CVE-2025-3756
A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially crafted 61850 packet, forcing the communication interfaces of the PM 877, CI850 and CI868 modules into fault mode or causing unavailability of the S+ Operations 61850 connectivity, resulting in a denial-of-service situation. The System 800xA IEC61850 Connect is not affected. Note: This vulnerability does not impact on the overall availability and functionality of the S+ Operations node, only the 61850 communication function. This issue affects AC800M (System 800xA): from 6.0.0x through 6.0.0303.0, from 6.1.0x through 6.1.0031.0, from 6.1.1x through 6.1.1004.0, from 6.1.1x through 6.1.1202.0, from 6.2.0x through 6.2.0006.0; Symphony Plus SD Series: A_0, A_1, A_2.003, A_3.005, A_4.001, B_0.005; Symphony Plus MR (Melody Rack): from 3.10 through 3.52; S+ Operations: 2.1, 2.2, 2.3, 3.3.
Dit record: live koppeling— laatst opgehaald: 24 september 2026 om 04:09.
Rechtstreeks overgenomen uit NVD, CISA of de leverancier — soms Engelstalig, ongewijzigd t.o.v. de bron.
A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially crafted 61850 packet, forcing the communication interfaces of the PM 877, CI850 and CI868 modules into fault mode or causing unavailability of the S+ Operations 61850 connectivity, resulting in a denial-of-service situation. The System 800xA IEC61850 Connect is not affected. Note: This vulnerability does not impact on the overall availability and functionality of the S+ Operations node, only the 61850 communication function. This issue affects AC800M (System 800xA): from 6.0.0x through 6.0.0303.0, from 6.1.0x through 6.1.0031.0, from 6.1.1x through 6.1.1004.0, from 6.1.1x through 6.1.1202.0, from 6.2.0x through 6.2.0006.0; Symphony Plus SD Series: A_0, A_1, A_2.003, A_3.005, A_4.001, B_0.005; Symphony Plus MR (Melody Rack): from 3.10 through 3.52; S+ Operations: 2.1, 2.2, 2.3, 3.3.
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Attack vector
NETWORK
Privileges required
NONE
User interaction
NONE
Vertrouwelijkheid
Geen
Integriteit
Geen
Beschikbaarheid
Hoog
Kans op misbruik binnen 30 dagen
0.2%
Percentiel
8e
Bron: FIRST.org, bijgewerkt op 23 september 2026.
ABB advises all customers to review their installations to determine if they are using an impacted product as listed above, no further analysis or tools are needed to make this determination. The recommended immediate actions per product are listed below: - CI868 (for AC 800M) Devices with firmware versions reported in Affected products are vulnerable. All the vulnerabilities will be corrected in 6.1.1 and 7.0 tracks for 800xA. AC 800M 6.1.1-3 is planned for Q2 2027, AC 800M 7.0 has been released in December 2025. - CI850 (for Symphony Plus SD Series) Devices with firmware versions reported in Affected products are vulnerable. All the vulnerabilities will be corrected in version C_0 or later (planned Q2 2026). - PM 877 (Symphony Plus MR) Devices with firmware versions reported in Affected products are vulnerable. All the vulnerabilities will be corrected with firmware version 3.53 or later (planned Q1 2026). - S+ Operations Versions reported in Affected products are vulnerable. All the vulnerabilities will be corrected in version 3.4 or later (released in January 2026). ABB recommends customers apply updates, as they become available, at their earliest convenience. It is also advisable to review the Mitigating Factors, Workarounds and General security recommendations sections for additional actions which may help reduce overall risk.
Onze eigen Nederlandstalige interpretatie en context bij de brondata hierboven.
IACS Radar-duiding
Onze eigen interpretatie en context bij deze kwetsbaarheid — geen officiële bron.
IACS Radar-prioriteringsscore
Gebaseerd op CVSS 6.5, EPSS 0.2%, industriële relevantie 70/100.
Weegt CVSS, EPSS, KEV-status, industriële relevantie en exposure-relevantie samen — een aanvulling op, geen vervanging van, de losse scores hieronder en hierboven.
Voorwaarden voor misbruik
Operationele impact & energierelevantie
Mogelijk verlies van zicht op of besturing over het proces bij succesvol misbruik.
Beoordeeld als relevant voor de energiesector op basis van: Vermeld in een officiële CISA ICS Advisory, wat directe relevantie voor industriële besturingssystemen bevestigt. Leverancier "ABB" is een bekende leverancier van apparatuur voor de energiesector. Beschrijving noemt een industrieel protocol dat typisch is voor elektriciteitsnetten (iec61850).
Aanbevolen defensieve maatregelen
Industriële relevantiescore
Automatisch geclassificeerd als industrieel relevant op basis van CISA/NVD-signalen (zie redenen).
Geclassificeerd door IACS Radar-analysepijplijn (geautomatiseerd) op 24 september 2026.
IEC 62443-mapping
Automatische IACS Radar-duiding op basis van de gerapporteerde CWE-zwakteclassificatie; geen officiële certificeringsuitspraak.