VDE-2024-048
Beckhoff: Improper neutralization of input in IPC-Diagnostics-www package included in TwinCAT/BSD operating system
Risk evaluation
By default, TwinCAT/BSD-based products have a device-specific web interface for web-based management (WBM) enabled, developed by Beckhoff and known as Beckhoff Device Manager UI. It can be accessed remotely or locally. When accessed locally, the user can bypass input validation by entering specially crafted inputs into the user interface for certain pages, which then allows local commands to be executed with administrative privileges.
Mitigation summary
Avoid the existence of user accounts with login permission on the target other than administrator access. By default, TwinCAT/BSD has preconfigured user accounts with lower privileges, but none of them have a password, which results in them being denied login access. Avoid running third-party applications on the target that have not been properly audited, regardless of the user they are running as.
Revision history (4)
Initial publication — 13 August 2024
initial revision
Update A — 6 November 2024
Fix: correct certvde domain, added self-reference
Update B — 16 January 2025
Fix: list of branches
Update C — 11 April 2025
Fix: version range
VDE-2021-008
Beckhoff: Stack Overflow and XXE vulnerability in various OPC UA products
Beckhoff — TwinCAT OPC UA Client System Manager Extension included in TF6100
Published
21 October 2024
Last update
22 May 2025
Linked CVEs
Affected sectors
Risk evaluation
The affected products can act as OPC UA client or server and are vulnerable to two different kind of attacks via the OPC UA protocol. For both cases the attacker can send packets via the OPC UA protocol without the need to authenticate and 1. provoke a stack overflow resulting in denial of service of the product or 2. make the product disclose information to the attacker without authorization.
Mitigation summary
Consider limiting access to the network communication ports of affected server products. Also consider limiting where the affected client products are allowed to connect to. For example, this can be achived with Windows' built-in firewall by incoming rules for servers and outgoing rules for clients. Consider to minimize the ability of an attacker to hijack communication establishment from a client to a server. For example this can be achieved with the help of zones and conduits: Try to keep servers and clients within the same network zone and prevent intrusion into that zone. Try to enclose communication establishment within conduits like VPN channels (where one conduit can serve for many OPC UA connections) and prevent attackers from intruding into such channels. Consider updating the .NET Framework.
Revision history (4)
Initial publication — 19 May 2021
Initial revision.
Update A — 16 January 2025
Fix: list of branches, references
Update B — 11 April 2025
Fix: version range
Update C — 22 May 2025
Fix: quotation mark
VDE-2024-050
Beckhoff: Denial-of-Service vulnerability in the MDP package included in TwinCAT/BSD operating system
Risk evaluation
By default, TwinCAT/BSD-based products have a device-specific web interface for web-based management (WBM) enabled, developed by Beckhoff and known as Beckhoff Device Manager UI. It can be accessed remotely or locally. When accessed locally, a user can post specifically crafted input which then causes a buffer overflow on stack which in turn lets the process 'MDPService' crash such that the web interface becomes unavailable until next restart or even execute code in the context of user 'root'.
Mitigation summary
Avoid the existence of user accounts with login permission on the target other than administrator access. By default, TwinCAT/BSD has preconfigured user accounts with lower privileges, but none of them have a password, which results in them being denied login access. Avoid running third-party applications on the target that have not been properly audited, regardless of the user they are running as.
Revision history (4)
Initial publication — 13 August 2024
initial revision
Update A — 6 November 2024
Fix: correct certvde domain, added self-reference
Update B — 16 January 2025
Fix: list of branches, typo in reference url
Update C — 11 April 2025
Fix: version range
Risk evaluation
The coupler's function could be inhibited by an attack.
Mitigation summary
Beckhoff will not change this behaviour. Customers should configure a perimeter firewall to block traffic from untrusted networks to the device.
Revision history (4)
Initial publication — 10 March 2020
Initial revision.
Update A — 16 January 2025
Fix: list of branches, typo in references url
Update B — 11 April 2025
Fix: version range
Update C — 22 May 2025
Fix: quotation mark
VDE-2024-045
Beckhoff: Local authentication bypass in IPC-Diagnostics package included in TwinCAT/BSD operating system
Risk evaluation
By default, TwinCAT/BSD-based products have a device-specific web interface for web-based management (WBM) enabled, developed by Beckhoff and known as Beckhoff Device Manager UI. It can be accessed remotely or locally. When accessed locally, the authentication mechanism for the web interface can be bypassed by any local user, regardless of their permissions, and they can act with administrative access rights via this mechanism.
Mitigation summary
Avoid the existence of user accounts with login permission on the target other than administrator access. By default, TwinCAT/BSD has preconfigured user accounts with lower privileges, but none of them have a password, which results in them being denied login access. Avoid running third-party applications on the target that have not been properly audited, regardless of the user they are running as.
Revision history (4)
Initial publication — 13 August 2024
initial revision
Update A — 6 November 2024
Fix: correct certvde domain, added self-reference
Update B — 16 January 2025
Fix: list of branches, references url
Update C — 11 April 2025
Fix: version range
VDE-2023-067
Beckhoff: Open redirect in TwinCAT/BSD package authelia-bhf
Risk evaluation
With TwinCAT/BSD based products the HTTPS request to the Authelia login page accepts user-controlled input that specifies a link to an external site.
Mitigation summary
Use firewall or web-proxy technology at your network perimeter which allow internal clients to access only trusted external sites directly.
Revision history (2)
Initial publication — 13 December 2023
initial revision
Update A — 22 May 2025
Fix: added distribution, quotation mark
VDE-2024-049
Beckhoff: Denial-of-Service vulnerability in the IPC-Diagnostics package included in TwinCAT/BSD operating system
Risk evaluation
By default, TwinCAT/BSD-based products have a device-specific web interface for web-based management (WBM) enabled, developed by Beckhoff and known as Beckhoff Device Manager UI. It can be accessed remotely or locally. When accessed locally, a user can post specifically crafted input which then lets the process 'MDPWebServer' consume a maximum of CPU cycles and Random Access Memory (RAM).
Mitigation summary
Avoid the existence of user accounts with login permission on the target other than administrator access. By default, TwinCAT/BSD has preconfigured user accounts with lower privileges, but none of them have a password, which results in them being denied login access. Avoid running third-party applications on the target that have not been properly audited, regardless of the user they are running as.
Revision history (4)
Initial publication — 13 August 2024
initial revision
Update A — 6 November 2024
Fix: correct certvde domain, added self-reference
Update B — 16 January 2025
Fix: list of branches, references url
Update C — 11 April 2025
Fix: version range
VDE-2020-019
Beckhoff: EtherLeak in TwinCAT RT network driver
Risk evaluation
Beckhoff's TwinCAT RT network driver for Intel 8254x and 8255x is providing EtherCAT functionality. The driver implements real-time features. Except for Ethernet frames sent from real-time functionality, all other Ethernet frames sent through the driver are not padded if their payload is less than the minimum Ethernet frame size. Instead, arbitrary memory content is transmitted within in the padding bytes of the frame. Most likely this memory contains slices from previously transmitted or received frames.
Mitigation summary
Beckhoff offers software patches for TwinCAT 3.1 and TwinCAT 2.11 on request. These patches will be included in the the next regular releases to the affected software versions. The advisory will be updated upon availability.
Revision history (4)
Initial publication — 16 June 2020
Initial revision.
Update A — 6 November 2024
Fix: added self-reference
Update B — 11 April 2025
Fix: version range
Update C — 22 May 2025
Fix: added distribution, quotation mark
Published
23 January 2024
Last update
22 May 2025
Affected sectors
Risk evaluation
The TRUMPF products that are listed above contain a vulnerable version of Notepad++. This version isbeing installed for support purposes only, so there is no danger of triggering this vulnerability inNotepad++ during normal operations. Nevertheless, TRUMPF recommends mitigation of thisvulnerability.When editing a specially crafted file containing UTF-8 characters in Notepad++ (Versions up to 8.5.6) and converting that file to UTF-16, a buffer overflow vulnerability can be exploited that allows an attacker to execute arbitrary code to take over the whole system.
Mitigation summary
For additional questions please contact your TRUMPF Service with the PR number 501709.
Revision history (2)
Initial publication — 23 January 2024
Initial revision.
Update A — 22 May 2025
Fix: quotation mark
Risk evaluation
The versions of TRUMPF products stated below are including a version of log4net that's prone to XXE (External XML Entities) attacks under certain circumstances. This means, the log4net code can be tricked into loading externally hosted, potentially malicious XML code and possibly executing it. This vulnerability allows for the execution of remote XML code, possibly resulting in unauthorized (remote) access to, change of data or disruption of the whole system running the vulnerable application.
Mitigation summary
New versions are available for the affected products. Install new versions as provided by TRUMPF SE + Co. KG. To aquire these versions please contact your TRUMPF Service with the PR number 500879.
Revision history (2)
Initial publication — 22 April 2025
Initial version
Update A — 22 May 2025
Fix: added distribution, quotation mark
VDE-2022-049
TRUMPF: Multiple products prone to X.Org server vulnerabilities
Risk evaluation
TruControl laser control software from versions 1.60.0 to 3.40.0 use a vulnerable X.Org server versions. The affected X.Org vulnerability is not validating the request length properly for the handler 'ProcXkbSetGeometry'. An authenticated Attacker could craft a request which could lead to memory out-of bounds write.
Mitigation summary
Securing the access to the production network. Please contact your service partner (service.tls@trumpf.com) for instructions on how to get automatically informed for the new major release 3.42.0 of the new TruControl software version.
Revision history (2)
Initial publication — 7 November 2022
Initial revision.
Update A — 22 May 2025
Fix: quotation mark
Risk evaluation
Unquoted Windows search path vulnerability in the below mentioned Software for Windows might allow local users to gain privileges via a malicious .exe file.
Mitigation summary
Ensure that Registry can only be accessed with administrator privileges. HOPCS: Install in a path without spaces and/or select a user with low privileges in the DCOM settings dcomcnfg/Identity. When using X-OPC or X-OTS it is recommended to protect the user program, with the system variables (see Automation Security Manual '3.2.2.2 Access Restrictions'): - Forcing Deactivation - Read-only in RUN - Reload Deactivation
Revision history (2)
Initial publication — 16 January 2023
Initial revision.
Update A — 22 May 2025
Fix: quotation mark
VDE-2024-013
HIMA: Multiple products affected by DoS and Port-Based-VLAN Crossing
Published
13 February 2024
Last update
22 May 2025
Linked CVEs
Affected sectors
Risk evaluation
CVE-2024-24781: If the above mentioned products are loaded with Wire speed (1Gbit/s or 100Mbit/s) the resources of the Ethernet-Controller are exhausted and it must be reset by the system automatically after load disappears. This leads to an interruption (DoS) of all other communications of the affected Ethernet-Controller. CVE-2024-24782: Most of the above mentioned products offer a VLAN feature. This helps to segregate ports of the switch included in each of the products. VLAN are meant to segregate networks. Furthermore a MAC-learning mode called 'conservative' is provided. In this mode the ARP table is updated earliest within 1..2 times ARP aging time. X-SB 01 (985210207) is not affected by this CVE.
Mitigation summary
CVE-2024-24781: All load limiting measures are helpful (e.g. in external devices or also in the switch of the above mentioned products). Please check whether the reduced speed is still sufficient for the desired application. Protect the network with segregation measures and restrict the access of unauthorized network participants (e.g. close unused ports) CVE-2024-24782: Switching the MAC-learning from 'conservative' to 'tolerant' mitigates the above described vulnerability but leads to potential IP-Spoofing and ARP-Poisoning and should therefore be avoided. HIMax and HIQuad X systems can be setup in the way that real physical segregation (between different modules) is used. E.g. it is impossible to ping from one X-COM to another X-COM in the same Rack. HIMatrix should be used in that way that CPU and COM are NOT connected via VLAN e.g. CPU connected to Port 1 and 2, COM Connected to Port 3 and 4.
Revision history (2)
Initial publication — 13 February 2024
Initial revision.
Update A — 22 May 2025
Fix: quotation mark
Risk evaluation
Weidmueller product ResMa is affected by ASP.NET AJAX vulnerability. Weidmueller has released a new firmware for the affected product to fix the vulnerability.
Mitigation summary
Update to version V3.7.4
Revision history (1)
Initial publication — 19 May 2025
Initial version
VDE-2024-033
PEPPERL+FUCHS: Device Master ICDM-RX/* – Vulnerability may allow unauthenticated remote attacker information disclosure and denial of service
Published
13 August 2024
Last update
14 May 2025
Linked CVEs
Affected sectors
Risk evaluation
Vulnerabilities have been discovered in the product, mainly caused by HTML injection and crosssite-scripting. The impact of the vulnerability on the affected device may result in an information disclosure and denial of service.
Mitigation summary
Update to a new version of the firmware you are using: * SocketServer v11.66 * PROFINET v3.4.10 * PROFINET/Modbus v1.0.8 * EtherNet/IP v7.23 * EIP/Modbus v1.09 * Modbus Router v7.10 * Modbus Server v7.12 * Modbus TCP v7.12
Revision history (3)
Initial publication — 13 August 2024
Initial revision.
Update A — 6 November 2024
Fix: correct certvde domain, added self-reference
Update B — 14 May 2025
Fix: version space
VDE-2020-014
Pepperl+Fuchs: Kr00k vulnerabilities in Broadcom Wi-Fi chipsets
Risk evaluation
Security researchers at ESET have reported a vulnerability called Kr00k (CVE-2019- 15126) which affects encrypted WiFi traffic for devices using Broadcom or Cypress chipsets. The vulnerability may allow an attacker to decrypt some WPA2- Personal/Enterprise traffic by forcing an AP/client to start utilizing an all-zero encryption key (similar to KRACK vulnerability).
Mitigation summary
Pepperl+Fuchs is continuously and rigorously working closely with our partner to patch all affected Devices. Update for Tab-Ex 02 is planned for 05/2020 ECOM mobile devices are normally used in the corporate network. This implies that outgoing connections and local software installations have to be configured by administrators. It should be ensured that the data connections are additionally encrypted, e.g. HTTPS or SSH.
Revision history (2)
Initial publication — 31 March 2020
Initial revision.
Update A — 14 May 2025
Fix: version space
Risk evaluation
Weidmüller product PROCON-WIN is affected by hard-coded credentials. Weidmüller has released a new version of the affected product to fix the vulnerability.
Mitigation summary
Update to 5.7.14.1
Revision history (2)
Initial publication — 5 March 2025
Initial version
Update A — 14 May 2025
Fix: reference category
Published
29 June 2021
Last update
14 May 2025
Affected sectors
Risk evaluation
Multiple vulnerabilities in the WAGO I/O-Check Service were reported.
Mitigation summary
- Disable I/O-Check service - Restrict network access to the device. - Do not directly connect the device to the internet.
Revision history (4)
Initial publication — 29 June 2021
Initial revision.
Update A — 6 November 2024
Fix: added self-reference
Update B — 12 February 2025
Fix: corrected self-reference, fixed version
Update C — 10 April 2025
Fixed csaf publisher information
Risk evaluation
The following firmware versions installed on several devices are are vulnerable due to a vulnerability in CODESYS Control.
Mitigation summary
The vulnerability is only exploitable if the an attacker has successfully logged in with according user rights. To prevent attackers from exploiting the vulnerability it is recommend to change the standard password in the web based management.
Revision history (3)
Initial publication — 4 February 2025
Initial release.
Update A — 19 February 2025
Update: fixed typo in Vendor fix, fixed version
Update B — 14 May 2025
Fix: added distribution
VDE-2020-050
Pepperl+Fuchs: Multiple Products - Vulnerability may allow remote attackers to cause a Denial Of Service
Risk evaluation
Critical vulnerability has been discovered in the utilized component 499ES EtherNet/IP Stack by Real Time Automation (RTA).
Mitigation summary
An external protective measure is required. - Minimize network exposure for affected products and ensure that they are not accessible via the Internet. - Isolate affected products from the corporate network. - If remote access is required, use secure methods such as virtual private networks (VPNs).
Revision history (3)
Initial publication — 15 February 2021
Initial revision.
Update A — 10 April 2025
Fixed URLs.
Update B — 14 May 2025
Fix: added distribution
VDE-2021-006
Pepperl+Fuchs: Multiple Products - Vulnerability may allow remote attackers to cause a Denial Of Service
Risk evaluation
Critical vulnerability has been discovered in the utilized component PROFINET IO Device by Hilscher Gesellschaft für Systemautomation mbH. The impact of the vulnerability on the affected device is that it can - no longer perform acyclic requests - may drop all established cyclic connections may - disappear completely from the network. For more information see advisory by Hilscher: https://kb.hilscher.com/display/ISMS/2020-12-03+Denial+of+Service+vulnerability+in+PROFINET+IO+Device Update 20.11.2024: Products have been added
Mitigation summary
An external protective measure is required. - Minimize network exposure for affected products and ensure that they are not accessible via the Internet. - Isolate affected products from the corporate network. - If remote access is required, use secure methods such as virtual private networks (VPNs).
Revision history (3)
Initial publication — 16 February 2021
Initial revision.
Update A — 20 November 2024
Products have been added
Update B — 14 May 2025
Fix: added distribution
VDE-2021-026
Weidmueller: Multiple vulnerabilities in Industrial WLAN devices
Published
23 June 2021
Last update
14 May 2025
Linked CVEs
Affected sectors
Risk evaluation
Multiple issues in Weidmueller Industrial WLAN devices have been found. Initial publication date: 2021-06-23 Update A publication date: 2021-07-02 Update A CVE-2021-33534 CVSS: 7.2 (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H) Description: An exploitable command injection vulnerability exists in the hostname functionality of Weidmueller Industrial WLAN devices. A specially crafted entry to network configuration information can cause execution of arbitrary system commands, resulting in full control of the device. An attacker can send various requests while authenticated as a high privilege user to trigger this vulnerability.
Mitigation summary
For all potential vulnerabilities, customers can download a patched firmware to secure their Industrial WLAN devices properly. Please follow the procedure below to download and install the latest firmware for your device: 1. Use the link: [www.weidmueller.com](www.weidmueller.com) 2. Enter the product number of the Industrial WLAN device you want to update in the search field on the webpage and press "Enter". 3. On the next page, expand the drop-down menu **"Downloads"**. 4. Download the respective firmware from the download table. 5. Install the firmware on your device. Patched firmware versions for all affected products | Product number | Product name | Firmware version | |---------------|-----------------------------------|------------------------------------------| | 2536600000 | IE-WL-BL-AP-CL-EU | <= V1.16.21 (Build 21010513) | | 2536650000 | IE-WLT-BL-AP-CL-EU | <= V1.16.21 (Build 21010513) | | 2536660000 | IE-WL-BL-AP-CL-US | <= V1.16.21 (Build 21010513) | | 2536670000 | IE-WLT-BL-AP-CL-US | <= V1.16.21 (Build 21010513) | | 2536680000 | IE-WL-VL-AP-BR-CL-EU | <= V1.11.13 (Build 21010513) | | 2536690000 | IE-WLT-VL-AP-BR-CL-EU | <= V1.11.13 (Build 21010513) | | 2536700000 | IE-WL-VL-AP-BR-CL-US | <= V1.11.13 (Build 21010513) | | 2536710000 | IE-WLT-VL-AP-BR-CL-US | <= V1.11.13 (Build 21010513) | If a firmware update is available for your device, please follow the steps above to install it.
Revision history (4)
Initial publication — 23 June 2021
Initial revision.
Update A — 2 July 2021
Update A
Update B — 10 April 2025
Fix: change vendor name
Update C — 14 May 2025
Fix: added distribution
Risk evaluation
Multiple Vulnerabilities in a software service of shDIALUP can lead to arbitrary code execution due to improper privilege management. Update A, 2022-03-28 Updated CVSS score from CVE-2021-33527 from 7.8 to 9.8 due to new information about the vulnerability
Mitigation summary
Update shDialup to 3.9R0.5
Revision history (2)
Initial publication — 28 March 2021
initial revision
Update A — 14 May 2025
Fix: added distribution
Risk evaluation
The communication between e!Cockpit and the programmable logic controller is not encrypted. The broken cryptographic algorithm allows an attacker to decode the password for the e!Cockpit communication and with this to manipulate the application. The password used by e!Cockpit for authentication against the PLC is encrypted with a hard-coded key. An attacker is able to decrypt the password by listening to the network traffic.
Mitigation summary
* Follow the instructions in WAGO's handbook Cyber Security for Controller * Restrict network access to the device. * Do not directly connect the device to the internet * Use an encrypted VPN connection to the device * Disable unused TCP/UDP-ports Typically the e!Cockpit communication is only needed during commissioning of the programmable logic controller and not during normal operations. WAGO highly recommends disabling the TCP Port 11740 and UDP Port 1740 after commissioning or using an encrypted VPN connection to the device.
Revision history (3)
Initial publication — 9 March 2020
initial revision
Update A — 10 April 2025
Fixed namespace URL
Update B — 14 May 2025
Fix: added distribution
VDE-2020-028
WAGO: Authentication Bypass Vulnerability in WAGO 750-36X and WAGO 750-8XX Version <= FW03
Risk evaluation
The Web-Based Management (WBM) of WAGOs programmable logic controller (PLC) is typically used for administration, commissioning and updates. With special crafted requests it is possible to change some special parameters without authentication.
Mitigation summary
* Restrict network access to the device. * Do not directly connect the device to the internet. * Disable unused TCP/UDP ports. * Disable web-based management ports 80/443 after the configuration phase
Revision history (3)
Initial publication — 30 September 2020
initial revision
Update A — 10 April 2025
Fixed csaf reference URL
Update B — 14 May 2025
Fix: added distribution