499

Found

Advisory data: live connection— last retrieved: 20 November 2026 at 22:50.

Filters

499 advisories found

VDE-2020-029

WAGO: XSS vulnerability in Web-UI in WAGO 750-88X and WAGO 750-89X

WAGO — 750 Fieldbus Coupler

WAGO PSIRTmiddel

Published

30 September 2020

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

The Web-Based Management (WBM) of WAGOs programmable logic controller (PLC) is typically used for administration, commissioning and updates. The SNMP configuration page of the device is vulnerable for a persistent XSS (Cross-Site Scripting) attack.

Mitigation summary

* Restrict network access to the device. * Use strong passwords * Do not directly connect the device to the internet * Disable unused TCP/UDP-ports

Revision history (3)
  1. Initial publication — 30 September 2020

    initial revision

  2. Update A — 10 April 2025

    Fixed csaf reference URL

  3. Update B — 14 May 2025

    Fix: added distribution

Official source: WAGO PSIRT

VDE-2021-009

Pilz: Multiple products prone to Niche Ethernet Stack vulnerabilities

Pilz — Base-Device PNOZ mxp ETH (PNOZmulti Classic)

Pilz PSIRTcritical

Published

20 September 2021

Last update

14 May 2025

Affected sectors

Risk evaluation

Multiple products of PILZ utilise a third-party TCP/IP implementation - the "Niche Ethernet Stack". This TCP/IP stack contains multiple vulnerabilities which are therefore affecting the products listed above.

Mitigation summary

It is adviced to use firewalls or similar network security devices to prevent unauthorized network communication to the products affected.

Revision history (2)
  1. Initial publication — 20 September 2021

    Initial revision.

  2. Update A — 14 May 2025

    Fix: added distribution

Official source: Pilz PSIRT

VDE-2020-038

Pepperl+Fuchs: Multiple vulnerabilites in Comtrol IO-Link Master

Pepperl+Fuchs — IO-Link Master

Pepperl+Fuchs PSIRThigh

Published

4 January 2021

Last update

14 May 2025

Affected sectors

Risk evaluation

Several vulnerabilities exist within firmware versions up to and including v1.5.48.

Mitigation summary

In order to prevent the exploitation of the reported vulnerabilities, we recommend that the affected units be updated with the following three firmware packages: - U-Boot bootloader version 1.36 - System image version 1.52 - Application base version 1.6.11

Revision history (3)
  1. Initial publication — 4 January 2021

    initial revision

  2. Update A — 12 February 2025

    Fix: corrected self-reference, fixed version

  3. Update B — 14 May 2025

    Fix: added distribution

Official source: Pepperl+Fuchs PSIRT

VDE-2019-002

Pepperl+Fuchs: Path traversal in WirelessHART Gateway

Pepperl+Fuchs — WHA-GW-*-ETH

Pepperl+Fuchs PSIRTmiddel

Published

6 March 2019

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

Pepperl+Fuchs analyzed WirelessHART-Gateways in respect of a critical vulnerability within the Firmware. An attacker may exploit this vulnerability to get access to files and access restricted directories that are stored on the device by manipulating file parameters that reference these. Incoming HTTP requests using fcgi-bin/wgsetcgi and a filename parameter allow a directory / path traversal. A publicly available exploit already exists for this vulnerability.

Mitigation summary

A Firmware (version see table below), which solves the problem, is available. Please contact your support representative for this particular firmware package and update the corresponding product. | Product ID | Version | Bus-Interface of Device | |-----------------|----------|-------------------------| | WHA-GW-*-ETH | 03.00.08 | Modbus | | WHA-GW-*-ETH.EIP | 02.00.01 | Ethernet/IP |

Revision history (4)
  1. Initial publication — 6 March 2019

    Initial revision.

  2. Update A — 6 November 2024

    Fix: correct certvde domain, added self-reference

  3. Update B — 12 March 2025

    Fix: Version, Remediation

  4. Update C — 14 May 2025

    Fix: added distribution

Official source: Pepperl+Fuchs PSIRT

VDE-2021-027

Pepperl+Fuchs: WirelessHART-Gateway - Vulnerability may allow remote attackers to cause a Denial Of Service

Pepperl+Fuchs — WHA-GW-F2D2-0-AS- Z2-ETH

Pepperl+Fuchs PSIRTcritical

Risk evaluation

Critical vulnerabilities have been discovered in the product and in the utilized components jQuery by jQuery Team and TLS Version 1.0/1.1. The impact of the vulnerabilities on the affected device may result in - denial of service - remote code execution - code exposure

Mitigation summary

An external protective measure is required. - Minimize network exposure for affected products and ensure that they are not accessible via the Internet. - Isolate affected products from the corporate network. - If remote access is required, use secure methods such as virtual private networks (VPNs).

Revision history (2)
  1. Initial publication — 16 October 2021

    Initial revision.

  2. Update A — 14 May 2025

    Fix: added distribution

Official source: Pepperl+Fuchs PSIRT

VDE-2021-028

Pepperl+Fuchs: Multiple VDM100-Distance Ethernet-IP sensors with multiple vulnerabilities

Pepperl+Fuchs — VDM100

Pepperl+Fuchs PSIRTcritical

Risk evaluation

Critical vulnerabilities have been discovered in the utilized component TRECK TCP/IP Stack by Digi International Inc. For more information see advisory by Digi International Inc.: Digi International Security Notice - TRECK TCP/IP Stack "RIPPLE20" VU#257161 ICS-VU-035787 | Digi International

Mitigation summary

An external protective measure is required. - Minimize network exposure for affected products and ensure that they are not accessible via the Internet. - Isolate affected products from the corporate network. - If remote access is required, use secure methods such as virtual private networks (VPNs).

Revision history (2)
  1. Initial publication — 16 August 2021

    Initial revision.

  2. Update A — 14 May 2025

    Fix: added distribution

Official source: Pepperl+Fuchs PSIRT

VDE-2021-042

Weidmueller: Remote I/O fieldbus couplers (IP20) affected by INFRA:HALT vulnerabilities

Weidmüller — UR20

Weidmüller PSIRThigh

Published

18 October 2021

Last update

14 May 2025

Affected sectors

Risk evaluation

The Weidmueller Remote I/O (IP20) fieldbus couplers (u-remote) are affected by several vulnerabilities of the third-party TCP/IP Niche stack. An attacker may use crafted IP packets to cause a denial of service or breach of integrity of the affected products. Weidmueller recommends restricting network access from the internet and also locally to reduce the attack vector to a manageable minimum.

Mitigation summary

Fieldbuses (including Industrial Ethernet protocols) in general are not intended for direct connection with the internet, as they lack a proper set of security capabilities. This also applies to Weidmüller IP20 Remote I/O fieldbus couplers, which are developed and designed for operation in closed industrial networks. - Do not directly connect the affected products to the internet. - Restrict network access to the affected products by proper secured network infrastructure (e.g. routers, firewalls, DMZ, VPNs). - Restrict physical access to the industrial network and affected products (e.g cabinets, seals, closures).

Revision history (3)
  1. Initial publication — 18 October 2021

    Initial revision.

  2. Update A — 10 April 2025

    Fix: change vendor in product tree

  3. Update B — 14 May 2025

    Fix: added distribution

Official source: Weidmüller PSIRT

VDE-2020-022

Endress+Hauser: Ecograph T utilizing Webserver firmware version 2.x exposes sensitive information

Endress+Hauser — Ecograph T

Endress+Hauser PSIRTmiddel

Published

19 November 2020

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

The firmware release has a dynamic token for each request submitted to the server, which makes repeating requests and analysis complex enough. Nevertheless, it's possible and during the analysis it was discovered that it also has an issue with the access-control matrix on the server-side.

Mitigation summary

Customers should configure a perimeter firewall to block traffic from untrusted networks and users to the device. These recommendations will be incorporated into the device documentation (operating instructions) Change default password for operator, service and admin account. Endress+Hauser will not change this behavior. Customers are recommended to take the measures for Temporary Fix / Mitigation as described above.

Revision history (4)
  1. Initial publication — 19 November 2020

    Initial revision.

  2. Update A — 6 November 2024

    Fix: correct certvde domain, added alias, added self-reference

  3. Update B — 11 April 2025

    Fix: version range

  4. Update C — 14 May 2025

    Fix: added distribution

Official source: Endress+Hauser PSIRT

VDE-2021-005

Endress+Hauser: Multiple Devices affected by fdtContainer vulnerability

Endress+Hauser — Asset Health Monitoring

Endress+Hauser PSIRThigh

Published

1 March 2021

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

The fdtCONTAINER component is integrated into an application (host application). The fdtCONTAINER application is a specific host application which integrates the fdtCONTAINER component. The fdtCONTAINER component exchanges binary data blobs with such a host application. Typically, the host application saves these binary data blobs into a project storage (project file or a project database). To manipulate the data inside the project storage, the attacker needs write access to this project storage. Additionally, the manipulated project needs to be opened by the host application. It depends on the host application whether opening the project requires a user action or not. In fdtCONTAINER applications, the user has to open the manipulated project file manually. In the case of opening a stored project, the deserialization of the manipulated data can be exploited.

Mitigation summary

1. Exchange project data only via secure exchange services 2. Use appropriate means to protect the project storage from unauthorized manipulation 3. Do not open project data from an unknown source 4. Reduce the user rights of the host application to the necessary minimum

Revision history (2)
  1. Initial publication — 1 March 2021

    Initial revision.

  2. Update A — 14 May 2025

    Fix: added distribution

Official source: Endress+Hauser PSIRT

VDE-2021-044

Endress+Hauser: Multiple products affected by log4net vulnerability

Endress+Hauser — DeviceCare

Endress+Hauser PSIRTcritical

Published

20 January 2022

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

Apache log4net versions before 2.0.10 do not disable XML external entities when parsing log4net configuration files. This allows for XXE-based attacks in applications that accept attacker-controlled log4net configuration files.

Mitigation summary

Make sure that no unauthorized access to the production environment is possible. Avoid using the above listed software with Windows administrator privileges if other users with lower privileges have access to the same software installation.

Revision history (3)
  1. Initial publication — 20 January 2022

    Initial revision.

  2. Update A — 12 February 2025

    Fix: corrected self-reference, fixed version

  3. Update B — 14 May 2025

    Fix: added distribution

Official source: Endress+Hauser PSIRT

VDE-2020-031

Endress+Hauser: Multiple products prone to WIBU CodeMeter vulnerabilities

Endress+Hauser — Codemeter

Endress+Hauser PSIRTcritical

Published

27 October 2020

Last update

14 May 2025

Affected sectors

Risk evaluation

For further Information please refer to WIBU Advisories directly at https://wibu.com/support/security-advisories.html and the aforementioned CVE-IDs.

Mitigation summary

WIBU SYSTEMS has released a new Code Meter Runtime version 7.10a dated on 16.9.2020. All the known vulnerabilities are fixed with this version. The version is available at https://www.wibu.com/support

Revision history (4)
  1. Initial publication — 27 October 2020

    Initial revision.

  2. Update A — 6 November 2024

    Fix: added self-reference

  3. Update B — 11 April 2025

    Fix: version range, remove Issuing authority

  4. Update C — 14 May 2025

    Fix: added distribution

Official source: Endress+Hauser PSIRT

VDE-2019-019

Beckhoff: TwinCAT Denial-of-Service in Profinet driver

Beckhoff — TwinCAT

Beckhoff PSIRThigh

Published

9 October 2019

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

In case TwinCAT is configured to use the Profinet driver, a denial of service of the controller could be reached by sending special packets to the device.

Mitigation summary

Profinet could be blocked in perimeter firewall to block PROFINET DCP packets from untrusted networks to the device. Beckhoff will provide updates for the mentioned TwinCAT Versions.

Revision history (4)
  1. Initial publication — 9 October 2019

    Initial revision.

  2. Update A — 6 November 2024

    Fix: correct certvde domain, added self-reference

  3. Update B — 11 April 2025

    Fix: version range

  4. Update C — 14 May 2025

    Fix: added distribution

Official source: Beckhoff PSIRT

vde-2023-002

MB Connect Line: Multiple vulnerabilities in mbConnect24 and mymbConnect24

MB connect line — mbCONNECT24

MB connect line PSIRThigh

Published

15 May 2023

Last update

14 May 2025

Affected sectors

Risk evaluation

Two vulnerabilites have been discovered in mbCONNECT24 and mbCONNECT24 in all versions through 2.13.3.

Mitigation summary

If you have MFA enabled on the admin user, the password will still be set, but the attacker will be unable to login as the MFA is still in place.

Revision history (2)
  1. Initial publication — 15 May 2023

    initial revision

  2. Update A — 14 May 2025

    Fix: added distribution

Official source: MB connect line PSIRT

VDE-2022-017

Helmholz: Unauthenticated user enumeration in myREX24 and myREX24.virtual

Helmholz — myREX24

Helmholz PSIRTmiddel

Published

7 September 2022

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

An issue was discovered in myREX24 and myREX24.virtual in all versions through 2.11.2.

Mitigation summary

Update to Version 2.12.1

Revision history (2)
  1. Initial publication — 7 September 2022

    initial revision

  2. Update A — 14 May 2025

    Fix: added distribution

Official source: Helmholz PSIRT

VDE-2021-058

Helmholz: Remote user enumeration in myREX24/myREX24-virtual

Helmholz — myREX24

Helmholz PSIRThigh

Published

8 December 2021

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

An issue was discovered in the myREX24 and myREX24-virtual software in all versions through V2.9.0.

Mitigation summary

Update myREX24/myREX24-virtual to 2.10.1

Revision history (2)
  1. Initial publication — 8 December 2021

    initial revision

  2. Update A — 14 May 2025

    Fix: added distribution

Official source: Helmholz PSIRT

VDE-2024-031

Helmholz: Vulnerabilities in myREX24 V2/myREX24.virtual

Helmholz — myREX24

Helmholz PSIRTcritical

Published

18 March 2025

Last update

14 May 2025

Affected sectors

Risk evaluation

The data24 service that is bundled with every installation of myREX24 V2/myREX24.virtual has two serious flaws in core components. These combined can lead to a complete loss of confidentiality, integrity and availability.

Mitigation summary

Update to latest version: 2.16.2 CVE-2024-23943: This fix does not apply to REX 200/REX 250 devices with firmware 8.0.0 - 8.1.3. If you are using a device with this firmware, please update it to >= 8.2.0.

Revision history (4)
  1. Initial publication — 18 March 2025

    Initial revision.

  2. Update A — 18 March 2025

    Update: Changed Product name

  3. Update B — 10 April 2025

    Update: fixed CSAF-Reference URL, changed url in credits, removed whitespace after version operator

  4. Update C — 14 May 2025

    Fix: added distribution

Official source: Helmholz PSIRT

VDE-2022-057

Wiesemann & Theis multiple products prone to web interface vulnerability

Wiesemann & Theis — Com-Server ++

Wiesemann & Theis PSIRThigh

Published

13 December 2022

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

Multiple Wiesemann & Theis product families are affected by a vulnerability in the web interface. The device allows an unauthenticated attacker to get the session ID of a logged in user. He may then spoof his IP address to act as the logged in user.

Mitigation summary

Update Com-Server family to version 1.55 Update Com-Server Highspeed family to version 1.78 or higher

Revision history (2)
  1. Initial publication — 13 December 2022

    Initial revision.

  2. Update A — 14 May 2025

    Fix: added distribution

Official source: Wiesemann & Theis PSIRT

VDE-2021-007

Pepperl+Fuchs: Multiple Products - Vulnerability may allow remote attackers to cause a Denial Of Service

Pepperl+Fuchs — PCV100-F200-B25-V1D-6011

Pepperl+Fuchs PSIRThigh

Published

16 February 2021

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

Critical vulnerability has been discovered in the utilized component Ethernet IP Stack by Hilscher Gesellschaft für Systemautomation mbH. The impact of the vulnerability on the affected device is that it can denial of service remote code execution code exposure For more information see advisory by Hilscher: https://kb.hilscher.com/pages/viewpage.action?pageId=108969480

Mitigation summary

An external protective measure is required. Minimize network exposure for affected products and ensure that they are not accessible via the Internet. Isolate affected products from the corporate network. If remote access is required, use secure methods such as virtual private networks (VPNs).

Revision history (2)
  1. Initial publication — 16 February 2021

    Initial revision.

  2. Update A — 14 May 2025

    Fix: version space, added distribution

Official source: Pepperl+Fuchs PSIRT

VDE-2020-039

TRUMPF: Multiple products prone to WIBU CodeMeter vulnerabilities

TRUMPF — CAD/CAM software tools

TRUMPF PSIRTcritical

Published

27 October 2020

Last update

14 May 2025

Affected sectors

Risk evaluation

A number of TRUMPF CAD/CAM software tools use the CodeMeter Runtime application from WIBU-SYSTEMS AG to manage licences. This application contains a number of vulnerabilities, which enable an attacker to prevent normal operation of CodeMeter, resulting in a Denial-of-Service and potentially execute arbitrary code.

Mitigation summary

- Use the updated versions of the TRUMPF CAD/CAM products that will be available via your service channel shortly. - Until then, reduce internet usage on workstations with TRUMPF CAD/CAM products to a minimum.

Revision history (2)
  1. Initial publication — 27 October 2020

    Initial revision.

  2. Update A — 14 May 2025

    Fix: reference category, added distribution

Official source: TRUMPF PSIRT

VDE-2024-018

Wiesemann & Theis: Multiple products prone to unquoted search path

Wiesemann & Theis — Com Redirector Legacy

Wiesemann & Theis PSIRThigh

Published

28 February 2024

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

Multiple Wiesemann & Theis software products are affected by a vulnerability through an unquoted search path in the Windows registry. A local attacker can execute arbitrary code and gain administrative privileges by inserting an executable file in the path of the affected product. Update A, 07.03.2024 Incorrect version numbers have been corrected.

Mitigation summary

- Update Com Redirector Legacy external link to version 3.94 or higher (Art.No. 00102) - Update Com Redirector PnP external link to version 4.43 or higher (Art.No. 00111) - Update OPC-Server external link to version 4.89 or higher (Art.No. 00103)

Revision history (3)
  1. Initial publication — 28 February 2024

    Initial revision.

  2. Update A — 7 March 2024

    Update A

  3. Update B — 14 May 2025

    Fix: reference category, added distribution

Official source: Wiesemann & Theis PSIRT

VDE-2024-009

Welotec: Two vulnerabilities in TK500v1 router series

Welotec — TK500v1

Welotec PSIRTcritical

Published

9 April 2024

Last update

14 May 2025

Affected sectors

Risk evaluation

Welotec has closed two vulnerabilities in the TK500v1 router series and advises to update the routers to firmware version r5542 or later. An exploitation of the vulnerabilities can allow an attacker to manipulate the device.

Mitigation summary

Update the product to firmware v2.3.0.r5542 or later.

Revision history (4)
  1. Initial publication — 7 June 2023

    initial revision

  2. Update A — 4 June 2024

    Minor typo changes. Reorder Products and Branches. Duplicate remediation from document notes to the vulnerabilities.

  3. Update B — 6 November 2024

    Fix: correct certvde domain, added self-reference

  4. Update C — 14 May 2025

    Fix: firmware category, added distribution, version space

Official source: Welotec PSIRT

VDE-2020-033

Pilz: Multiple products prone to WIBU-SYSTEMS CodeMeter vulnerabilities

Pilz — CODESYS DevSys

Pilz PSIRTcritical

Published

10 September 2020

Last update

14 May 2025

Affected sectors

Risk evaluation

A number of Pilz software tools use the Software CodeMeter Runtime application from WIBU-SYSTEMS AG to manage licences. This application contains a number of vulnerabilities, which enable an attacker to change and falsify a licence file, prevent normal operation of Code- Meter (Denial-of-Service) and potentially execute arbitrary code.

Mitigation summary

Use the current Version 7.10 of the Software CodeMeter Runtime, available via the manufacturer's website. https://www.wibu.com/de/support/anwendersoftware/anwendersoftware.html Only use the Software CodeMeter Runtime as Client. The software tools named under affected products use the Software CodeMeter Runtime as Client in their default setting. Pilz also recommends using a local firewall to limit unwanted access to the network ser- vices of the device with Software CodeMeter Runtime installed.

Revision history (3)
  1. Initial publication — 10 September 2020

    Initial revision.

  2. Update A — 6 November 2024

    Fix: correct certvde domain, added self-reference

  3. Update B — 14 May 2025

    Fix: version space, removed ia, firmware category, added distribution

Official source: Pilz PSIRT

VDE-2018-016

Pepperl+Fuchs: ecom Mobile devices prone to Android privilege elevation vulnerability

Pepperl+Fuchs — CT50-Ex

Pepperl+Fuchs PSIRTmiddel

Published

19 October 2018

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

An attacker may gain access (by elevated privileges) to CT50-Ex mobile computers through a vulnerability in a system service running the Android Operating System (OS). The system service improperly validates incoming connection requests. Although the vulnerability is significant, currently no known exploits publicly available.

Mitigation summary

An update is available that resolves this vulnerability. All customers using the impacted products should update their products as indicated in the chart below. Only products listed below are affected by this vulnerability. Updates are available via the Pepperl+Fuchs / ecom product support channel or directly from the original manufacturer Honeywell at https://hsmftp.honeywell.com . Pepperl+Fuchs strongly recommends that users upgrade to the version identified below to resolve the vulnerability. CT50-Ex, Android 6.0, Update to CommonES 4.01.00.4134 or later CT50-Ex, Android 6.0, Update ECP to version 2.30.00.0167 or later (if applicable) CT50-Ex, Android 4.4, Update to CommonES 3.17.3445 or later For support, please contact your local Pepperl+Fuchs sales representative.

Revision history (3)
  1. Initial publication — 19 October 2018

    Initial revision.

  2. Update A — 6 November 2024

    Fix: correct certvde domain, added self-reference

  3. Update B — 14 May 2025

    Fix: version space, firmware category, added distribution

Official source: Pepperl+Fuchs PSIRT

VDE-2024-065

PEPPERL+FUCHS: HMI devices are affected by Insecure Platform Key

Pepperl+Fuchs — BTC22-*

Pepperl+Fuchs PSIRTmiddel

Published

26 November 2024

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

A vulnerability in the use of hard-coded Platform Keys (PK) within the UEFI framework, known as PKfail, has been discovered in several Pepperl+Fuchs devices.

Mitigation summary

Protect the device from unauthorized physical access.

Revision history (2)
  1. Initial publication — 26 November 2024

    Initial revision.

  2. Update A — 14 May 2025

    Fix: version space

Official source: Pepperl+Fuchs PSIRT

VDE-2021-002

Weidmueller: WI Manager affected by fdtContainer vulnerability

Weidmüller — WI Manager

Weidmüller PSIRThigh

Published

20 January 2021

Last update

14 May 2025

Linked CVEs

Affected sectors

Risk evaluation

A vulnerability has been discovered in the fdtCONTAINER component and application by M&M Software GmbH. As this software is part of the Weidmüller FDT/DTM Software with WI Manager, this Weidmueller software is affected by the above vulnerability as well. The fdtCONTAINER component exchanges binary data blobs with the WI Manager. The WI Manager saves these binary data blobs into a project file. If an attacker gets write access to the project file, the project file can be manipulated to contain malicious code.

Mitigation summary

- Exchange project data only via secure exchange services - Use appropriate means to protect the project storage from unauthorized manipulation - Do not open project data from an unknown source - Reduce the user rights of the WI Manager to the necessary minimum

Revision history (2)
  1. Initial publication — 20 January 2021

    Initial revision.

  2. Update A — 14 May 2025

    Fix: version space, added distribution

Official source: Weidmüller PSIRT