VDE-2026-065
Endress+Hauser: iDTM Debug Interface Vulnerability in the FDI Package Library
Gepubliceerd
3 augustus 2026
Laatste update
3 augustus 2026
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
A vulnerability in the iDTM FDI allows an attacker with elevated privileges and access to the host system to enable the debug interface by placing a crafted file in the application directory.
Mitigatiesamenvatting
If an immediate update is not possible, Endress+Hauser recommends the following measures to reduce the risk of exploitation: * Restrict access to affected systems to authorized personnel only * Apply the principle of least privilege and limit administrative access to trusted users. * Protect application installation directories against unauthorized modification through appropriate operating system access controls. Following these recommendations reduces the risk of unauthorized activation.
Revisiegeschiedenis (1)
Initiële publicatie — 3 augustus 2026
Initial revision
VDE-2026-045
Endress+Hauser: Multiple products affected by SopasET interface vulnerability
Risk evaluation
A vulnerability was discovered in several Endress+Hauser products that can be accessed via ethernet.
Mitigatiesamenvatting
Restrict device access to trusted and authorized entities only. Apply the general security measures during product operation to mitigate the identified security risk. Refer to the ICS‑CERT Recommended Practices for Industrial Security for additional guidance.
Revisiegeschiedenis (1)
Initiële publicatie — 16 juli 2026
Initial version
VDE-2026-032
Endress+Hauser: sudo vulnerability affects Endress+Hauser MCS200HW
Gepubliceerd
21 april 2026
Laatste update
21 april 2026
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
The display unit of the Endress+Hauser MCS200HW is affected by a sudo chroot vulnerability.
Mitigatiesamenvatting
The display unit's firmware versions below 4.3.4 are affected. To address the vulnerability, customers are strongly recommended to update the display unit of their devices to firmware version 4.3.4. Endress+Hauser will include this firmware version in the MCS200HW products starting with version 1.11.5.6R. Alternatively, customers can contact Endress+Hauser directly to obtain the updated display firmware, or download the original firmware - including update instructions - from the Phoenix Contact website referenced below.
Revisiegeschiedenis (1)
Initiële publicatie — 21 april 2026
Initial version
VDE-2025-107
Endress+Hauser: Multiple products affected by Qualcomm vulnerabilities
Gepubliceerd
5 december 2025
Laatste update
2 april 2026
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Multiple vulnerabilities in a Qualcomm component have been reported in a closed-source report. This component is an integral part of the radio chip found in several Endress+Hauser products.
Mitigatiesamenvatting
If a firmware update is no longer possible, it is recommended to replace the device.
Revisiegeschiedenis (2)
Initiële publicatie — 5 december 2025
Initial version
Update A — 2 april 2026
Updated CPEs
VDE-2026-003
Endress+Hauser: Multiple products prone to multiple vulnerabilities in e!Runtime and CODESYS V3 Runtime
Gepubliceerd
31 maart 2026
Laatste update
1 april 2026
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Multiple Endress+Hauser devices are prone to vulnerabilities found in e!Runtime and the CODESYS V3 framework.
Mitigatiesamenvatting
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
Revisiegeschiedenis (2)
Initiële publicatie — 31 maart 2026
Initial version
Update A — 1 april 2026
Edited a typo in product tree.
VDE-2026-002
Endress+Hauser: buffer overflow in glibc ld.so leading to privilege escalation
Risk evaluation
A vulnerability has been identified in WAGO devices utilized in Endress+Hauser IoT solutions. WAGO has provided fixes for these vulnerabilities, which have been integrated into the solutions by Endress+Hauser.
Mitigatiesamenvatting
Local access is required to exploit this vulnerability. To mitigate the risk, ensure that only authorized personnel have physical access to the device.
Revisiegeschiedenis (1)
Initiële publicatie — 2 maart 2026
Initial version
VDE-2025-068
Endress+Hauser: Proline 10 Maintenance credentials may be exposed under certain conditions
Gepubliceerd
2 september 2025
Laatste update
20 februari 2026
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
A privilege escalation vulnerability has been identified in Endress+Hauser's Proline 10 devices. This flaw allows an authenticated user with Operator-level access to elevate their privileges and gain Maintenance-level access, potentially enabling unauthorized configuration changes. Endress+Hauser has released a security update addressing this issue.
Mitigatiesamenvatting
If an immediate firmware update is not feasible, it is recommended to disable the device's Bluetooth communication when not actively in use. This significantly reduces the risk of unauthorized access by eliminating the key vector through which the vulnerability could be exploited.
Revisiegeschiedenis (2)
Initiële publicatie — 2 september 2025
Initial version
Update A — 20 februari 2026
fixed typo in alias
VDE-2025-105
Endress+Hauser: Multiple products affected by Wibu-Systems CodeMeter Vulnerability
Gepubliceerd
8 december 2025
Laatste update
8 december 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
A vulnerability in Wibu-Systems CodeMeter (up to version 7.60b) affects multiple Endress+Hauser products. This flaw can lead to a heap buffer overflow, which may allow remote code execution under certain conditions.
Mitigatiesamenvatting
If possible, configure CodeMeter to run in client-only mode. If server mode is required, restrict access to authorized clients by implementing an access control list. For Proline Promag 800 OPC UA Connectivity, CodeMeter operates as a server only during license activation. Installation and license activation are managed by Endress+Hauser. If a customer performs manual license activation, it is strongly recommended to limit network access to necessary clients only by using firewalls or equivalent security measures.
Revisiegeschiedenis (1)
Initiële publicatie — 8 december 2025
Initial version
VDE-2024-054
Endress+Hauser: Netilion Network Insights is affected by multiple vulnerabilities
Gepubliceerd
21 oktober 2024
Laatste update
22 mei 2025
Getroffen sectoren
Risk evaluation
Several vulnerabilities have been identified in the web-based management of WAGO devices utilized in Endress+Hauser IoT solutions. WAGO has provided fixes for these vulnerabilities, which have been integrated into the solutions by Endress+Hauser. Additionally, a guideline on secure operation of these solutions has been made available.
Mitigatiesamenvatting
If an immediate firmware update is not possible, the only way to prevent an attack is to prevent the access of the Web Based Management tool from the internet. This can be achieved by using a network element, such as a router, which hides and secures the components from the internet.
Revisiegeschiedenis (3)
Initiële publicatie — 21 oktober 2024
Initial revision.
Update A — 6 november 2024
Fix: correct certvde domain, added self-reference
Update B — 22 mei 2025
Fix: version space, quotation mark
VDE-2021-005
Endress+Hauser: Multiple Devices affected by fdtContainer vulnerability
Risk evaluation
The fdtCONTAINER component is integrated into an application (host application). The fdtCONTAINER application is a specific host application which integrates the fdtCONTAINER component. The fdtCONTAINER component exchanges binary data blobs with such a host application. Typically, the host application saves these binary data blobs into a project storage (project file or a project database). To manipulate the data inside the project storage, the attacker needs write access to this project storage. Additionally, the manipulated project needs to be opened by the host application. It depends on the host application whether opening the project requires a user action or not. In fdtCONTAINER applications, the user has to open the manipulated project file manually. In the case of opening a stored project, the deserialization of the manipulated data can be exploited.
Mitigatiesamenvatting
1. Exchange project data only via secure exchange services 2. Use appropriate means to protect the project storage from unauthorized manipulation 3. Do not open project data from an unknown source 4. Reduce the user rights of the host application to the necessary minimum
Revisiegeschiedenis (2)
Initiële publicatie — 1 maart 2021
Initial revision.
Update A — 14 mei 2025
Fix: added distribution
VDE-2020-022
Endress+Hauser: Ecograph T utilizing Webserver firmware version 2.x exposes sensitive information
Gepubliceerd
19 november 2020
Laatste update
14 mei 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
The firmware release has a dynamic token for each request submitted to the server, which makes repeating requests and analysis complex enough. Nevertheless, it's possible and during the analysis it was discovered that it also has an issue with the access-control matrix on the server-side.
Mitigatiesamenvatting
Customers should configure a perimeter firewall to block traffic from untrusted networks and users to the device. These recommendations will be incorporated into the device documentation (operating instructions) Change default password for operator, service and admin account. Endress+Hauser will not change this behavior. Customers are recommended to take the measures for Temporary Fix / Mitigation as described above.
Revisiegeschiedenis (4)
Initiële publicatie — 19 november 2020
Initial revision.
Update A — 6 november 2024
Fix: correct certvde domain, added alias, added self-reference
Update B — 11 april 2025
Fix: version range
Update C — 14 mei 2025
Fix: added distribution
VDE-2021-044
Endress+Hauser: Multiple products affected by log4net vulnerability
Risk evaluation
Apache log4net versions before 2.0.10 do not disable XML external entities when parsing log4net configuration files. This allows for XXE-based attacks in applications that accept attacker-controlled log4net configuration files.
Mitigatiesamenvatting
Make sure that no unauthorized access to the production environment is possible. Avoid using the above listed software with Windows administrator privileges if other users with lower privileges have access to the same software installation.
Revisiegeschiedenis (3)
Initiële publicatie — 20 januari 2022
Initial revision.
Update A — 12 februari 2025
Fix: corrected self-reference, fixed version
Update B — 14 mei 2025
Fix: added distribution
VDE-2020-031
Endress+Hauser: Multiple products prone to WIBU CodeMeter vulnerabilities
Gepubliceerd
27 oktober 2020
Laatste update
14 mei 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
For further Information please refer to WIBU Advisories directly at https://wibu.com/support/security-advisories.html and the aforementioned CVE-IDs.
Mitigatiesamenvatting
WIBU SYSTEMS has released a new Code Meter Runtime version 7.10a dated on 16.9.2020. All the known vulnerabilities are fixed with this version. The version is available at https://www.wibu.com/support
Revisiegeschiedenis (4)
Initiële publicatie — 27 oktober 2020
Initial revision.
Update A — 6 november 2024
Fix: added self-reference
Update B — 11 april 2025
Fix: version range, remove Issuing authority
Update C — 14 mei 2025
Fix: added distribution
VDE-2021-040
Endress+Hauser: Promass 83 with EtherNet/IP affected by a stack-based buffer overflow
Risk evaluation
Promass 83 devices utilizing 499ES EtherNet/IP (ENIP) Stack by Real Time Automation (RTA) are vulnerable to a stack-based buffer overflow. Update A, 2021-10-07: added credits changed title from "ENDRESS+HAUSER: Promass 83 with Ether/IP affected by DoS vulnerability" to "ENDRESS+HAUSER: Promass 83 with EtherNet/IP affected by a stack-based buffer overflow"
Mitigatiesamenvatting
If an immediate firmware update is not possible, the only way to prevent an attack is to disable communication via EtherNet/IP.
Revisiegeschiedenis (3)
Initiële publicatie — 4 oktober 2021
Initial revision.
Update A — 7 oktober 2021
Update A
Update B — 14 mei 2025
Fix: firmware category, added distribution
VDE-2021-010
Endress+Hauser: products utilizing WPA2 vulnerable to KRACK attacks
Gepubliceerd
18 mei 2021
Laatste update
14 mei 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Endress+Hauser products utilizing WPA2 are vulnerable to KRACK attacks. Proline portfolio is a flow meter with an optional WLAN interface in the display. The flowmeters are only affected if the optional WLAN display is present.
Mitigatiesamenvatting
If an immediate firmware update is not possible, the WLAN on the unit can also be switched off as a precautionary measure.
Revisiegeschiedenis (2)
Initiële publicatie — 15 mei 2021
Initial revision.
Update A — 14 mei 2025
Fix: version space, added distribution
VDE-2020-021
Endress+Hauser: Ecograph T utilizing Webserver firmware version 1.x suffers from improper privilege management
Gepubliceerd
19 november 2020
Laatste update
11 april 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
The affected device has a web-based user interface with a role-based access system. Users with different roles have different write and read privileges. The access system is based on dynamic "tokens".
Mitigatiesamenvatting
Customers should configure a perimeter firewall to block traffic from untrusted networks and users to the device. These recommendations will be incorporated into the device documentation (operating instructions). Change default password for operator, service and admin account. Endress+Hauser will not change this behavior. Customers are recommended to take the measures for Temporary Fix / Mitigation as described above.
Revisiegeschiedenis (2)
Initiële publicatie — 19 november 2020
Initial revision.
Update A — 11 april 2025
Fix: version range
Gepubliceerd
6 maart 2025
Laatste update
6 maart 2025
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Several vulnerabilities in the Endress+Hauser MEAC300-FNADE4 were discovered, that can be accessed via Ethernet.
Mitigatiesamenvatting
Customers are strongly advised to update to the newest version.
Revisiegeschiedenis (1)
Initiële publicatie — 6 maart 2025
Initial version
VDE-2024-041
Endress+Hauser: Multiple products are vulnerable to code injection
Gepubliceerd
10 september 2024
Laatste update
10 september 2024
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Echo Curve Viewer is an utility used for offline visualization of previously recorded envelope curve data. Envelope curve records are exported from other Endress+Hauser software products like FieldCare as .curves files. Echo Curve Viewer opens .curves files and displays their contents. The .curves files contain device- specific C# calculation scripts as .cs files, that are needed for the interpretation of certain curve record types. Echo Curve Viewer loads .curves files and executes the contained C# code.
Mitigatiesamenvatting
- For standalone Echo Curve Viewer installations, download and install Echo Curve Viewer version >=6.00.00 from the Endress+Hauser Software Portal - For bundled installations with FieldCare SFE500, download and install FieldCare SFE500 Package version >= 1.40.1 from the Endress+Hauser Software Portal external link - For Field Xpert Devices, the required update is installed automatically during startup. This requires a working internet connection and (under certain circumstances) a valid maintenance period and/or a connection to the E+H Netilion Cloud. Please refer to the Field Xpert documentation for details regarding the update mechanism.
Revisiegeschiedenis (1)
Initiële publicatie — 10 september 2024
Initial revision.
VDE-2022-019
Endress+Hauser: Multiple products utilizing vulnerable WIBU-SYSTEMS CodeMeter components
Gepubliceerd
2 juni 2022
Laatste update
2 juni 2022
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
For detailed information please refer to WIBU SYSTEMS original Advisories at https://wibu.com/support/security-advisories.html.
Mitigatiesamenvatting
All vulnerabilities have already been fixed in several CodeMeter versions. Endress+Hauser recommends to use CodeMeter version >=7.40b. The version is available at https://www.wibu.com/support. For the Operating System WIN 7 it's recommended to update the operating system, use/re-install the Endress+Hauser Software Application supporting the newer operating system and update Code Meter to version >= 7.40b.
Revisiegeschiedenis (1)
Initiële publicatie — 2 juni 2022
Initial revision.
VDE-2022-006
Endress+Hauser: FieldPort SFP50 Memory Corruption in Bluetooth Controller Firmware
Gepubliceerd
24 maart 2022
Laatste update
24 maart 2022
Gekoppelde CVE's
Getroffen sectoren
Risk evaluation
Possible memory corruption in BT controller when it receives an oversized LMP packet over 2-DH1 link and leads to denial of service.
Mitigatiesamenvatting
Endress+Hauser recommends using the FieldPort SFP50 only in secure environment and to allow access tothe devices only to authorized persons.
Revisiegeschiedenis (1)
Initiële publicatie — 24 maart 2022
Initial revision.