VDE-2026-004

WAGO: Vulnerabilities in Managed Switch

WAGO — Industrial Managed Switch

WAGO PSIRTcritical

Published

9 February 2026

Last update

9 February 2026

Affected sectors

Risk evaluation

Several vulnerabilities have been identified in the WAGO 852‑1328 device's web‑based management interface, which is implemented using a modified lighttpd server and custom CGI binaries. These issues include multiple stack buffer overflows, an authentication bypass, and insecure credential storage.

Mitigation summary

Please update your devices to the specified fixed firmware version 02.65.

Revision history (1)
  1. Initial publication — 9 February 2026

    Release version.

Official source: WAGO PSIRT

VDE-2021-011

TRUMPF Laser GmbH: TruControl 2.14.0 to 3.14.0 affected by recent sudo vulnerability

TRUMPF — redpowerDirect

TRUMPF PSIRThigh

Published

22 March 2021

Last update

2 February 2026

Linked CVEs

Affected sectors

Risk evaluation

TruControl laser control software from versions 2.14.0 to 3.14.0 use sudo versions affected by CVE-2021-3156. The affected sudo has a heap-based buffer overflow, allowing privilege escalation to root via "sudoedit -s" and a command-line argument that ends with a single backslash character.

Mitigation summary

- Update to TruControl version 3.16.0 or higher or - Please contact your service partner (service.tls@trumpf.com) for instructions on how to retrieve the patch

Revision history (4)
  1. Initial publication — 22 March 2021

    initial revision

  2. Update A — 10 April 2025

    Fixed csaf reference URL and publisher information.

  3. Update B — 14 May 2025

    Fix: added distribution

  4. Update C — 2 February 2026

    Fix: CSAF Document Alias had the wrong VDE-ID, changed revision versioning scheme to semver

Official source: TRUMPF PSIRT

PPSA-2026-001

Pilz: Multiple Vulnerabilities affecting the PIT User Authentication Service

Pilz — PIT User Authentication Service

Pilz PSIRThigh

Published

2 February 2026

Last update

2 February 2026

Affected sectors

Risk evaluation

**PIT User Authentication Service is part of the operating mode selection and access permission system PITmode.** The PIT User Authentication Service is affected by multiple vulnerabilities in included third-party components.

Mitigation summary

Limit network access to the PITreader and PIT User Authentication Service by using a firewall, a host-based firewall or similar measures.

Revision history (2)
  1. Initial publication — 2 February 2026

    Initial Version

  2. Update A — 2 February 2026

    Summary has been updated.

Official source: Pilz PSIRT

FSA-202302

Festo: Several vulnerabilities in FactoryViews

Festo — FactoryViews

Festo PSIRTcritical

Risk evaluation

FactoryViews bundles many third-party applications which are used in background processes to provide the software's features. From time to time, vulnerabilities in these bundled applications are discovered. These are typically fixed in newer versions of FactoryViews by updating the bundled applications. FactoryViews versions up to and including 1.5.2 contain around 200 such vulnerabilities listed in this advisory.Version 1.6.0 is a security rollup release which includes updates to all bundled applications and fixes these vulnerabilities. At this time, FactoryViews Lite cannot be updated beyond version 1.1. FactoryViews 1.7 unifies the non-Lite and Lite versions and fixes these vulnerabilities for users of FactoryViews Lite.

Mitigation summary

FactoryViews (non-Lite): Upgrade to FactoryViews 1.6.0. See the upgrade guide for information on how to upgrade. FactoryViews Lite: Upgrade to FactoryViews 1.7.0. See the upgrade guide for information on how to upgrade.

Revision history (4)
  1. Initial publication — 10 July 2023

    Initial revision.

  2. Update A — 11 January 2024

    Adjust link to VDE Advisory.

  3. Update B — 31 July 2025

    Adjusted to VDE template. Changed title from "Several Vulnerabilities in FactoryViews <= 1.5.2" to "Festo: Several vulnerabilities in FactoryViews". Updated legal disclaimer to add references to special provisions. Included remediation for FactoryViews Lite

  4. Update C — 2 February 2026

    Added missing CWE values

Official source: Festo PSIRT

VDE-2025-092

Beckhoff: Privilege escalation and information leak via Beckhoff Device Manager

Beckhoff — Beckhoff.Device.Manager.XAR

Beckhoff PSIRThigh

Published

27 January 2026

Last update

27 January 2026

Affected sectors

Risk evaluation

The vulnerability CVE-2025-41726 (NN-2025-0074) allows an authenticated remote user to execute arbitrary commands on the device. This can be exploited over the web UI or via API. In one case the execution of the arbitrary command happens within a privileged process. The vulnerability CVE-2025-41727 (NN-2025-0075) allows a local user with low privileges on the device to bypass the authentication mechanism of the UI and send commands to a privileged process which it executes on behalf of that user but with higher privileges. This way the local user can escalate privileges. The vulnerability CVE-2025-41728 (NN-2025-0076) allows an authenticated remote user to cause an out-of-bounds read operation within a specific service process which runs on the device. The read operation might copy sensitive information from the memory of the specific service into a response message which is then provided to the user but the user cannot choose which information is disclosed.

Mitigation summary

Please update to a recent version of the affected components or update the complete operating system image. Operating system images are available on request from Beckhoff's service (service@beckhoff.com). The setup / installer for Windows 10 and 11 are available on request from Beckhoff's service also.

Revision history (2)
  1. Initial publication — 20 January 2026

    Initial revision

  2. Update A — 27 January 2026

    fixed date

Official source: Beckhoff PSIRT

VDE-2025-095

WAGO: Vulnerabilities in WAGO Industrial-Managed Switches

WAGO — Industrial Managed Switch

WAGO PSIRTcritical

Published

10 December 2025

Last update

19 January 2026

Affected sectors

Risk evaluation

Two remote stack buffer overflow vulnerabilities were discovered in WAGO industrial switches. These issues originate from unsafe input handling in custom HTTP request parsing functions within the lighttpd binary. The affected binary lacks modern security features such as PIE and RELRO, increasing the risk of successful exploitation.

Mitigation summary

Please update your devices to the specified fixed firmware version.

Revision history (3)
  1. Initial publication — 10 December 2025

    Initial release.

  2. Update A — 11 December 2025

    Updated CVSS-Scores

  3. Update B — 19 January 2026

    Updated model numbers.

Official source: WAGO PSIRT

VDE-2024-012

ifm: Vulnerabilities in ifm AC14 firmware

ifm — Smart PLC

ifm PSIRTcritical

Published

9 July 2024

Last update

15 January 2026

Affected sectors

Risk evaluation

In ifm Smart PLC firmware up to version 4.3.17 for Smart PLC controllers AC14xx and AC4xxS, an attacker can access the configuration by using the hardcoded credentials. The endpoint hosts a scripts capable of executing various commands.

Mitigation summary

When using automation components, make sure that no unauthorized access can take place. Addition measures should be taken to ensure that the components do not have direct access to Internet resources and that they cannot be accessed from insecure networks. Use available security measures such as authentication and authorization groups.

Revision history (4)
  1. Initial publication — 9 July 2024

    Initial revision.

  2. Update A — 27 August 2025

    Update: CWE from CVE-2024-28751, Revision History

  3. Update B — 6 January 2026

    Fixed Version range, Added Score to Vulnerability CVE-2024-28750, deleted "firmware" from the full product name of the hardware, changed Vulnerability title to CVE description

  4. Update C — 15 January 2026

    Update Product information

Official source: ifm PSIRT

VDE-2024-028

ifm moneo password reset can be exploited

ifm — QVA200

ifm PSIRTcritical

Published

6 May 2024

Last update

15 January 2026

Linked CVEs

Affected sectors

Risk evaluation

moneo \"Forgot Password\" function has a vulnerability which allows gaining privileged access.

Mitigation summary

Update to moneo version 1.13.5 or later.

Revision history (4)
  1. Initial publication — 6 May 2024

    initial revision

  2. Update A — 24 May 2024

    final draft

  3. Update B — 27 May 2024

    Update

  4. Update C — 3 June 2024

    Update after review

Official source: ifm PSIRT

VDE-2025-073

Phoenix Contact: Security Advisory for TC ROUTER and CLOUD CLIENT Industrial mobile network routers

Phoenix Contact — TC ROUTER

Phoenix Contact PSIRThigh

Published

13 January 2026

Last update

13 January 2026

Linked CVEs

Affected sectors

Risk evaluation

A code injection vulnerability at the upload-config endpoint in the firmware of TC ROUTER and CLOUD CLIENT Industrial Mobile network routers has been discovered that can be exploited by an high privileged attacker.

Mitigation summary

As this vulnerability can only be exploited by an authenticated high privileged user, Phoenix Contact recommends to strictly restrict administrative access to the device. The administrative use shall only import configuration files from trusted sources.

Revision history (1)
  1. Initial publication — 13 January 2026

    Initial Revision

Official source: Phoenix Contact PSIRT

VDE-2025-071

Phoenix Contact: Multiple Vulnerabilities in FL SWITCH 2xxx Firmware

Phoenix Contact — FL SWITCH

Phoenix Contact PSIRThigh

Risk evaluation

Multiple vulnerabilities have been identified in the FL SWITCH 2xxx firmware prior to version 3.50. Two of these (CVE-2025-41692 and CVE-2025-41696) enable an attacker to access the device's file system. Two other vulnerabilities (CVE-2025-41693 and CVE-2025-41694) are related to Denial of Service (DoS) attacks, which partly limit the device's functionality. Another vulnerability (CVE-2025-41697) allows an unauthenticated physical attacker to access a login shell via an undocumented UART port. Furthermore, there are multiple vulnerabilities relating to reflected cross-site scripting in the web-based management of the device. All vulnerabilities have been resolved in firmware version 3.50.

Mitigation summary

Phoenix Contact strongly recommends to upgrade to firmware 3.50 which addresses this vulnerability and is available for download for all affected devices.

Revision history (2)
  1. Initial publication — 9 December 2025

    Initial release.

  2. Update A — 12 January 2026

    Version range specifier and product idfentification helper added to firmware branch of product tree.

Official source: Phoenix Contact PSIRT

VDE-2022-050

IFM: weak password recovery vulnerability in moneo appliance

ifm — QHA210

ifm PSIRTcritical

Published

12 December 2022

Last update

6 January 2026

Linked CVEs

Affected sectors

Risk evaluation

An unauthenticated remote attacker could reset the administrator's password with information from the default, self-signed certificate.

Mitigation summary

The certificate is renewed by adjusting the hostname to an own customer-specific, so it does not contain the serial number.

Revision history (2)
  1. Initial publication — 12 December 2022

    Initial revision.

  2. Update A — 6 January 2026

    fixed version range, added Hardware with relationship, changed vulnerability title to CVE description

Official source: ifm PSIRT

FSA-202402

Several Vulnerabilities in MES PC (Windows 10)

Festo — MES-PC

Festo PSIRTcritical

Risk evaluation

MES PCs shipped with Windows 10 come pre-installed with XAMPP. XAMPP is a bundle of third-party open-source applications including the Apache HTTP Server, the MariaDB database and more. From time to time, vulnerabilities in these applications are discovered. These are fixed in newer versions of XAMPP by updating the bundled applications. MES PCs shipped with Windows 10 include a copy of XAMPP which contains around 140 such vulnerabilities listed in this advisory. They can be fixed by replacing XAMPP with Festo Didactic's Factory Control Panel application.

Mitigation summary

Festo Didactic has released Factory Control Panel as a replacement for XAMPP on its MES PCs. Contact technical support at services.didactic@festo.com to obtain the current version of Factory Control Panel which includes fixes for these vulnerabilities.

Revision history (3)
  1. Initial publication — 27 February 2024

    Initial version

  2. Update A — 4 November 2025

    Adjust to VDE template. Add missing CWE-IDs if available. Updated legal disclaimer to add references to special provisions.

  3. Update B — 8 December 2025

    Add all missing CWE identifier and CVSS 3.x scores.

Official source: Festo PSIRT

Advisory2025-11_VDE-2025-101

CODESYS Development System - Deserialization of Untrusted Data

CODESYS — CODESYS Development System

CODESYS PSIRThigh

Published

1 December 2025

Last update

1 December 2025

Linked CVEs

Affected sectors

Risk evaluation

A vulnerability has been discovered in the print engine of the CODESYS development system. If a CODESYS project file or archive file was crafted in a specific way, the CODESYS development system could execute arbitrary code when a user opens these files and configures the print/printer options or prints the project or parts of it. This arbitrary code would be executed in the context of the user who was tricked into opening the project.

Mitigation summary

Open/install CODESYS archives, projects and packages from trustworthy sources only.

Revision history (1)
  1. Initial publication — 1 December 2025

    Initial revision.

Official source: CODESYS PSIRT

VDE-2025-094

Janitza: Vulnerability in Modbus interface of UMG 96-PA and UMG 96-PA-MID+

Janitza — UMG 96-PA

Janitza PSIRThigh

Published

24 November 2025

Last update

24 November 2025

Linked CVEs

Affected sectors

Risk evaluation

A vulnerability in the devices UMG 96-PA and UMG 96-PA-MID+ enables an unauthenticated remote attacker to cause the device to become unavailable.

Mitigation summary

It is strongly advised to operate the device in a closed network protected by a suitable firewall. Network access to the device should be limited to only enable necessary components to access it. Special focus should be on the Modbus protocol as the core communication protocol of the device.

Revision history (1)
  1. Initial publication — 24 November 2025

    Initial release.

Official source: Janitza PSIRT

VDE-2025-018

WAGO: Vulnerabilities in WAGO Device Manager

WAGO — CC100

WAGO PSIRTmiddel

Published

16 June 2025

Last update

21 November 2025

Affected sectors

Risk evaluation

Vulnerabilities have been discovered in the WAGO Device Manager that allow any origin to access the server and set header values, as well as an endpoint that permits read access to the file system. The WAGO Device Manager is a software for configuring and parameterizing single WAGO products, which is included in the firmware. These vulnerabilities could be exploited by attackers to send requests and read server responses through crafted web applications or to access the file system.

Mitigation summary

Update to Firmware version 04.07.01 (FW29) or 03.10.11 (FW22 Patch 2). For the latest Custom Firmware please contact the WAGO support.

Revision history (4)
  1. Initial publication — 16 June 2025

    Initial release.

  2. Update A — 4 July 2025

    Removed incorrect custom firmware versions.

  3. Update B — 7 October 2025

    Fixed a typo in the description for CVE-2025-25264

  4. Update C — 21 November 2025

    The two CVE descriptions and CVSS scores were edited.

Official source: WAGO PSIRT

VDE-2025-086

Jumo: Predictable debug-interface password in variTRON series

JUMO — variTRON300

JUMO PSIRThigh

Published

10 November 2025

Last update

10 November 2025

Linked CVEs

Affected sectors

Energieopwekking

Risk evaluation

A vulnerability was identified in the variTRON password generation algorithm of the debug-interface. The PRNG is initialized with the current Unix Timestamp, thus the resulting password is predictable. With the password root-access to the UART and ssh Interface can be gained. The impact is limited, since the debug-interface has to be actively enabled by an authorized user and will be deactivated automatically after the next reboot of the device.

Mitigation summary

Update the affected products to version 9.0.2.5.

Revision history (1)
  1. Initial publication — 10 November 2025

    Release version.

Official source: JUMO PSIRT

FSA-202405

Festo: Siemens S7-1500/ET200SP CPU used in Festo Didactic products contains a memory protection bypass vulnerability

Festo — Didactic CP including S7 PLC

Festo PSIRTcritical

Published

9 September 2024

Last update

5 November 2025

Linked CVEs

Affected sectors

Risk evaluation

Siemens SIMATIC S7-1200 and S7-1500 CPUs contained in various Festo Didactic products contain a memory protection bypass vulnerability that could allow an attacker to write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks

Mitigation summary

Update Siemens Simatic S7-1500 / ET200SP Firmware to V2.9.2 or higher

Revision history (4)
  1. Initial publication — 9 September 2024

    Initial version

  2. Update A — 6 November 2024

    Fix: correct certvde domain, fixed language setting, added self-reference

  3. Update B — 27 February 2025

    Update: new Dokument ID

  4. Update C — 5 November 2025

    Removed environmental score from CVSS rating.

Official source: Festo PSIRT

FSA-202401

Festo: Multiple products contain CoDe16 vulnerability

Festo — Control block CPX-CEC

Festo PSIRThigh

Risk evaluation

Several high severity vulnerabilities in CODESYS V3 affecting Festo products could lead to Remote Code Execution or Denial of Service.

Mitigation summary

As part of a security strategy, Festo recommends the following general defense measures to reduce the risk of exploits: - Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside - Use firewalls to protect and separate the control system network from other networks - Use VPN (Virtual Private Networks) tunnels if remote access is required Activate and apply user management and password features - Use encrypted communication links - Limit the access to both development and control system by physical means, operating system features, etc. - Protect both development and control system by using up to date virus detecting solutions Festo strongly recommends to minimize and protect network access to connected devices with state of the art techniques and processes. For a secure operation follow the recommendations in the product manuals.

Revision history (2)
  1. Initial publication — 30 January 2024

    Initial revision.

  2. Update A — 4 November 2025

    Adjusted to VDE template. Changed title from "Several Codesys Vulnerabilities in Festo Products" to "Festo: Multiple products contain CoDe16 vulnerability". Updated legal disclaimer to add references to special provisions.

Official source: Festo PSIRT

VDE-2025-062

WAGO: Multiple Vulnerabilities in CODESYS components

WAGO — CC100

WAGO PSIRThigh

Published

3 November 2025

Last update

3 November 2025

Affected sectors

Risk evaluation

Several WAGO firmwares installed on different devices are impacted by various CODESYS vulnerabilities. These affect the runtime, visualization, and OPC UA server.

Mitigation summary

Update to Firmware version 04.08.01 (FW30), 01.05.01 (FW05), 03.10.11 (FW22 Patch 2). For the latest Custom Firmware please contact the WAGO support.

Revision history (1)
  1. Initial publication — 3 November 2025

    Release version.

Official source: WAGO PSIRT

FSA-202202

Festo: Controller CECC-S,LK,D family <= 2.3.8.1 - multiple vulnerabilities in CODESYS V3 runtime system

Festo — Controller CECC-D

Festo PSIRTcritical

Risk evaluation

The Festo controller CECC product family is affected by multiple vulnerabilities in the CODESYS V3 runtime.

Mitigation summary

For CVE-2019-5105, CVE-2019-9011, CVE-2019-9013, CVE-2020-10245, CVE-2020-12067, CVE-2020-12068, CVE-2020-12069, CVE-2020-15806, CVE-2021-29241, CVE-2021-29242, CVE-2021-33485, CVE-2021-36763, CVE-2021-36764, CVE-2022-22513, CVE-2022-22514, CVE-2022-22515, CVE-2022-22517, CVE-2022-22519: No fix planned. This issue will be handled with next hardware generation release.

Revision history (4)
  1. Initial publication — 18 July 2022

    Initial revision.

  2. Update A — 11 January 2024

    Adjust link to VDE Advisory, TLP and update some CVE information, where CVSS was not known before.

  3. Update B — 28 July 2025

    Adjusted to VDE template. Changed title from 'Festo Controller CECC-S,-LK,-D Family Firmware <= 2.3.8.1 - Multiple Vulnerabilities in CODESYS V3 Runtime System' to 'Festo: Controller CECC-S,LK,D family <= 2.3.8.1 - multiple vulnerabilities in CODESYS V3 runtime system'. Updated legal disclaimer to add references to special provisions.

  4. Update C — 3 November 2025

    Add missing CWE values for vulnerabilities. Add missing CVSS 3.0 score for CVE-2010-5250.

Official source: Festo PSIRT

FSA-202209

Festo: Incomplete documentation of remote accessible functions and protocols in Festo products

Festo — Bus module CPX-E-EP

Festo PSIRTcritical

Published

29 November 2022

Last update

3 November 2025

Linked CVEs

Affected sectors

Risk evaluation

Incomplete Festo product documentation of remote accessible functions and their required IP ports. Depending on the product a description of the supported features can be found in the product documentation to some extent. Update A, 2022-12-13 Added affected device "Bus module CPX-E-PN, 4080497"

Mitigation summary

Update of technical user manual documentation in next product version.

Revision history (4)
  1. Initial publication — 29 November 2022

    Initial revision.

  2. Update A — 5 December 2022

    added bus module CPX-E-PN as affected product

  3. Update B — 6 April 2023

    adjusted technical user documentation to user documentation and fixed some typos.

  4. Update C — 3 November 2025

    Adjust link to VDE Advisory. Change title from "Incomplete User Documentation of Remote Accessible Functions and Protocols in Festo Products" to "Festo: Incomplete documentation of remote accessible functions and protocols in Festo products". Updated legal disclaimer to add references to special provisions.

Official source: Festo PSIRT

FSA-202208

Festo: Multiple Festo products contain an unsafe default Codesys configuration

Festo — Compact Vision System SBO*-Q-*

Festo PSIRTcritical

Published

29 November 2022

Last update

28 October 2025

Affected sectors

Risk evaluation

The products are shipped with an unsafe configuration of the integrated CODESYS Runtime environment. In this case no default password is set to the CODESYS PLC and therefore access without authentication is possible. With a successful established connection to the CODESYS Runtime the PLC-Browser commands are available. Thus granting the possibilities to e.g. read and modify the configuration file(s), start/stop the application and reboot the device.

Mitigation summary

Festo has identified the following compensatory measures to reduce the risk: - For CVE-2022-22515: Using the online user management prevents an attacker from downloading and execute malicious code, but also suppresses start, stop, debug, or other actions on a known working application that could potentially disrupt a machine or system.

Revision history (3)
  1. Initial publication — 29 November 2022

    Initial revision.

  2. Update A — 11 January 2024

    Adjust link to VDE Advisory

  3. Update B — 28 October 2025

    Adjusted to VDE template. Changed title from "Multiple Festo products contain an unsafe default Codesys configuration" to "Festo: Multiple Festo products contain an unsafe default Codesys configuration". Updated legal disclaimer to add references to special provisions.

Official source: Festo PSIRT

PPSA-2025-004

Pilz: Vulnerability affecting PASvisu Runtime

Pilz — PMIv7xxe

Pilz PSIRThigh

Published

20 October 2025

Last update

20 October 2025

Linked CVEs

Affected sectors

Risk evaluation

The PASvisu Runtime is affected by a vulnerability in a third-party component which can be exploited by a malicious web request.

Mitigation summary

Limit network access to PASvisu server by using a firewall, a host-based firewall or similar measures.

Revision history (1)
  1. Initial publication — 20 October 2025

    Initial Version

Official source: Pilz PSIRT

VDE-2025-074

Phoenix Contact: Security Advisory for CHARX SEC-3xxx charging controllers

Phoenix Contact — CHARX SEC

Phoenix Contact PSIRThigh

Published

14 October 2025

Last update

15 October 2025

Linked CVEs

Affected sectors

Risk evaluation

A vulnerability in the firmware of CHARX SEC-3xxx charging controllers has been discovered.

Mitigation summary

This product was designed for use in closed industrial networks. Phoenix Contact strongly recommends operating network-capable devices in closed networks or protected with a suitable firewall. For detailed information on our recommendations for measures to protect network-capable devices, please refer to our [application note](https://dam-mdc.phoenixcontact.com/asset/156443151564/0a870ae433c19148b80bd760f3a1c1f2/107913_en_03.pdf).

Revision history (2)
  1. Initial publication — 8 July 2025

    Initial Revision

  2. Update A — 15 October 2025

    Updated the reporting credits, corrected reference token for one product, fixed typo in Document notes

Official source: Phoenix Contact PSIRT

VDE-2025-091

Murrelektronik: Cleartext Transmission of Sensitive Information in IMPACT67 Pro

Murrelektronik — Impact67 Pro

Murrelektronik PSIRThigh

Published

14 October 2025

Last update

14 October 2025

Linked CVEs

Affected sectors

Risk evaluation

The embedded web interface of the MURRELEKTRONIK IMPACT67 Pro PN DIO8 IOL8 transmits login credentials over unencrypted HTTP using a GET request. The device does not offer HTTPS/TLS support, exposing user credentials to passive interception by any attacker on the same network.

Mitigation summary

Murrelektronik recommends: * Deactivating the Webserver will prevent any data from being sent unencrypted. More information on how to disable the webserver can be found in the manual. * Deactivating all unused network ports in the unit will prevent data sniffing. * Segmenting the network strictly helps to minimize unauthorized access to network traffic. If the webserver must stay activated, this is recommended to reduce the security breaches impact. * Advise users of the system to not use personal data or standard passwords for the webserver accounts. This helps to prevent personal data leakage.

Revision history (1)
  1. Initial publication — 14 October 2025

    initial release

Official source: Murrelektronik PSIRT