Skip to content
IACS RadarIndustrial Cyber Exposure & Intelligence

CISA + vendors

ICS Advisories

Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.

499

Found

Advisory data: live connection— last retrieved: 20 November 2026 at 22:19.

Filters

499 advisories found

VDE-2025-042

Lenze: VPN Client Privilege Escalation in combination with Lenze x500 IoT Gateway

Lenze — x500

Lenze PSIRThigh

Published

27 May 2025

Last update

27 May 2025

Affected sectors

Risk evaluation

The Lenze VPN client is vulnerable to a Local Privilege Escalation to root/SYSTEM by executing a configuration file which can be controlled by a non-privileged user. This occurs through a race condition exploit, where an attacker can overwrite the temporary OpenVPN configuration file located in a world-writable directory. By injecting malicious commands into the configuration file prior to its execution by the VPN client, an attacker can trigger arbitrary code execution with root/system privileges when a VPN connection is initiated. The vulnerability has been remediated in the version 1.4.4 of the Lenze VPN client. Due to some further developments and completion of the functional scope, it is recommended to update the firmware of the x500 IoT Gateway devices immediately, regardless of the current security vulnerability in the VPN client.

Mitigation summary

Obtain the updated VPN software (version >= 1.4.4) from https://cloud.lenze.digital/fleet-manager/tools and run the installer on a windows and macOS system or run the following commands in an linux system: tar -xzf vpn_client_x64.tar.gz cd vpn_client_x64 sudo ./install

Revision history (1)
  1. Initial publication — 27 May 2025

    Initial version

Official source: Lenze PSIRT

VDE-2018-010

WAGO: Multiple vulnerabilities in e!DISPLAY products

WAGO — e!DISPLAY

WAGO PSIRThigh

Published

10 July 2018

Last update

22 May 2025

Affected sectors

Energieopwekking

Risk evaluation

An unauthenticated user can exploit a vulnerability (CVE-2018-12981) to inject code in the WBM via reflected cross-site scripting (XSS), if he is able trick a user to open a special crafted web site. This could allow an attacker to execute code in the context of the user and execute arbitrary commands with restriction to the permissions of the user. Authenticated users can use a vulnerability to inject code in the WBM via persistent cross-site scripting (XSS) via special crafted requests which will be rendered and/or executed in the browser. Authenticated WBM users can transfer arbitrary files to different file system locations (CVE- 2018-12980) to which the web server has the required permissions and partially allowing replacing existing files due weak file permissions (CVE-2018-12979) which can result in an authentication bypass.

Mitigation summary

Update your device to the latest firmware (FW 02). In case this is not feasible limit the access to trusted users and devices. For details on how to obtain the new firmware, please send a request by email to support@wago.com.

Revision history (3)
  1. Initial publication — 10 July 2018

    initial revision

  2. Update A — 16 January 2024

    added vendor name to title

  3. Update B — 22 May 2025

    Fix: removed ia, firmware category, version space, distribution, added distribution, quotation mark

Official source: WAGO PSIRT

VDE-2020-009

WAGO: e!Cockpit Two Update Package Vulnerabilities

WAGO — PFC100

WAGO PSIRThigh

Published

9 March 2020

Last update

22 May 2025

Affected sectors

Risk evaluation

The firmware update package (WUP) is not signed entirely. The used password offers no additional security, it is just meant to protect from unintentional modifications of the WUP file. Thus only the integrity of the signed firmware part (rauc file) is protected against intended manipulation. An attacker could manipulate the WUP file in a way that additional files with potentially malicious content are added to the WUP file. In case an authorized user that issues a firmware update could be tricked into installing this manipulated WUP file onto the device, the potentially malicious files would also be copied and installed on to the device and executed with elevated privileges.

Mitigation summary

Execute FW-Update only as user 'admin'.

Revision history (2)
  1. Initial publication — 9 March 2020

    initial revision

  2. Update A — 22 May 2025

    Fix: version space, quotation mark

Official source: WAGO PSIRT

VDE-2020-011

WAGO: Multiple Vulnerabilities in I/O-Check Service

WAGO — PFC100

WAGO PSIRThigh

Risk evaluation

An attacker needs an authorized login on the device in order to exploit the herein mentioned vulnerabilities. The reported vulnerabilities allow a local attacker with valid login credentials who is able to create files on the device to change the devices settings, e.g. default gateway address, time server etc. and potentially execute code.

Mitigation summary

* Disable I/O-Check service. * Restrict network access to the device. * Do not directly connect the device to the internet. * Disable unused TCP/UDP-ports.

Revision history (2)
  1. Initial publication — 9 March 2020

    Initial revision.

  2. Update A — 22 May 2025

    Fix: version space, quotation mark

Official source: WAGO PSIRT

VDE-2021-014

WAGO: Multiple Vulnerabilities in CODESYS Runtime 2.3

WAGO — PFC200

WAGO PSIRTcritical

Risk evaluation

Multiple vulnerabilities were reported in CODESYS 2.3 Runtime. The CODESYS 2.3 Runtime is an essential component in several WAGO PLC's.

Mitigation summary

If an immediate firmware update is not possible, the WLAN on the unit can also be switched off as a precautionary measure.

Revision history (2)
  1. Initial publication — 15 May 2021

    Initial revision.

  2. Update A — 22 May 2025

    Fix: version space, added distribution, quotation mark

Official source: WAGO PSIRT

VDE-2021-049

WAGO: Denial of Service Vulnerability in CODESYS Runtime 2.3

WAGO — PFC200

WAGO PSIRThigh

Published

16 November 2021

Last update

22 May 2025

Linked CVEs

Affected sectors

Risk evaluation

A Denial-of-Service Vulnerability was reported in CODESYS 2.3 Runtime. The CODESYS 2.3 Runtime is an essential component in several WAGO PLC's. All vulnerable PLCs are listed in chapter 'Affected Products'.

Mitigation summary

1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the CODESYS 2.3 port 2455.

Revision history (2)
  1. Initial publication — 16 November 2021

    initial revision

  2. Update A — 22 May 2025

    Fix: version space, added distribution, quotation mark

Official source: WAGO PSIRT

VDE-2021-060

WAGO: Smart Script affected by Log4Shell Vulnerability

WAGO — Smart Script

WAGO PSIRTcritical

Published

5 January 2022

Last update

22 May 2025

Affected sectors

Risk evaluation

Apache Log4j is used for logging events in WAGO Smart Script in Version 4.2 and higher. Events logged by Log4j can contain JNDI references. An attacker who can control log messages or log message parameters can execute arbitrary code loaded from LDAP servers when message lookup substitution is enabled. Additionally, Log4j does not protect from self-referential lookups, which can lead to Denial of Service. UPDATE A1/2: Affected versions: CVE-2021-44228 and CVE-2021-45046: WAGO Smart Script >= Version 4.2 and < Version 4.8.1.3 CVE-2021-45105: WAGO Smart Script >= Version 4.2 and < Version 4.8.1.4 CVE-2021-44832 WAGO Smart Script >= Version 4.2 and < Version 4.8.1.5 END UPDATE A1/2

Mitigation summary

Do not use projects from untrusted sources. For further impact information and risk mitigation, see the recommendations of the Apache Foundation https://logging.apache.org/log4j/2.x/security.html Bundesamt für Sicherheit in der Informationstechnik (BSI) https://www.bsi.bund.de/DE/Service-Navi/Presse/Pressemitteilungen/Presse2021/211211_log4Shell_WarnstufeRot.html

Revision history (3)
  1. Initial publication — 5 January 2022

    Initial revision.

  2. Update A — 9 February 2022

    Update

  3. Update B — 22 May 2025

    Fix: added distribution, quotation mark

Official source: WAGO PSIRT

VDE-2022-002

WAGO: Vulnerable WIBU-SYSTEMS Codemeter installed through e!COCKPIT and WAGO-I/O-Pro

WAGO — e!COCKPIT

WAGO PSIRThigh

Published

31 January 2022

Last update

22 May 2025

Linked CVEs

Affected sectors

Risk evaluation

A vulnerability is reported in WIBU-SYSTEMS Codemeter. WIBU-SYSTEMS Codemeter is installed by default during e!COCKPIT and WAGO-I/O-Pro (CODESYS 2.3) installations. All currently existing e!COCKPIT installation bundles and WAGO-I/O-Pro (CODESYS 2.3) installation bundles are affected with vulnerable versions of WIBU-SYSTEMS Codemeter.

Mitigation summary

Mitigation Use general security best practices to protect systems from local and network attacks. Disable the container type 'Mass Storage' in CodeMeter via the Windows Registry.

Revision history (2)
  1. Initial publication — 31 January 2022

    Initial revision.

  2. Update A — 22 May 2025

    Fix: quotation mark

Official source: WAGO PSIRT

VDE-2022-009

WAGO: Multiple Products affected by Linux Kernel Vulnerability Dirty Pipe

WAGO — PFC100

WAGO PSIRThigh

Published

6 April 2022

Last update

22 May 2025

Linked CVEs

Affected sectors

Risk evaluation

The Linux kernel starting from 5.8 has a flaw which can lead to privilege escalation for a local user. The kernel is used in several Versions of the FW of several WAGO products. All vulnerable PLCs are listed in chapter 'Affected Products'.

Mitigation summary

- Restrict network access to the device. - Use strong passwords - Do not directly connect the device to the internet - Disable unused TCP/UDP-ports

Revision history (2)
  1. Initial publication — 6 April 2022

    Initial revision.

  2. Update A — 22 May 2025

    Fix: quotation mark

Official source: WAGO PSIRT

VDE-2023-007

WAGO: Unauthenticated command execution via Web-based-management UPDATE A

WAGO — CC100

WAGO PSIRTcritical

Published

15 May 2023

Last update

22 May 2025

Linked CVEs

Affected sectors

Risk evaluation

The 'legal information' plugin of web-based-management contained a vulnerability which allowed execution of arbitrary commands with privileges of www user. UPDATE A 15.06.2023 : Removed PFC100 with FW23 as affected product and from solution PFC200 with FW23 is only affected on 750-821x/xxx-xxx Renamed "FW22 Patch 1" to "FW22 SP1" to match the versions of the download portal

Mitigation summary

As general security measures strongly WAGO recommends: Use general security best practices to protect systems from local and network attacks. Do not allow direct access to the device from untrusted networks. Update to the latest firmware according to the table in chapter solutions. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium (https://www.bsi.bund.de/SharedDocs/Downloads/EN/BSI/ICS/ICS-Security_compendium.pdf).

Revision history (2)
  1. Initial publication — 15 May 2023

    Initial revision.

  2. Update A — 22 May 2025

    Fix: quotation mark

Official source: WAGO PSIRT

VDE-2023-026

WAGO: Multiple products prone to multiple vulnerabilities in e!Runtime / CODESYS V3 Runtime

WAGO — CC100

WAGO PSIRThigh

Risk evaluation

Multiple WAGO devices are prone to vulnerabilites in the used CODESYS V3 framework.

Mitigation summary

Vulnerabilities of CODESYS Advisory 2023-02:• Please make sure that the 'port authentication' option in the web-based management is activated. In this way none of the vulnerabilities can be exploited by unauthenticated users.• Please change the default admin password. Vulnerability of CODESYS Advisory 2023-03:• This vulnerability exists in the CODESYS programming service which is needed for commission only. Deactivate the CODESYS programming port in the web-based management if you do not need the service. In addition to the mitigation hints CODESYS GmbH recommends the following general defense measures to reduce the risk of exploits: Use controllers and devices only in a protected environment to minimize network exposure and ensure they are not accessible from outside. Use firewalls to protect and separate the control system network from other networks. Use VPN (Virtual Private Networks) tunnels if remote access is required. Activate and apply user management and password features. Use encrypted communication links. Limit the access to both development and control system by physical means, operating system features, etc. Protect both development and control system by using up to date virus detection solutions. For further impact information and risk mitigation, please refer to the official CODESYS Advisory Website at https://www.codesys.com/security/security-reports.html

Revision history (2)
  1. Initial publication — 31 July 2023

    Initial revision.

  2. Update A — 22 May 2025

    Fix: quotation mark

Official source: WAGO PSIRT

VDE-2024-047

WAGO: Multiple vulnerabilities in docker configuration

WAGO — CC100

WAGO PSIRThigh

Risk evaluation

Nozomi reported eight vulnerabilities to WAGO affecting different firmwares installed on several devices.

Mitigation summary

Update to Firmware 4.6.1 (FW28) or for CC100 devices to 4.6.3 (FW28). For G1 devices update to Firmware 3.10.11 (FW22 Patch 2). For the latest Custom Firmware, please contact the WAGO support.

Revision history (4)
  1. Initial publication — 18 November 2024

    Initial document.

  2. Update A — 30 January 2025

    Added known mitigations as remediation. Added the Custom Firmware to the product branch. Added firmware 3.10.11 (Firmware 22 Patch 2) to the fixed products. This version was in revision 1 listed as vulnerable.

  3. Update B — 12 February 2025

    Fix: corrected self-reference, fixed version

  4. Update C — 22 May 2025

    Fix: quotation mark

Official source: WAGO PSIRT

VDE-2022-045

Pilz: PAS 4000 prone to ZipSlip

Pilz — PAS4000

Pilz PSIRTmiddel

Published

24 November 2022

Last update

22 May 2025

Affected sectors

Risk evaluation

PAS4000 is the software platform for the Automation System PSS 4000. PAS 4000 does not properly check pathnames contained in archives. An attacker can utilise this vulnerability to write arbitrary files, potentially leading to code execution.

Mitigation summary

Install the fixed version as soon as it is available. Please visit the Pilz Shop (www.pilz.com/en-INT/eshop) to check for the fixed version

Revision history (2)
  1. Initial publication — 24 November 2022

    Initial revision.

  2. Update A — 22 May 2025

    Fix: quotation mark

Official source: Pilz PSIRT

VDE-2023-033

Pilz: WIBU Vulnerabilitiy in multiple Products

Pilz — PASloto

Pilz PSIRTcritical

Published

12 October 2023

Last update

22 May 2025

Linked CVEs

Affected sectors

Risk evaluation

Several Pilz products use the 3rd party component "CodeMeter Runtime" from WIBU-SYSTEM AG to manage software licenses. This component is affected by a vulnerability, which may enable an attacker to gain full control over the system running the software product. The vulnerability can be exploited locally or over the network. Update A, 2023-12-05 changed affected version of "Software PASvisu < 1.15.0" to "Software PASvisu < 1.14.1" removed CVE-2023-4701 because it was revoked.

Mitigation summary

PAS4000, PASvisu, PIT User Authentication Service, PNOZsigma Configurator, PMIv8: Installthe fixed version as soon as it is available. Please visit the Pilz eShop(https://www.pilz.com/en-INT/eshop) to check for the fixed version. PASloto, Live Video Server, SafetyEYE Configurator, PMC programming tool: These productsare end-of-live, please follow the general countermeasures.

Revision history (3)
  1. Initial publication — 12 October 2023

    Initial revision.

  2. Update A — 5 December 2023

    Update A

  3. Update B — 22 May 2025

    Fix: quotation mark

Official source: Pilz PSIRT

VDE-2023-048

Pilz: Multiple products prone to libwebp vulnerability

Pilz — PASvisu

Pilz PSIRThigh

Published

5 December 2023

Last update

22 May 2025

Linked CVEs

Affected sectors

Risk evaluation

Several Pilz products use the 3rd-party component 'libwebp' for decoding of images in WebP format. This component is affected by a vulnerability, which may enable an attacker to gain full control over the system running the software product. Depending on the affected product, the vulnerabilities can be exploited locally or over the network.

Mitigation summary

Install the fixed product version as soon as it is available. Please visit the Pilz eShop(https://www.pilz.com/en-INT/eshop) to check for the fixed version. PASvisu Runtime: Limit network access to legitimate connections by using a firewall or similarmeasures. Restrict administrative access by setting up user authentication properly.

Revision history (2)
  1. Initial publication — 5 December 2023

    Initial revision.

  2. Update A — 22 May 2025

    Fix: quotation mark

Official source: Pilz PSIRT

VDE-2022-021

Pepperl+Fuchs: RSM-EX devices - Multiple Bluetooth vulnerabilities

Pepperl+Fuchs — RSM-EX01B product Family

Pepperl+Fuchs PSIRThigh

Published

16 May 2022

Last update

22 May 2025

Affected sectors

Risk evaluation

Critical vulnerabilities have been discovered in the utilized Bluetooth component. For more information see: https://kb.cert.org/vuls/id/799380

Mitigation summary

The device will play a confirmation sound when a Bluetooth connection is successfully established and a status LED labeled BT indicates that a Bluetooth connection is active. This can be used to detect an unauthenticated connection.

Revision history (2)
  1. Initial publication — 16 May 2022

    initial revision

  2. Update A — 22 May 2025

    Fix: quotation mark

Official source: Pepperl+Fuchs PSIRT

VDE-2020-017

Pepperl+Fuchs, PACTware: Two password vulnerabilities found

Pepperl+Fuchs — PACTware

Pepperl+Fuchs PSIRThigh

Published

29 May 2020

Last update

22 May 2025

Affected sectors

Risk evaluation

PACTware passwords are stored in a recoverable format (CVE-2020-9403) PACTware passwords may be modified without knowing the current password (CVE-2020-9404)

Mitigation summary

Any further changes in 'user role'-administration will need a confirmation by using the current login password. This will be fixed in following versions (and higher): PACTware 5.0.5.31 PACTware 4.1 SP6 Overview about version history: https://pactware.com/de/service You can protect yourself against manipulation by restricting the access to the PC where PACTware is installed. In case of not known passwords it can be reset by reinstallation of PACTware (all PACTware versions).

Revision history (2)
  1. Initial publication — 29 May 2020

    initial revision

  2. Update A — 22 May 2025

    Fix: version space, added distribution, quotation mark

Official source: Pepperl+Fuchs PSIRT

VDE-2020-053

Pepperl+Fuchs: Comtrol RocketLinx ICRL-M - Multiple Vulnerabilities

Pepperl+Fuchs — ICRL-M-16RJ45/4CP-G-DIN

Pepperl+Fuchs PSIRTcritical

Published

8 March 2021

Last update

22 May 2025

Affected sectors

Risk evaluation

Several critical vulnerabilities within firmware.

Mitigation summary

For vulnerability CVE-2020-12502 'Cross-Site Request Forgery (CSRF)', CVE-2020- 12503 'Multiple Authenticated Command Injections' and CVE-2020-12504 'Active TFTP- Service' 1. Update following products to the respective Firmware Version: | Product ID | Firmware Version | |------------------------------|-------------------| | ICRL-M-8RJ45/4SFP-G-DIN | 1.4.0 | | ICRL-M-16RJ45/4CP-G-DIN | 1.4.0 | 2. Deactivate TFTP-Service

Revision history (3)
  1. Initial publication — 8 March 2021

    initial revision

  2. Update A — 12 February 2025

    Fix: corrected self-reference, fixed version

  3. Update B — 22 May 2025

    Fix: reference category, added distribution, quotation mark

Official source: Pepperl+Fuchs PSIRT

VDE-2021-041

Pepperl+Fuchs: Multiple DTM and VisuNet Software affected by log4net vulnerability

Pepperl+Fuchs — ABB Project Builder

Pepperl+Fuchs PSIRTcritical

Published

26 October 2021

Last update

22 May 2025

Linked CVEs

Affected sectors

Control centres

Risk evaluation

Critical vulnerabilities have been discovered in the utilized component log4net by Apache Software Foundation. UPDATE A: Remediation: added fixed VisuNet Products

Mitigation summary

External countermeasures are needed for the remaining products. The following protective measure is required for VisuNet devices and the PCs/Servers with an installed DTM: Restrict local access to the device, PC/Server and use user authentication to prevent unauthorized access.

Revision history (3)
  1. Initial publication — 26 October 2021

    Initial revision.

  2. Update A — 17 January 2022

    UPDATE A: add list of affected VisuNet products

  3. Update B — 22 May 2025

    Fix: firmware category, quotation mark

Official source: Pepperl+Fuchs PSIRT

VDE-2025-002

PEPPERL+FUCHS: HMI – devices are affected by Windows RCE

Pepperl+Fuchs — Native Windows

Pepperl+Fuchs PSIRTcritical

Published

25 February 2025

Last update

22 May 2025

Linked CVEs

Affected sectors

Risk evaluation

An unauthenticated attacker could repeatedly send IPv6 packets, that include specially crafted packets, to a Windows machine which could enable remote code execution.

Mitigation summary

Please install:<br>RM Shell 5 based on Windows 10 LTSB 2016: 18-33624T Windows Cumulative Security Patch - 2024-08 for RM Image 5 based on Windows 10 LTSB 2016 (KB5041773) found at Thin Client Firmware VisuNet RM Shell 5 (2016 LTSB) (pepperl-fuchs.com).

Revision history (3)
  1. Initial publication — 25 February 2025

    Initial revision.

  2. Update A — 10 April 2025

    fixed reference urls

  3. Update B — 22 May 2025

    Fix: added distribution, quotation mark

Official source: Pepperl+Fuchs PSIRT

VDE-2019-018

Weidmueller: multiple vulnerabilities in various Industrial Ethernet managed switches

Weidmüller — IE-SW

Weidmüller PSIRTcritical

Published

5 December 2019

Last update

22 May 2025

Affected sectors

Risk evaluation

Multiple issues have been found. Please check the CVEs for details.

Mitigation summary

For all potential vulnerabilities, customers can download a patched firmware to secure their switches properly. Please download and install the latest firmware for your switch by following the procedure below: Use the link www.weidmueller.com external link external link Enter within search field on the web page the product number of the switch you want to update and press 'enter' On next page expand the drop-down menu 'show downloads' Download the respective firmware from the download table Install the firmware on your switch Solution for CVE-2019-16672 a.) Solution for vulnerability, valid for switch series IE-SW-VL05M and IE-SW-VL08MT To avoid the vulnerabilities referred to in this section, it is necessary to install patched firmware. After installation of patched firmware the web interface can be accessed via encrypted communication using https, and web interface access can be configured to ensure encrypted connections by selecting 'https only'. The respective web interface menu section for this setting can be reached via the following path: Main Menu > Basic Settings > System: Set the 'Web Configuration' to 'https only' b.) Solution for vulnerability, valid for switch series IE-SW-PL08M, IE-SW-PL10M, IE-SW-PL16M, IE-SW-PL18M, IE-SW-PL09M To avoid the vulnerabilities referred to in this section, installation of patched firmware is not necessary. Web interface access can be configured to ensure encrypted connections by selecting 'https only'. The respective web interface menu section for this setting can be reached via the following path: Main Menu > Basic Settings > System: Set the 'Web Configuration' to 'https only' Solution for CVE-2019-16670, CVE-2019-16671, CVE-2019-16673, CVE-2019-16674 Solution for vulnerabilities, valid for switch series IE-SW-VL05M, IE-SW-VL08MT, IE-SW-PL08M, IE-SW-PL10M, IE-SW-PL16M, IE-SW-PL18M, IE-SW-PL09M After installing the patched firmware on the switch, it is possible to disable the unencrypted search service via Weidmüllermüller configuration software named 'WM Switch Utility' for Windows OS and to enable an encrypted search service, that will be working with the new 'Weidmüllermüller Switch Configuration Utility'. (available soon) Both services – the encrypted and the unencrypted search service - are enabled by default. To avoid the vulnerabilities referred to in this section the unencrypted search service should be disabled. The respective web interface menu section for this setting can be reached via the following path: Main Menu > Basic Settings > Security > Management Interface: Uncheck the checkbox 'Enable Search Service' Note: After disabling the unencrypted search service the switches can no longer be found or configured with the current 'WM Switch Utility'! Web interface settings are not affected by this configuration. --- Please find below the appropriate patched firmware versions for all affected products. | **Product Number** | **Product Name** | **Patched Firmware Version** | |---------------------|---------------------------------|---------------------------------------| | 1504280000 | IE-SW-VL05M-5TX | ≥ V3.6.24_Build_19062809 | | 1504310000 | IE-SW-VL05MT-5TX | ≥ V3.6.24_Build_19062809 | | 1504330000 | IE-SW-VL05M-3TX-2SC | ≥ V3.6.24_Build_19062809 | | 1504350000 | IE-SW-VL05MT-3TX-2SC | ≥ V3.6.24_Build_19062809 | | 1504370000 | IE-SW-VL05M-3TX-2ST | ≥ V3.6.24_Build_19062809 | | 1504390000 | IE-SW-VL05MT-3TX-2ST | ≥ V3.6.24_Build_19062809 | | 1240940000 | IE-SW-VL08MT-8TX | ≥ V3.5.22_Build_19062810 | | 1240970000 | IE-SW-VL08MT-5TX-3SC | ≥ V3.5.22_Build_19062810 | | 1345240000 | IE-SW-VL08MT-5TX-1SC-2SCS | ≥ V3.5.22_Build_19062810 | | 1240990000 | IE-SW-VL08MT-6TX-2ST | ≥ V3.5.22_Build_19062810 | | 1344770000 | IE-SW-VL08MT-6TX-2SC | ≥ V3.5.22_Build_19062810 | | 1241020000 | IE-SW-VL08MT-6TX-2SCS | ≥ V3.5.22_Build_19062810 | | 1241040000 | IE-SW-PL08M-8TX | ≥ V3.3.16_Build_19062811 | | 1286780000 | IE-SW-PL08MT-8TX | ≥ V3.3.16_Build_19062811 | | 1241070000 | IE-SW-PL08M-6TX-2SC | ≥ V3.3.16_Build_19062811 | | 1286790000 | IE-SW-PL08MT-6TX-2SC | ≥ V3.3.16_Build_19062811 | | 1241080000 | IE-SW-PL08M-6TX-2ST | ≥ V3.3.16_Build_19062811 | | 1286800000 | IE-SW-PL08MT-6TX-2ST | ≥ V3.3.16_Build_19062811 | | 1241090000 | IE-SW-PL08M-6TX-2SCS | ≥ V3.3.16_Build_19062811 | | 1286810000 | IE-SW-PL08MT-6TX-2SCS | ≥ V3.3.16_Build_19062811 | | 1241290000 | IE-SW-PL10M-3GT-7TX | ≥ V3.3.24_Build_19062813 | | 1286930000 | IE-SW-PL10MT-3GT-7TX | ≥ V3.3.24_Build_19062813 | | 1241300000 | IE-SW-PL10M-1GT-2GS-7TX | ≥ V3.3.24_Build_19062813 | | 1286940000 | IE-SW-PL10MT-1GT-2GS-7TX | ≥ V3.3.24_Build_19062813 | | 1241100000 | IE-SW-PL16M-16TX | ≥ V3.4.18_Build_19062814 | | 1286820000 | IE-SW-PL16MT-16TX | ≥ V3.4.18_Build_19062814 | | 1241120000 | IE-SW-PL16M-14TX-2SC | ≥ V3.4.18_Build_19062814 | | 1286830000 | IE-SW-PL16MT-14TX-2SC | ≥ V3.4.18_Build_19062814 | | 1241130000 | IE-SW-PL16M-14TX-2ST | ≥ V3.4.18_Build_19062814 | | 1286840000 | IE-SW-PL16MT-14TX-2ST | ≥ V3.4.18_Build_19062814 | | 1241320000 | IE-SW-PL18M-2GC-16TX | ≥ V3.4.30_Build_19062817 | | 1286970000 | IE-SW-PL18MT-2GC-16TX | ≥ V3.4.30_Build_19062817 | | 1241330000 | IE-SW-PL18M-2GC14TX2SC | ≥ V3.4.30_Build_19062817 | | 1286990000 | IE-SW-PL18MT-2GC14TX2SC | ≥ V3.4.30_Build_19062817 | | 1241340000 | IE-SW-PL18M-2GC14TX2ST | ≥ V3.4.30_Build_19062817 | | 1287000000 | IE-SW-PL18MT-2GC14TX2ST | ≥ V3.4.30_Build_19062817 | | 1241350000 | IE-SW-PL18M-2GC14TX2SCS | ≥ V3.4.30_Build_19062817 | | 1287010000 | IE-SW-PL18MT-2GC14TX2SCS | ≥ V3.4.30_Build_19062817 | | 1241370000 | IE-SW-PL09M-5GC-4GT | ≥ V3.3.20_Build_19070111 | | 1287020000 | IE-SW-PL09MT-5GC-4GT | ≥ V3.3.20_Build_19070111 |

Revision history (2)
  1. Initial publication — 5 December 2019

    Initial revision.

  2. Update A — 22 May 2025

    Fix: firmware category, version space, added distribution, quotation mark

Official source: Weidmüller PSIRT

VDE-2023-032

Weidmueller: WIBU Vulnerability in multiple Products

Weidmüller — IOT-GW30-4G-EU (with u-OS)

Weidmüller PSIRTcritical

Published

9 November 2023

Last update

22 May 2025

Linked CVEs

Affected sectors

Control centres

Risk evaluation

Multiple Weidmueller products are affected by recent WIBU vulnerability.

Mitigation summary

u-create studio: Disabling the network server function within CodeMeter would mitigate the vulnerability. To disable this function please refer to the following steps: 1. Navigate to the CodeMeter WebAdmin Website 2. Select option Settings > Server > Server access 3. Choose option 'deactivate' in section 'network server' 4. Click 'Apply' button on the bottom of the website

Revision history (2)
  1. Initial publication — 9 November 2023

    Initial revision.

  2. Update A — 22 May 2025

    Fix: quotation mark

Official source: Weidmüller PSIRT

VDE-2024-054

Endress+Hauser: Netilion Network Insights is affected by multiple vulnerabilities

Endress+Hauser — Compact Controller CC 100

Endress+Hauser PSIRTcritical

Published

21 October 2024

Last update

22 May 2025

Affected sectors

Risk evaluation

Several vulnerabilities have been identified in the web-based management of WAGO devices utilized in Endress+Hauser IoT solutions. WAGO has provided fixes for these vulnerabilities, which have been integrated into the solutions by Endress+Hauser. Additionally, a guideline on secure operation of these solutions has been made available.

Mitigation summary

If an immediate firmware update is not possible, the only way to prevent an attack is to prevent the access of the Web Based Management tool from the internet. This can be achieved by using a network element, such as a router, which hides and secures the components from the internet.

Revision history (3)
  1. Initial publication — 21 October 2024

    Initial revision.

  2. Update A — 6 November 2024

    Fix: correct certvde domain, added self-reference

  3. Update B — 22 May 2025

    Fix: version space, quotation mark

Official source: Endress+Hauser PSIRT

VDE-2021-051

Beckhoff: Relative path traversal vulnerability through TwinCAT OPC UA Server

Beckhoff — TwinCAT OPC UA Server in TF6100 < 4.3.48.0

Beckhoff PSIRTmiddel

Published

4 November 2021

Last update

22 May 2025

Linked CVEs

Affected sectors

Risk evaluation

Through specific nodes of the server configuration interface of the TwinCAT OPC UA Server administrators are able to remotely create and delete any files on the system which the server is running on, though this access should have been restricted to specific directories. In case that configuration interface is combined with not recommended settings to allow anonymous access via the TwinCAT OPC UA Server then this kind of file access is even possible for any unauthenticated user from remote.

Mitigation summary

Consider restricting access to the nodes of the 'TcOpcUAServer' with the methods described by https://infosys.beckhoff.com/content/1033/tcopcuaserver/5930038411-1.html such that the administrative interface can only be accessed by administrative users of well known OPC UA clients.

Revision history (2)
  1. Initial publication — 4 November 2021

    initial revision

  2. Update A — 22 May 2025

    Fix: added distribution, quotation mark

Official source: Beckhoff PSIRT

VDE-2020-037

Beckhoff: Privilege Escalation through TwinCat System Tray (TcSysUI.exe)

Beckhoff — TwinCAT XAR with default installation path

Beckhoff PSIRThigh

Published

19 November 2020

Last update

22 May 2025

Linked CVEs

Affected sectors

Risk evaluation

The default installation path and its permissions for the TwinCAT runtime allow a local user to replace or modify executables other users of the same system might execute. The issue does not apply for installations underneath C:\Program Files.

Mitigation summary

Please consider the solution described with the next section (title 'Solution') for new installations only and installations for which it is acceptable to reinstall TwinCAT. For existing installations a script is provided for download at the following link: https://download.beckhoff.com/download/Document/product-security/Advisories/advisory-2020-003/cve-2020-12510.zip external link It changes the permissions of a directory of an already installed TwinCAT 3.1 installation. More precisely, it reads the current permissions of 'C:\Program Files' and copies them to the directory '3.1\System' underneath the installation path of TwinCAT (default 'C:\TwinCAT\3.1\System'). The procedure to use that script is as follows: 1. Download the script, unzip it, and copy it to the IPC. 2. On the IPC log in as administrator and open a PowerShell (Windows-Key + R + 'PowerShell'). 3. At the PowerShell enter the following command to temporarily allow the execution of scripts: set-executionpolicy -ExecutionPolicy Unrestricted -Scope Process (The effect of this is limited to the life-time of the current shell window because of '-Scope Process'.) 4. Then change to the path to where you downloaded the script and execute it: .\cve-2020-12510.ps1 The expected output is 'Copied the permissions from C:\Program Files to \3.1\System'. 5. Close the PowerShell and log out from the IPC as needed. It is safe to apply the script several times. It is safe to run it during full operation of TwinCAT XAR 3.1. There is no need to reboot the IPC afterwards. There is no need to periodically run the script. Future updates of TwinCAT 3.1 will either not touch the permissions which are set by the script or apply more appropriate ones. To apply the procedure to a set of IPCs you can prepare a USB stick with the content of the ZIP file 'cve-2020- 12510.zip' (see download URL above). Then the procedure for each IPC is: 1. Log in as administrator on the IPC. 2. Open the USB stick with the File Explorer (formerly known as Windows Explorer). 3. Double click on the file 'run-cve-2020-12510.bat'. (This simply invokes the PowerShell to execute the script already described above.)

Revision history (3)
  1. Initial publication — 19 November 2020

    Initial revision.

  2. Update A — 11 November 2021

    Update A

  3. Update B — 22 May 2025

    Fix: added distribution, quotation mark

Official source: Beckhoff PSIRT