Kwetsbaarheden worden geladen…
Kwetsbaarheden worden geladen…
CVE-2020-12510
The default installation path of the TwinCAT XAR 3.1 software in all versions is underneath C:\TwinCAT. If the directory does not exist it and further subdirectories are created with permissions which allow every local user to modify the content. The default installation registers TcSysUI.exe for automatic execution upon log in of a user. If a less privileged user has a local account he or she can replace TcSysUI.exe. It will be executed automatically by another user during login. This is also true for users with administrative access. Consequently, a less privileged user can trick a higher privileged user into executing code he or she modified this way. By default Beckhoff’s IPCs are shipped with TwinCAT software installed this way and with just a single local user configured. Thus the vulnerability exists if further less privileged users have been added.
Dit record: live koppeling— laatst opgehaald: 7 november 2026 om 14:22.
Leverancier
Gepubliceerd
19 november 2020
Laatst gewijzigd
17 juni 2026
Rechtstreeks overgenomen uit NVD, CISA of de leverancier — soms Engelstalig, ongewijzigd t.o.v. de bron.
The default installation path of the TwinCAT XAR 3.1 software in all versions is underneath C:\TwinCAT. If the directory does not exist it and further subdirectories are created with permissions which allow every local user to modify the content. The default installation registers TcSysUI.exe for automatic execution upon log in of a user. If a less privileged user has a local account he or she can replace TcSysUI.exe. It will be executed automatically by another user during login. This is also true for users with administrative access. Consequently, a less privileged user can trick a higher privileged user into executing code he or she modified this way. By default Beckhoff’s IPCs are shipped with TwinCAT software installed this way and with just a single local user configured. Thus the vulnerability exists if further less privileged users have been added.
CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H
Attack vector
LOCAL
Privileges required
LOW
User interaction
REQUIRED
Vertrouwelijkheid
Hoog
Integriteit
Hoog
Beschikbaarheid
Hoog
Kans op misbruik binnen 30 dagen
0.9%
Percentiel
59e
Bron: FIRST.org, bijgewerkt op 6 november 2026.
Please consider the solution described with the next section (title 'Solution') for new installations only and installations for which it is acceptable to reinstall TwinCAT. For existing installations a script is provided for download at the following link: https://download.beckhoff.com/download/Document/product-security/Advisories/advisory-2020-003/cve-2020-12510.zip external link It changes the permissions of a directory of an already installed TwinCAT 3.1 installation. More precisely, it reads the current permissions of 'C:\Program Files' and copies them to the directory '3.1\System' underneath the installation path of TwinCAT (default 'C:\TwinCAT\3.1\System'). The procedure to use that script is as follows: 1. Download the script, unzip it, and copy it to the IPC. 2. On the IPC log in as administrator and open a PowerShell (Windows-Key + R + 'PowerShell'). 3. At the PowerShell enter the following command to temporarily allow the execution of scripts: set-executionpolicy -ExecutionPolicy Unrestricted -Scope Process (The effect of this is limited to the life-time of the current shell window because of '-Scope Process'.) 4. Then change to the path to where you downloaded the script and execute it: .\cve-2020-12510.ps1 The expected output is 'Copied the permissions from C:\Program Files to \3.1\System'. 5. Close the PowerShell and log out from the IPC as needed. It is safe to apply the script several times. It is safe to run it during full operation of TwinCAT XAR 3.1. There is no need to reboot the IPC afterwards. There is no need to periodically run the script. Future updates of TwinCAT 3.1 will either not touch the permissions which are set by the script or apply more appropriate ones. To apply the procedure to a set of IPCs you can prepare a USB stick with the content of the ZIP file 'cve-2020- 12510.zip' (see download URL above). Then the procedure for each IPC is: 1. Log in as administrator on the IPC. 2. Open the USB stick with the File Explorer (formerly known as Windows Explorer). 3. Double click on the file 'run-cve-2020-12510.bat'. (This simply invokes the PowerShell to execute the script already described above.)
Onze eigen Nederlandstalige interpretatie en context bij de brondata hierboven.
IACS Radar-duiding
Onze eigen interpretatie en context bij deze kwetsbaarheid — geen officiële bron.
IACS Radar-prioriteringsscore
Gebaseerd op CVSS 7.3, EPSS 0.9%, industriële relevantie 55/100.
Weegt CVSS, EPSS, KEV-status, industriële relevantie en exposure-relevantie samen — een aanvulling op, geen vervanging van, de losse scores hieronder en hierboven.
Voorwaarden voor misbruik
Operationele impact & energierelevantie
Mogelijk verlies van zicht op of besturing over het proces bij succesvol misbruik.
Beoordeeld als relevant voor de energiesector op basis van: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Leverancier "Beckhoff" is een bekende leverancier van apparatuur voor de energiesector.
Aanbevolen defensieve maatregelen
Industriële relevantiescore
Classificatie is voorlopig; handmatige verificatie door een OT-securityanalist wordt aanbevolen.
Geclassificeerd door IACS Radar-analysepijplijn (geautomatiseerd) op 7 november 2026.
IEC 62443-mapping
Automatische IACS Radar-duiding op basis van de gerapporteerde CWE-zwakteclassificatie; geen officiële certificeringsuitspraak.