could allow an attacker to write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks
Mitigatiesamenvatting
Update Siemens Simatic S7-1500 / ET200SP Firmware to V2.9.2 or higher
Revisiegeschiedenis (4)
Initiële publicatie — 9 september 2024
Initial version
Update A — 6 november 2024
Fix: correct certvde domain, fixed language setting, added self-reference
Update B — 27 februari 2025
Update: new Dokument ID
Update C — 5 november 2025
Removed environmental score from CVSS rating.
Gepubliceerd
30 januari 2024
Laatste update
4 november 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Several high severity vulnerabilities in CODESYS V3 affecting Festo products could lead to Remote Code Execution or Denial of Service.
Mitigatiesamenvatting
As part of a security strategy, Festo recommends the following general defense measures to reduce the risk of exploits: - Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside - Use firewalls to protect and separate the control system network from other networks - Use VPN (Virtual Private Networks) tunnels if remote access is required Activate and apply user management and password features - Use encrypted communication links - Limit the access to both development and control system by physical means, operating system features, etc. - Protect both development and control system by using up to date virus detecting solutions Festo strongly recommends to minimize and protect network access to connected devices with state of the art techniques and processes. For a secure operation follow the recommendations in the product manuals.
Revisiegeschiedenis (2)
Initiële publicatie — 30 januari 2024
Initial revision.
Update A — 4 november 2025
Adjusted to VDE template. Changed title from "Several Codesys Vulnerabilities in Festo Products" to "Festo: Multiple products contain CoDe16 vulnerability". Updated legal disclaimer to add references to special provisions.
FSA-202202
Festo: Controller CECC-S,LK,D family <= 2.3.8.1 - multiple vulnerabilities in CODESYS V3 runtime system
Gepubliceerd
18 juli 2022
Laatste update
3 november 2025
Gekoppelde CVE's
Getroffen sectoren
Energieopwekking
Risk evaluation
The Festo controller CECC product family is affected by multiple vulnerabilities in the CODESYS V3 runtime.
Mitigatiesamenvatting
For CVE-2019-5105, CVE-2019-9011, CVE-2019-9013, CVE-2020-10245, CVE-2020-12067, CVE-2020-12068, CVE-2020-12069, CVE-2020-15806, CVE-2021-29241, CVE-2021-29242, CVE-2021-33485, CVE-2021-36763, CVE-2021-36764, CVE-2022-22513, CVE-2022-22514, CVE-2022-22515, CVE-2022-22517, CVE-2022-22519: No fix planned. This issue will be handled with next hardware generation release.
Revisiegeschiedenis (4)
Initiële publicatie — 18 juli 2022
Initial revision.
Update A — 11 januari 2024
Adjust link to VDE Advisory, TLP and update some CVE information, where CVSS was not known before.
Update B — 28 juli 2025
Adjusted to VDE template. Changed title from 'Festo Controller CECC-S,-LK,-D Family Firmware <= 2.3.8.1 - Multiple Vulnerabilities in CODESYS V3 Runtime System' to 'Festo: Controller CECC-S,LK,D family <= 2.3.8.1 - multiple vulnerabilities in CODESYS V3 runtime system'. Updated legal disclaimer to add references to special provisions.
Update C — 3 november 2025
Add missing CWE values for vulnerabilities. Add missing CVSS 3.0 score for CVE-2010-5250.
FSA-202209
Festo: Incomplete documentation of remote accessible functions and protocols in Festo products
Gepubliceerd
29 november 2022
Laatste update
3 november 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Incomplete Festo product documentation of remote accessible functions and their required IP ports. Depending on the product a description of the supported features can be found in the product documentation to some extent. Update A, 2022-12-13 Added affected device "Bus module CPX-E-PN, 4080497"
Mitigatiesamenvatting
Update of technical user manual documentation in next product version.
Revisiegeschiedenis (4)
Initiële publicatie — 29 november 2022
Initial revision.
Update A — 5 december 2022
added bus module CPX-E-PN as affected product
Update B — 6 april 2023
adjusted technical user documentation to user documentation and fixed some typos.
Update C — 3 november 2025
Adjust link to VDE Advisory. Change title from "Incomplete User Documentation of Remote Accessible Functions and Protocols in Festo Products" to "Festo: Incomplete documentation of remote accessible functions and protocols in Festo products". Updated legal disclaimer to add references to special provisions.
FSA-202208
Festo: Multiple Festo products contain an unsafe default Codesys configuration
Gepubliceerd
29 november 2022
Laatste update
28 oktober 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
The products are shipped with an unsafe configuration of the integrated CODESYS Runtime environment. In this case no default password is set to the CODESYS PLC and therefore access without authentication is possible. With a successful established connection to the CODESYS Runtime the PLC-Browser commands are available. Thus granting the possibilities to e.g. read and modify the configuration file(s), start/stop the application and reboot the device.
Mitigatiesamenvatting
Festo has identified the following compensatory measures to reduce the risk: - For CVE-2022-22515: Using the online user management prevents an attacker from downloading and execute malicious code, but also suppresses start, stop, debug, or other actions on a known working application that could potentially disrupt a machine or system.
Revisiegeschiedenis (3)
Initiële publicatie — 29 november 2022
Initial revision.
Update A — 11 januari 2024
Adjust link to VDE Advisory
Update B — 28 oktober 2025
Adjusted to VDE template. Changed title from "Multiple Festo products contain an unsafe default Codesys configuration" to "Festo: Multiple Festo products contain an unsafe default Codesys configuration". Updated legal disclaimer to add references to special provisions.
Gepubliceerd
13 december 2022
Laatste update
1 oktober 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
A vulnerability was reported in WIBU-SYSTEMS CodeMeter Runtime. WIBU-SYSTEMS CodeMeter Runtime is part of the installation packages of several Festo products.FluidDraw < 6.2c and CIROS <= 7.0.6 contain a vulnerable version of WIBU-SYSTEMS CodeMeter Runtime.
Mitigatiesamenvatting
FluidDraw P5, FluidDraw P6 Avoid any FluidDraw installation with a FluidDraw installation package below version 6.2c. Updated versions of FluidDraw are available on the Festo website. In case of a FluidDraw installation package with a version below 6.2c, do not use the WIBU CodeMeter package, that is part of the FluidDraw installation package. Skip the CodeMeter installation step during the FluidDraw installation and instead use a current CodeMeter version from the WIBU website and install that separately. In case of an already installed vulnerable CodeMeter version, update all of these WIBU CodeMeter installations with the current version of WIBU CodeMeter. Please refer to the WIBU CodeMeter documentation and website for further details and mitigations on usage of WIBU CodeMeter Runtime before 7.30a. CIROS For future installations, ensure you're using a CIROS installer downloaded from https://ip.festo-didactic.com/ Infoportal/CIROS/EN/Download.html after September 15, 2022. For existing installations, update the WIBU CodeMeter Runtime separately with at least version 7.30a downloaded from the WIBU Systems website. Please refer to the WIBU CodeMeter documentation and website for further details and mitigations on usage of WIBU CodeMeter Runtime before 7.30a. MES PC If your copy of MES4 came preinstalled on a PC shipped before December 2022, you'll need to make sure this PC has at least CodeMeter Runtime 7.30a installed. If necessary, download the update from the WIBU Systems website. Additional to the above: Festo strongly recommends to restrict unprivileged access to machines running Festo software and to minimize and protect network access to connected devices with state of the art techniques and processes. For a secure operation follow the recommendations in the product manuals.
Revisiegeschiedenis (3)
Initiële publicatie — 13 december 2022
Initial revision.
Update A — 11 januari 2024
Adjust link to VDE Advisory
Update B — 1 oktober 2025
Adjusted to VDE template. Changed title from "Vulnerable WIBU-SYSTEMS CodeMeter Runtime in multiple Festo products" to "Festo: Vulnerable WIBU-SYSTEMS CodeMeter Runtime in multiple products".
FSA-202304
Festo: MSE6-C2M/D2M/E2M Incomplete User Documentation of Remote Accessible Functions
Gepubliceerd
5 september 2023
Laatste update
1 oktober 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Incomplete user documentation of undocumented, authenticated test mode and further remote accessible functions. The supported features may be covered only partly by the corresponding user documentation. Festo developed the products according to the respective state of the art. As a result, the protocols used no longer fully meet today's security requirements. The products are designed and developed for use in sealed-off (industrial) networks. If the network is not adequately sealed off, unauthorized access to the product can cause damage or malfunctions, particularly Denial of Service (DoS) or loss of integrity.
Mitigatiesamenvatting
Update of user documentation in next product version.
Revisiegeschiedenis (2)
Initiële publicatie — 5 september 2023
Initial revision.
Update A — 1 oktober 2025
Adjusted to VDE template. Changed title from "MSE6-C2M/D2M/E2M Incomplete User Documentation of Remote Accessible Functions" to "Festo: MSE6-C2M/D2M/E2M Incomplete User Documentation of Remote Accessible Functions".
Gepubliceerd
29 augustus 2023
Laatste update
1 oktober 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
A vulnerability in the Video.js package could allow a user of LX Appliance, with a high privilege account (i.e., with the "Teacher" role), to craft a malicious course and launch an XSS attack.
Mitigatiesamenvatting
Contact Festo Didactic services department at services.didactic@festo.com to update your LX Appliance to the latest version.
Revisiegeschiedenis (2)
Initiële publicatie — 29 augustus 2023
Initial revision.
Update A — 1 oktober 2025
Adjusted to VDE template. Changed title from "Video.js Cross-Site-Scripting (XSS) vulnerability in LX Appliance" to "Festo: Cross-Site-Scripting (XSS) vulnerability in LX-Appliance".
Gepubliceerd
17 oktober 2023
Laatste update
1 oktober 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
A vulnerability was reported in Siemens TIA Portal. TIA Portal is part of the installation packages of several Festo Didactic products. TP 260 before June 2023 and MES PC based on DELL XE3 contain a vulnerable versions of TIA Portal V15 to V18. Affected products of TIA Portal contain a path traversal vulnerability that could allow the creation or overwrite of arbitrary files in the engineering system.
Mitigatiesamenvatting
Update TIA-Portal. Please refer to Siemens SSA-116924 for more details.
Revisiegeschiedenis (2)
Initiële publicatie — 17 oktober 2023
Initial revision.
Update A — 1 oktober 2025
Adjusted to VDE template. Changed title from "Vulnerable Siemens TIA-Portal in several Festo Didactic Products" to "Festo: Vulnerable Siemens TIA-Portal in multiple Festo Didactic products".
FSA-202101
Festo: Multiple vulnerabilities in Ethernet/IP Stack of SBRD-Q/SBOC-Q/SBOI-Q
Gepubliceerd
22 september 2021
Laatste update
26 augustus 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
The affected product families are cameras SBOC/SBOI and the Controller SBRD. The vulnerabilities are located within the Ethernet IP Stack from EIPStackGroup OpENer Ethernet/IP.
Mitigatiesamenvatting
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet. - Deactivate EtherNet/IP in device settings if not used
Revisiegeschiedenis (3)
Initiële publicatie — 28 september 2021
Initial revision.
Update A — 11 januari 2024
Adjust link to VDE Advisory
Update B — 26 augustus 2025
Adjusted to VDE template. Changed document title from 'Vulnerability in Ethernet/IP Stack of SBRD-Q/SBOC-Q/SBOI-Q' to 'Festo: Multiple vulnerabilities in Ethernet/IP Stack of SBRD-Q/SBOC-Q/SBOI-Q'. Updated legal disclaimer to add references to special provisions.". Updated vulnerability notes and mitigation information. Updated legal disclaimer to add references to special provisions.
FSA-202207
Festo: CPX-CEC-C1 and CPX-CMXX, Missing Authentication for Critical Webpage Function
Gepubliceerd
20 september 2022
Laatste update
28 juli 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Unauthenticated access to critical webpage functions (e.g. reboot) may cause a denial of service of the device.
Mitigatiesamenvatting
Currently no fix is planned. Festo recommends limiting access to the webserver (tcp port 80) of the device to what is absolutely necessary. Replace CPX-CEC-C1 with follow-up product CPX-CEC-C1-V3. Replace CPX-CMXX with follow up product CPX-CEC-M1-V3.
Revisiegeschiedenis (4)
Initiële publicatie — 20 september 2022
Initial revision.
Update A — 19 oktober 2022
Added Control block-Set CPX-CEC-C1 and Control block-SET CPX-CMXX to affected products.
Update B — 11 januari 2024
Adjust link to VDE Advisory
Update C — 28 juli 2025
Adjusted to VDE template. Change title from 'CPX-CEC-C1 and CPX-CMXX, Missing Authentication for Critical Webpage Function' to 'Festo: CPX-CEC-C1 and CPX-CMXX, Missing Authentication for Critical Webpage Function'. Updated legal disclaimer to add references to special provisions. Remediations were consolidated into one.
FSA-202203
Festo: Controller CECC-S,LK,D family firmware 2.4.2.0 - multiple vulnerabilities in CODESYS V3 runtime system
Gepubliceerd
18 juli 2022
Laatste update
10 juli 2025
Gekoppelde CVE's
Getroffen sectoren
Energieopwekking
Risk evaluation
The Festo controller CECC product family in firmware version 2.4.2.0 is affected by multiple vulnerabilities in the CODESYS V3 runtime.
Mitigatiesamenvatting
No fix planned. This issue will be handled with next hardware generation release.
Revisiegeschiedenis (3)
Initiële publicatie — 18 juli 2022
Initial version.
Update A — 11 januari 2024
Adjust link to VDE Advisory, TLP and update some CVE information, where CVSS was not known before.
Update B — 10 juli 2025
Adjusted to VDE template. Changed document title from 'Festo Controller CECC-S,-LK,-D Family Firmware = 2.4.2.0 - Multiple Vulnerabilities in CODESYS V3 Runtime System' to' Festo: Controller CECC-S,LK,D family firmware 2.4.2.0 - multiple vulnerabilities in CODESYS V3 runtime system'. Updated legal disclaimer to add references to special provisions.
Gepubliceerd
6 juli 2022
Laatste update
23 juni 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
The Festo controller CECC-X-M1 product family in multiple versions are affected by a preauthentication command injection vulnerability. Update A, 2022-07-05 Remediation has been updated. Fixed firmwares are now available.
Mitigatiesamenvatting
Please update to firmware versions as described below: | Product | Product Details | Fixed in version | |-----------------------------|-----------------------------------------------------------|------------------| | Controller CECC-X-M1 | Festo:Partnumber:4407603 Festo:Ordercode:CECC-X-M1 | 3.8.18 | | Controller CECC-X-M1 | Festo:Partnumber:8124922 Festo:Ordercode:CECC-X-M1 | 4.0.18 | | Controller CECC-X-M1-MV | Festo:Partnumber:4407605 Festo:Ordercode:CECC-X-M1-MV | 3.8.18 | | Controller CECC-X-M1-MV | Festo:Partnumber:8124923 Festo:Ordercode:CECC-X-M1-MV | 4.0.18 | | Controller CECC-X-M1-MVS1 | Festo:Partnumber:4407606 Festo:Ordercode:CECC-X-M1-MV-S1 | 3.8.18 | | Controller CECC-X-M1-MVS1 | Festo:Partnumber:8124924 Festo:Ordercode:CECC-X-M1-MV-S1 | 4.0.18 | | Controller CECC-X-M1-YYJKP | Festo:Partnumber:4803891 Festo:Ordercode:CECC-X-M1-YYJKP | 3.8.18 | | Controller CECC-X-M1-YSL1 | Festo:Partnumber:8082793 Festo:Ordercode:CECC-X-M1-YS-L1 | 3.8.18 | | Controller CECC-X-M1-YSL2 | Festo:Partnumber:8082794 Festo:Ordercode:CECC-X-M1-YS-L2 | 3.8.18 | | Servo Press Kit YJKP | Festo:Partnumber:8077950 Festo:Ordercode:YJKP | 3.8.18 | | Servo Press Kit YJKP | Festo:Partnumber:8058596 Festo:Ordercode:YJKP | 3.8.18 |
Revisiegeschiedenis (3)
Initiële publicatie — 6 juli 2022
Initial revision.
Update A — 5 juni 2025
Fix: quotation mark
Update B — 23 juni 2025
Changed Document ID
Gepubliceerd
28 november 2023
Laatste update
13 mei 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
A vulnerability in the Wibu CodeMeter Runtime, which is part of the installation packages of several Festo products, was found. An attacker exploiting the vulnerability in WIBU CodeMeter Runtime in server mode could gain full access to the affected server via network access without any user interaction. This could lead to remote code execution and escalation of privileges giving full admin access on the host system for an already authenticated user (logged in locally to the PC).
Mitigatiesamenvatting
Update CodeMeter Runtime to version >= 7.60c The latest version of CodeMeter Runtime can be downloaded from WIBU System's web site.
Revisiegeschiedenis (3)
Initiële publicatie — 28 november 2023
Initial version
Update A — 5 december 2023
Removed 'MES4 (v3)', 'MES4 (<=v2)' and 'Energy-PC' from affected products as they do not install WIBU CodeMeter Runtime.
Update B — 13 mei 2025
Adjusted to VDE template and updated information on fixed version of the Festo Automation Suite. Changed document title from 'Vulnerable Wibu CodeMeter Runtime in Several Festo Products' to 'Festo: Vulnerable WIBU-SYSTEMS CodeMeter Runtime in several products'. Updated legal disclaimer to add references to special provisions.
FSA-202406
Several Codesys Gateway v2 vulnerabilities in Codesys provided by Festo
Gepubliceerd
3 december 2024
Laatste update
3 december 2024
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
An unauthenticated attacker would be able to send crafted requests to cause the CODESYS Gateway Server V2 to allocate excessive memory or consume all available TCP client connections. Besides, passwords are insufficiently checked during login. All versions of the following CODESYS V2 product prior version V2.3.9.38 are affected: • CODESYS Gateway Server
Mitigatiesamenvatting
Enable password protection at login in case no password is set at the controller. Please note that the password configuration file is not covered by the default FFT backup and restore mechanism. You must select the related file manually.
Revisiegeschiedenis (2)
Initiële publicatie — 3 december 2024
Initial version
Update A — 3 december 2024
One reference has been corrected