Advisory2026-03_VDE-2026-018

CODESYS Control V3 - Externally-controlled format string in Auditlog

CODESYS — CODESYS Control RTE (SL)

CODESYS PSIRThigh

Published

24 March 2026

Last update

18 June 2026

Linked CVEs

Affected sectors

Risk evaluation

The CODESYS Control runtime system's CmpAuditLog component allows potentially unauthenticated remote attackers to control the format string of processed log messages. Due to the internal processing logic, the impact is limited to a crash of the CODESYS Control runtime.

Mitigation summary

As a mitigation, the Audit Log feature can be disabled in the CODESYS Control runtime configuration file. When the Audit Log logger is not enabled, the affected functionality is no longer exposed and the vulnerability cannot be exploited. To disable the Audit Log feature, use the following settings. Depending on your existing configuration, the logger index may vary. [CmpLog] Logger.0.Name=.Audit.log Logger.0.Enable=0

Revision history (2)
  1. Initial publication — 24 March 2026

    Initial revision.

  2. Update A — 18 June 2026

    Updated remediation category - fixed SL runtimes are now available. Updated mitigation category - clarified description.

Official source: CODESYS PSIRT

Advisory2026-10_VDE-2026-057

CODESYS Control - Out-of-bounds Write

CODESYS — CODESYS Control RTE (SL)

CODESYS PSIRThigh

Published

26 May 2026

Last update

18 June 2026

Linked CVEs

Affected sectors

Risk evaluation

The CmpWebServer component in the CODESYS Control Runtime allows users to create browser-based visualizations for monitoring and controlling industrial processes. Due to improper bounds checking, a specially crafted HTTP request from an unauthenticated remote attacker may lead to a size-limited out-of-bounds write, causing a denial of service of the affected device. The CODESYS Control runtime system is only affected if the web server is active, which by default requires a running application with an enabled Web Visualization.

Mitigation summary

Update the following products to version 3.5.22.20. * CODESYS Control RTE (SL) * CODESYS Control RTE (for Beckhoff CX) SL * CODESYS Control Win (SL) * CODESYS HMI (SL) * CODESYS Runtime Toolkit The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.

Revision history (2)
  1. Initial publication — 26 May 2026

    Initial revision.

  2. Update A — 18 June 2026

    Updated remediation category - fixed SL runtimes are now available.

Official source: CODESYS PSIRT

Advisory2026-08_VDE-2026-056

CODESYS Control - Incorrect Authorization

CODESYS — CODESYS Control RTE (SL)

CODESYS PSIRThigh

Published

26 May 2026

Last update

18 June 2026

Linked CVEs

Affected sectors

Risk evaluation

The CODESYS Control runtime system provides a user management mechanism with multiple privilege groups including the visualization administrators group, which is intended solely to manage visualization users. Due to insufficient authorization checks an authenticated remote user with low-privileged visualization administrator access can delete higher-privileged accounts. However, independent mechanisms protect the deletion of the last remaining device admin user, preventing a complete loss of administrative access to the device. The CODESYS Control runtime system is only affected if the optional visualization user management feature is enabled and a visualization administrator account has been configured.

Mitigation summary

Update the following products to version 3.5.22.20. * CODESYS Control RTE (SL) * CODESYS Control RTE (for Beckhoff CX) SL * CODESYS Control Win (SL) * CODESYS HMI (SL) * CODESYS Runtime Toolkit The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.

Revision history (2)
  1. Initial publication — 26 May 2026

    Initial revision.

  2. Update A — 18 June 2026

    Updated remediation category - fixed SL runtimes are now available.

Official source: CODESYS PSIRT

Advisory2026-02_VDE-2026-011

CODESYS Control V3 - Untrusted boot application

CODESYS — CODESYS Control RTE (SL)

CODESYS PSIRThigh

Published

24 March 2026

Last update

18 June 2026

Linked CVEs

Affected sectors

Risk evaluation

The CODESYS Control runtime system provides a user management mechanism with multiple privilege groups. While only the privileged Administrators and Developer groups are intended to load or debug applications on the controller, users in the restricted Service group are allowed to perform maintenance operations, including explicitly replacing the boot application. In addition to access control, the CODESYS Control runtime system includes an optional application signing feature. When enabled, the controller executes only applications that have been validly signed by authorized developers. However, the CmpApp component of the CODESYS Control runtime systems allows Service‑group users to install a new boot application without requiring any cryptographic validation, if the application signing is not enforced. As a result, users with Service‑level privileges can install arbitrary boot applications and gain control over the code executed on the controller. Note: The user group "Service" is a predefined group within the CODESYS Control runtime system. If additional user groups have been created or if the permissions of predefined groups have been modified, then the term "Service" should be understood as a synonym for all groups and their users with no or only limited access rights to the "PlcLogic" object, in conjunction with "Add/Remove" or "Modify" permissions for the boot application files.

Mitigation summary

Without applying the update, the vulnerability can be mitigated by enforcing the use of signed applications through the following setting: [CmpApp] SECURITY.EnforceSignedCode=YES This can be configured either via the Device Security Settings dialog in the CODESYS Development System or directly in the configuration file of the CODESYS Control runtime system (CODESYSControl.cfg). When this option is enabled, the CODESYS Control runtime system loads only trusted and valid signed applications. Alternatively, all users belonging to the Service group can be removed, or the Service group can be deleted entirely. If none of the other mitigation options are feasible, the permissions of the Service group can be restricted by adjusting their access rights. For example, removing modify permissions for the Service group on relevant file system objects can prevent the upload of untrusted boot applications. However, such changes must be applied with caution, as they may lead to inconsistent permissions for this user group and result in unexpected operational limitations. Therefore, this approach should only be considered after a careful assessment of the specific situation.

Revision history (2)
  1. Initial publication — 24 March 2026

    Initial revision.

  2. Update A — 18 June 2026

    Updated remediation category - fixed SL runtimes are now available.

Official source: CODESYS PSIRT

SA26P010

Impact of Linux Kernel vulnerabilities on B&R products

B&R Industrial Automation GmbH — Linux for B&R

ABB PSIRThigh

Published

11 June 2026

Last update

18 June 2026

Affected sectors

Risk evaluation

B&R is aware of publicly reported vulnerabilities affecting the Linux kernel versions shipped with the products listed as affected in the advisory. Successful local exploitation of these vulnerabilities could allow an attacker to escalate privileges on the affected system. Public proof-of-concept exploits are available for the vulnerabilities described herein. At the time of publication of this advisory, B&R had no evidence of active exploitation targeting B&R products.

Mitigation summary

For affected products, software updates should be installed upon availability. Product Patch version - APROL : APROL-AutoYaST-DVD- V4.4-010.10.260602 Until remediated software versions are available, customers are required to conduct a risk assessment of their affected systems and to implement the mitigation measures and workarounds specified in this advisory.

Revision history (2)
  1. Initial publication — 11 June 2026

    Initial version.

  2. Update A — 18 June 2026

    Updating the CWE classification for CVE-2026-43494.

Official source: ABB PSIRT

7PAA020361

Freelance Security Lock - Access to Windows OS

ABB — System Version

ABB PSIRTmiddel

Published

10 June 2026

Last update

17 June 2026

Linked CVEs

Affected sectors

Risk evaluation

ABB is aware of a vulnerability in the product versions listed as affected in the advisory. An attacker who successfully exploited this vulnerability could cause the product to stop or make the product inaccessible.

Mitigation summary

ABB recommends using Freelance Extended User Management instead of Security Lock. Freelance Extended User Management is based on Windows user accounts and is available for Freelance 2019 or higher. For Freelance 2016 and earlier, please refer to chapter “General Security Information”. A fix for Freelance Security Lock is in preparation and will be announced in this updated document. Refer to section “General security recommendations” for further advise on how to keep your system secure. To reduce the likelihood of exploitation via keyboard shortcuts: - disable unnecessary accessibility features - use hardened OS configurations that suppress system-level shortcuts - implement BIOS/UEFI-level restrictions on keyboard input during runtime.

Revision history (2)
  1. Initial publication — 10 June 2026

    Initial version.

  2. Update A — 17 June 2026

    Correction on the product relationship

Official source: ABB PSIRT

VDE-2026-038

TURCK: Multiple Vulnerabilities in Managed Ethernet Switches

Turck — Managed Ethernet Switch TBEN-LL-SE-M2

Turck PSIRTcritical

Published

16 June 2026

Last update

16 June 2026

Affected sectors

Risk evaluation

Multiple vulnerabilities have been identified in the TBEN-Lx-SE-M2 firmware prior to version 2.1.2.0 in Managed Ethernet Switches.

Mitigation summary

Turck recommends to update to the latest 2.1.2.0 Firmware Release which fixes these vulnerabilities.

Revision history (2)
  1. Initial publication — 19 May 2026

    Initial revision.

  2. Update A — 16 June 2026

    The Initial revision date was wrong

Official source: Turck PSIRT

SA26P009

XZ Utils vulnerability impacting B&R Products

B&R Industrial Automation GmbH — PPC3100

ABB PSIRThigh

Published

10 June 2026

Last update

10 June 2026

Linked CVEs

Affected sectors

Risk evaluation

An update is available that resolves vulnerability in the product versions listed as affected in the advisory. An attacker who successfully exploited this vulnerability could cause the product to stop or corrupt memory data.

Mitigation summary

The problem is corrected in the following product versions: Product Terminal OS Version - PPC3100 1.8.1 - C50 1.8.0 - C80 1.8.0 - FT50 1.8.1 - MT50 1.8.1 - T30 1.8.0 - T80 1.8.0 - T50 1.8.1 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual.

Revision history (1)
  1. Initial publication — 10 June 2026

    Initial version.

Official source: ABB PSIRT

SEVD-2026-160-03

Multiple Vulnerabilities on PowerLogic™ P7

Schneider Electric — PowerLogic™ P7

Schneider Electric CPCERThigh

Published

9 June 2026

Last update

9 June 2026

Affected sectors

Risk evaluation

Schneider Electric is aware of a vulnerability in its PowerLogic™ P7 product. The PowerLogic™ P7 is a protection and control platform designed for complex and advanced electrical network applications. Failure to apply the remediation provided below may risk unauthorized execution of privileged commands or loss of HMI operability and configuration functionality, which could result in loss of control over system operations and disruption of critical services.

Mitigation summary

Version V02.004.001 of PowerLogicTM P7 includes a fix for this vulnerability and is available for download here: • Contact Schneider Electric’s Customer Care Center to download this firmware. • Reboot needed: Yes

Revision history (1)
  1. Initial publication — 9 June 2026

    Original Release

Official source: Schneider Electric CPCERT

SEVD-2026-160-01

Improper Restriction of XML External Entity Reference vulnerability on the EcoStruxure™ IT Data Center Expert

Schneider Electric — EcoStruxure IT Data Center Expert

Schneider Electric CPCERTmiddel

Published

9 June 2026

Last update

9 June 2026

Linked CVEs

Affected sectors

Risk evaluation

Schneider Electric is aware of a vulnerability in its EcoStruxure™ IT Data Center Expert. The EcoStruxure™ IT Data Center Expert product is a scalable monitoring software that collects, organizes, and distributes critical device information providing a comprehensive view of equipment. Failure to apply the remediation provided below may risk information disclosure.

Mitigation summary

v9.1.2 of EcoStruxure™ IT Data Center Expert includes a fix for this vulnerability and is available for download here: https://www.se.com/en/product-range/61851-ecostruxure-it-data- center-expert/#software-and-firmware

Revision history (1)
  1. Initial publication — 9 June 2026

    Original Release

Official source: Schneider Electric CPCERT

SEVD-2026-160-02

Multiple Vulnerabilities on EasyLogic T150 and Saitel DP RTU

Schneider Electric — EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller

Schneider Electric CPCERThigh

Published

9 June 2026

Last update

9 June 2026

Affected sectors

, Transmissie, Energieopwekking

Risk evaluation

Schneider Electric is aware of a vulnerability in its EasyLogic T150 (formerly known as Saitel DR) and Saitel DP Remote Terminal Unit & Controller products. The [EasyLogic T150 (formerly known as Saitel DR RTU)](https://www.se.com/ww/en/product-country-selector/?pageType=product-range&sourceId=62685#overview) is a field device, offering a solid and powerful modular platform for data acquisition, communication, automation and IED integration for distribution and transmission networks, generation sector and railway. The [Saitel DP RTU](https://www.se.com/ww/en/product-country-selector/?pageType=product-range&sourceId=61747) is a modular platform for medium voltage and high voltage public distribution and transmission substation control. Failure to apply the mitigations provided below may risk credential harvesting and unauthorized access attacks, which could result in exposure of sensitive information and compromise of device integrity and operations when an attacker has subsequent physical access to the device.

Mitigation summary

Version 11.06.32 of EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller includes a fix for these vulnerabilities and is available:• Contact Schneider Electric’s Customer Care Center to download this firmware.• Reboot needed: Yes.

Revision history (1)
  1. Initial publication — 9 June 2026

    Original Release

Official source: Schneider Electric CPCERT

VDE-2026-060

Phoenix Contact: Unauthenticated log download vulnerability in the firmware of CHARX SEC-3xxx charging controllers

Phoenix Contact — CHARX SEC

Phoenix Contact PSIRThigh

Published

3 June 2026

Last update

3 June 2026

Linked CVEs

Affected sectors

Risk evaluation

VDE-2026-060: A unauthenticated log download vulnerability in the firmware of CHARX SEC-3xxx charging controllers has been discovered.

Mitigation summary

Phoenix Contact strongly recommends to upgrade to firmware version 1.9.0 which fixes these vulnerabilities.

Revision history (2)
  1. Initial publication — 3 June 2026

    Initial revision

  2. Update A — 3 June 2026

    added "Firmware" to the textual description of the relationships.

Official source: Phoenix Contact PSIRT

9AKK108472A7840

Vulnerabilities in T-MAC Plus

ABB — T-MAC Plus

ABB PSIRTcritical

Published

3 June 2026

Last update

3 June 2026

Affected sectors

Risk evaluation

ABB became aware of vulnerability in the products versions listed as affected in the advisory. An update is available that resolves the reported vulnerabilities. An attacker who successfully exploited any of these vulnerabilities could potentially compromise the system in different ways.

Mitigation summary

ABB has investigated these vulnerabilities to provide adequate protection to customers. The problem is corrected in the following product versions: T-MAC Plus version 4.0-25 ABB recommends that customers apply the update at earliest convenience.

Revision history (1)
  1. Initial publication — 3 June 2026

    Initial version.

Official source: ABB PSIRT

VDE-2026-054

MB connect line: Multiple vulnerabilities in mbNET/mbNET.rokey/mbNET.mini

MB connect line — mbNET

MB connect line PSIRThigh

Published

27 May 2026

Last update

27 May 2026

Affected sectors

Risk evaluation

Two command injection vulnerabilities have been discovered in MB connect line mbNET/mbNET.rokey/mbNET.mini.

Mitigation summary

Update: - mbNET/mbNET.rokey: 8.4.5 - mbNET.mini: 3.0.3

Revision history (1)
  1. Initial publication — 27 May 2026

    Initial revision.

Official source: MB connect line PSIRT

VDE-2026-059

Helmholz: Multiple vulnerabilities in REX100/REX200/REX250

Helmholz — REX200/250

Helmholz PSIRThigh

Published

27 May 2026

Last update

27 May 2026

Affected sectors

Risk evaluation

Two command injection vulnerabilities have been discovered in Helmholz REX100/REX200/REX250.

Mitigation summary

Update: - REX200/250: 8.4.5 - REX100: 3.0.3

Revision history (1)
  1. Initial publication — 27 May 2026

    Initial revision.

Official source: Helmholz PSIRT

VDE-2026-050

Phoenix Contact: PLCnext Firmware Security Issues Related to APPs and Configuration Files

Phoenix Contact — AXC F

Phoenix Contact PSIRThigh

Published

27 May 2026

Last update

27 May 2026

Affected sectors

Risk evaluation

This advisory addresses security issues in PLCnext firmware versions prior to 2026.0.3 that are related to APP handling and the processing of configuration files. The identified vulnerabilities affect APP installation authenticity as well as the handling of configuration data in writable directories. Successful exploitation may allow authenticated attackers with different privilege levels to compromise integrity, availability, and system security of affected PLCnext Control. Both issues are resolved starting with PLCnext firmware version 2026.0.3.

Mitigation summary

For firmware versions prior to 2026.0.3 apps are installed via WBM (APP Manager) without enforced authenticity validation. Verify the SHA-256 checksum provided by the PLCnext Store manually before installing an APP. Restrict WBM access to trusted IP ranges via the firewall and protect Engineer credentials. Monitor APP lifecycle security notifications locally or via a central Syslog server. If APPs are not required, disable the APP Manager service via the WBM System Services page to eliminate an unnecessary attack vector. Starting with firmware version 2026.0.3, APP signature verification is enabled by default and only signed apps can be installed.

Revision history (1)
  1. Initial publication — 27 May 2026

    Initial

Official source: Phoenix Contact PSIRT

Advisory2026-09_VDE-2026-055

CODESYS Development System - Incorrect Default Permissions

CODESYS — CODESYS Development System

CODESYS PSIRThigh

Published

26 May 2026

Last update

26 May 2026

Affected sectors

Risk evaluation

Two local privilege escalation vulnerabilities were identified in the CODESYS Development System. Specifically, the PackageManager and the IPM create temporary directories with insecure default permissions when executed with administrative privileges. This allows low-privileged local users to modify a temporary bootstrap file to force the deployment of arbitrary components, or to exploit a Time-of-Check to Time-of-Use (TOCTOU) race condition to replace digitally verified installation files with malicious ones prior to installation. Both flaws bypass intended security boundaries during the installation of packages or add-ons.

Mitigation summary

Update the following product to version 3.5.22.20. * CODESYS Development System The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.

Revision history (1)
  1. Initial publication — 26 May 2026

    Initial revision.

Official source: CODESYS PSIRT

VDE-2026-009

JUMO: Multiple products affected by nodejs vulnerability

JUMO — variTRON300

JUMO PSIRTlow

Published

26 May 2026

Last update

26 May 2026

Linked CVEs

Affected sectors

Risk evaluation

A vulnerability in the REST API of the JUMO device allows an attacker to trigger a denial‑of‑service (DoS) condition. Due to an incorrect implementation of the arrayLimit option in the Node.js qs module, limits for incoming request parameters are not properly enforced. As a result, an attacker can send specially crafted requests containing excessively large or deeply nested arrays, causing the web server to become unresponsive. This condition leads to a crash of the web server, followed by an automatic restart of the device.

Mitigation summary

Update the affected products to version 431.10.0.0.26 for variTRON 300, to version 388.10.0.0.26 for variTRON 500 and to version 446.10.0.0.26 for variTRON 500 touch. The release of this versions are expected to Q2 2026.

Revision history (1)
  1. Initial publication — 26 May 2026

    Release version.

Official source: JUMO PSIRT

SA25P006

PPT30 OPC-UA Server has issues handling concurrent connections

B&R Industrial Automation GmbH — PPT30 Operating System

ABB PSIRThigh

Published

26 May 2026

Last update

26 May 2026

Linked CVEs

Affected sectors

Risk evaluation

B&R is aware of a vulnerability in the product versions listed as affected in the advisory. An attacker who successfully exploits this vulnerability could make the OPC-UA server of the product inaccessible.

Mitigation summary

The problem is corrected in the following product versions: PPT30 Operating System 1.8.0 The OPC-UA server is not activated by default. B&R recommends that customers with the OPC-UA Server enabled to install the update at their earliest opportunity. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual.

Revision history (1)
  1. Initial publication — 26 May 2026

    Initial version.

Official source: ABB PSIRT

VDE-2026-043

Helmholz: Multiple Vulnerabilities in myREX24V2/myREX24V2.virtual

Helmholz — myREX24V2

Helmholz PSIRTcritical

Published

13 April 2026

Last update

22 May 2026

Affected sectors

Risk evaluation

Multiple vulnerabilities have been discovered in Helmholz myREX24V2/myREX24V2.virtual that could allow RCE, SQLi or information leakage.

Mitigation summary

Update the myREX24V2/myREX24V2.virtual instance to version 2.19.5.

Revision history (2)
  1. Initial publication — 13 April 2026

    Initial revision.

  2. Update A — 22 May 2026

    Typo Fix

Official source: Helmholz PSIRT

7PAA023732

System 800xA affected by 3rd party component vulnerabilities

ABB — 800xA History

ABB PSIRThigh

Risk evaluation

ABB is aware of public reports of vulnerabilities in 7-Zip version 18.5 and Microsoft Azure Data Studio version 1.32 included in the product versions listed as affected in the advisory. The vulnerability in 7-Zip can be exploited if attacker gains control over the system and extracts a malicious file using this version of 7-Zip. Otherwise, the attacker must force the user to visit malicious websites or click links and extract the package through 7-zip. Microsoft Azure Data Studio gets installed along with SQL Server Management Studio. An attacker who successfully exploits vulnerability in Microsoft Azure Data studio may compromise the security of the product by gaining privileges, reading sensitive information, executing commands, evading detection, etc. if the Authentication, Authorization and Accountability is not configured properly in the system. However, none of the products listed above uses Microsoft Azure Data Studio. Microsoft Azure Data Studio is automatically removed from the system from System 800xA 7.0 onwards. These vulnerabilities may appear when the product media is scanned. However, they can only be ex-ploited if the vulnerable software is installed on the system. For this reason, it is strongly advised to uninstall outdated or vulnerable versions of third-party software immediately.

Mitigation summary

Workarounds are specific measures that a user can take to help block an attack, for example, temporarily disabling the vulnerable feature may remove the exposure with well-known impact on functionality. There are no workarounds. Uninstalling the affected third-party software fully eliminates the risk of vulnerabilities. Refer to the section ‘Recommended immediate actions’.

Revision history (2)
  1. Initial publication — 31 March 2026

    Initial version.

  2. Update A — 22 May 2026

    Added missing CVE description for CVE-2024-26203.

Official source: ABB PSIRT

3ADR011432

AC500 V2 Buffer overread on Modbus protocol

ABB — AC500 V2

ABB PSIRTmiddel

Published

23 July 2025

Last update

22 May 2026

Linked CVEs

Affected sectors

Risk evaluation

ABB became aware of vulnerabilities in AC500 V2 listed as affected in the advisory. An attacker who successfully exploited this vulnerability could access fragments of Modbus telegrams that have been sent earlier by that PLC

Mitigation summary

The vulnerabilities have been resolved in the following product versions: AC500 V2 firmware version 2.5.3 (released in 2016) and later

Revision history (2)
  1. Initial publication — 23 July 2025

    Initial version.

  2. Update A — 22 May 2026

    Minor correction to the affected product version in the product tree.

Official source: ABB PSIRT

Advisory2026-07_VDE-2026-052

CODESYS Visualization - Insufficiently Protected Credentials

CODESYS — CODESYS Visualization

CODESYS PSIRTmiddel

Published

21 May 2026

Last update

21 May 2026

Linked CVEs

Affected sectors

Risk evaluation

A vulnerability in the CODESYS Visualization login dialog has been identified. During logins within the CODESYS Visualization, authentication data may not be sufficiently isolated when multiple users perform login operations concurrently. As a result, an authenticated visualization user may be able to obtain credentials entered by another visualization user. The issue affects only login operations within an active visualization session and can be triggered via local and remote access to the visualization.

Mitigation summary

Two alternative mitigation options have been identified. One option is to avoid using the Input Action "User Management -> Login" for changing users within an active visualization session. Instead, use the Input Action "User Management -> Logout" to do a complete logout followed by a new Login to the Visualization to re-login with another user. Alternatively, property handling within the visualization can be disabled via Project Settings -> Visualization -> General -> Advanced -> "Activate property handling in all element properties", if this is not required for the compilation of the application.

Revision history (1)
  1. Initial publication — 21 May 2026

    Initial revision.

Official source: CODESYS PSIRT

VDE-2024-017

Pepperl+Fuchs: ICE2- * and ICE3- * are affected by multiple vulnerabilities

Pepperl+Fuchs — ICE2

Pepperl+Fuchs PSIRThigh

Published

10 April 2024

Last update

18 May 2026

Affected sectors

Risk evaluation

Critical vulnerabilities have been discovered in the product due to outdated software components.The impact of the vulnerabilities on the affected device may result in Denial of service Bypassing of authentication Information disclosure

Mitigation summary

External protective measures are required: Disable the webserver after configuration, if possible, by following these steps: - Enable SSH via the web server. - Login to the SSH server. - Disable the webserver via SSH portal. - Reboot the device. or: - Use HTTPS rather than HTTP while using the webserver. - Minimize network exposure for affected products and ensure that they are not accessible via the Internet. - Isolate affected products from the corporate network. - If remote access is required, use secure methods such as virtual private networks(VPNs). Pepperl+Fuchs will provide an update to address some of these vulnerabilities in the future.

Revision history (3)
  1. Initial publication — 10 April 2024

    Initial revision.

  2. Update A — 22 May 2025

    Fix: quotation mark

  3. Update B — 18 May 2026

    added score to vulnerability, Added CPEs, added last affected products to vulnerabilities

Official source: Pepperl+Fuchs PSIRT

SA25P007

B&R Automation Studio Update of SQLite version

B&R Industrial Automation GmbH — Automation Studio

ABB PSIRTcritical

Risk evaluation

ABB became aware of vulnerability in the product versions listed as affected in the advisory. An update is available that replaces an outdated third-party component. Although no successful exploitation was observed during testing of the affected B&R products, the identified vulnerabilities could present potential attack vectors that might enable unauthorized access, data exposure, or remote code execution.

Mitigation summary

The problem is corrected in the following product versions: B&R Automation Studio 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual.

Revision history (2)
  1. Initial publication — 18 February 2026

    Initial version.

  2. Update A — 14 May 2026

    Corrected vendor name from 'ABB' to 'B&R Industrial Automation GmbH' to ensure accurate product matching.

Official source: ABB PSIRT