CISA + vendors
ICS Advisories
Advisories specifically aimed at industrial control systems — from CISA ICS-CERT and directly from vendors (including Siemens, ABB, Schneider Electric, WAGO and Phoenix Contact) — including revision history (initial publication, Update A, Update B) and linked CVEs.
20
Found
Advisory data: live connection— last retrieved: 7 November 2026 at 00:32.
Filters
1 active20 advisories found
VDE-2026-084
Phoenix Contact: CodeMeter Runtime Security Vulnerabilities in License Validation in the PLCnext Firmware
Published
4 November 2026
Last update
4 November 2026
Affected sectors
Risk evaluation
This advisory addresses security vulnerabilities in Phoenix Contact products with an integrated CodeMeter Runtime, like PLCnext devices and Virtual Controls. These security vulnerabilities only may occur with versions <8.41a of the integrated software CodeMeter Runtime from Wibu-Systems. Please see listed products to determine which devices and firmware versions are affected.
Mitigation summary
Please check the Phoenix Contact e-Shop regularly to see if the fixed firmware is already available for your specific PLCnext device or Virtual PLCnext Control. The Fix is planned to be integrated in version 2026.0.6 which is planned for Q4/2026.
Revision history (1)
Initial publication — 4 November 2026
Initial
VDE-2026-098
Phoenix Contact: CodeMeter Runtime Security Vulnerabilities in License Validation for SW Tools
Phoenix Contact — CodeMeter Runtime licensed software components
Published
4 November 2026
Last update
4 November 2026
Affected sectors
Risk evaluation
This advisory addresses multiple security vulnerabilities in Phoenix Contact products using the software CodeMeter Runtime like licensed desktop software tools. These security vulnerabilities only may occur with CodeMeter Runtime 8.x versions <V8.41a and CodeMeter Runtime 9.x versions <9.10 from Wibu-Systems.
Mitigation summary
Updates for the affected products are planned for Q4 2026. Until the fix is available, please follow the mitigation measures and check the respective product page on the Phoenix Contact website regularly to see if the fix is already available.
Revision history (1)
Initial publication — 4 November 2026
Initial
VDE-2026-121
Phoenix Contact: GSDX SignatureValue verification, signed plug-in validation bypass and path traversal vulnerabilities in PLCnext Engineer programming software
Published
4 November 2026
Last update
4 November 2026
Affected sectors
Risk evaluation
GSDX SignatureValue verification, signed plug-in validation bypass and path traversal vulnerabilities have been identified in PLCnext Engineer prior to version 2026.6. The effects of these vulnerabilities may result in a complete loss of confidentiality, integrity and availability.
Mitigation summary
Phoenix Contact strongly recommends to upgrade to PLCnext Engineer 2026.6 which fixes these vulnerabilities.
Revision history (1)
Initial publication — 14 October 2026
Initial revision.
VDE-2026-027
Phoenix Contact: Multiple vulnerabilities in the firmware of IOL MA8 EIP DI8 and IOL MA8 PN DI8 devices
Published
16 September 2026
Last update
16 September 2026
Linked CVEs
Affected sectors
Risk evaluation
The firmware of IOL MA8 EIP DI8 and IOL MA8 PN DI8 devices is affected by security vulnerabilities that can be used to bypass authentication. Code can be executed on the devices through command injection and local file inclusion. Path traversal and modified schemata can be used to read sensitive information such as password hashes or private keys from the devices.
Mitigation summary
Phoenix Contact strongly recommends to update affected devices to firmware version 1.7.8.
Revision history (1)
Initial publication — 16 September 2026
Initial release.
vde-2025-056
Phoenix Contact: Improper Input Validation Vulnerabilities in PLCnext Firmware
Published
12 August 2026
Last update
12 August 2026
Linked CVEs
Affected sectors
Risk evaluation
This advisory addresses multiple security vulnerabilities in PLCnext firmware versions prior to 2026.0.3. The vulnerabilities may allow unauthenticated attackers to cause denial of service, trigger unexpected system behavior, or execute unauthorized SQL queries. Successful exploitation could impact the availability, integrity, and confidentiality of affected PLCnext Control devices. All issues are resolved in PLCnext firmware version 2026.0.3.
Mitigation summary
Update to PLCnext firmware version 2026.0.3 or later which fixes this vulnerability. Check regularly for firmware updates and apply them as soon as they are available for the specific device.
Revision history (1)
Initial publication — 12 August 2026
Initial
VDE-2026-008
Phoenix Contact: Multiple vulnerabilities in the firmware of CHARX SEC3xxx charging controllers
Published
30 July 2026
Last update
30 July 2026
Linked CVEs
Affected sectors
Risk evaluation
Multiple vulnerabilities have been identified in the firmware of CHARX SEC-3xxx EV charging controllers, including the CHARX SEC-3000, SEC-3050, SEC-3100, and SEC-3150 models. The flaws could allow attackers to compromise the devices remotely, resulting in a complete loss of confidentiality, integrity, and availability.
Mitigation summary
Phoenix Contact strongly recommends to upgrade to firmware version 1.9.1 which fixes these vulnerabilities.
Revision history (1)
Initial publication — 30 July 2026
Initial revision.
VDE-2026-060
Phoenix Contact: Unauthenticated log download vulnerability in the firmware of CHARX SEC-3xxx charging controllers
Risk evaluation
VDE-2026-060: A unauthenticated log download vulnerability in the firmware of CHARX SEC-3xxx charging controllers has been discovered.
Mitigation summary
Phoenix Contact strongly recommends to upgrade to firmware version 1.9.0 which fixes these vulnerabilities.
Revision history (2)
Initial publication — 3 June 2026
Initial revision
Update A — 3 June 2026
added "Firmware" to the textual description of the relationships.
VDE-2026-050
Phoenix Contact: PLCnext Firmware Security Issues Related to APPs and Configuration Files
Risk evaluation
This advisory addresses security issues in PLCnext firmware versions prior to 2026.0.3 that are related to APP handling and the processing of configuration files. The identified vulnerabilities affect APP installation authenticity as well as the handling of configuration data in writable directories. Successful exploitation may allow authenticated attackers with different privilege levels to compromise integrity, availability, and system security of affected PLCnext Control. Both issues are resolved starting with PLCnext firmware version 2026.0.3.
Mitigation summary
For firmware versions prior to 2026.0.3 apps are installed via WBM (APP Manager) without enforced authenticity validation. Verify the SHA-256 checksum provided by the PLCnext Store manually before installing an APP. Restrict WBM access to trusted IP ranges via the firewall and protect Engineer credentials. Monitor APP lifecycle security notifications locally or via a central Syslog server. If APPs are not required, disable the APP Manager service via the WBM System Services page to eliminate an unnecessary attack vector. Starting with firmware version 2026.0.3, APP signature verification is enabled by default and only signed apps can be installed.
Revision history (1)
Initial publication — 27 May 2026
Initial
VDE-2026-023
Phoenix Contact: Several products are affected by vulnerabilities found in OpenSSL
Published
22 April 2026
Last update
22 April 2026
Linked CVEs
Affected sectors
Risk evaluation
Attacks are possible when installing key files and digitally signed objects. These attacks can only be carried out if these files are uploaded and installed by a logged-in user with high privileges.
Mitigation summary
Phoenix Contact strongly recommends to upload firmware only from trusted source and to thorougly check the SHA256 checksum of the firmware image to be uploaded.
Revision history (1)
Initial publication — 22 April 2026
Initial release.
VDE-2025-104
Phoenix Contact: Multiple Vulnerabilities in FL SWITCH 2xxx, FL SWITCH TSN 23xx and FL SWITCH 59xx Firmware
Published
18 March 2026
Last update
18 March 2026
Linked CVEs
Affected sectors
Risk evaluation
Multiple vulnerabilities have been identified in the FL SWITCH 2xxx, FL SWITCH TSN 23xx and FL SWITCH 59xx firmware prior to version 3.53. One of these (CVE-2026-22317) enables an attacker to execute system commands as root user on the device. Five other vulnerabilities (CVE-2026-22316, CVE-2026-22318, CVE-2026-22319, CVE-2026-22320 and CVE-2026-22321) are related to Denial of Service (DoS) attacks, which partly limit the device's functionality. Another vulnerability (CVE-2026-22322) relates to reflected cross-site scripting in the web-based management of the device. And one vulnerability (CVE-2026-22323) relates to Cross‑Site Request Forgery in the web-based management of the device. All vulnerabilities have been resolved in firmware version 3.53.
Mitigation summary
Phoenix Contact strongly recommends to upgrade to firmware 3.53 which addresses this vulnerability and is available for download for all affected devices.
Revision history (1)
Initial publication — 18 March 2026
Initial release.
VDE-2025-109
Phoenix Contact: Unbounded growth of the session cache in TCP encapsulation service in FL MGUARD 2xxx and 4xxx firmware
Risk evaluation
The OpenSSL library used in the affected products is vulnerable to an unbounded growth of the session cache in the TLSv1.3 implementation.
Mitigation summary
It is recommended to disable TCP encapsulation on affected mGuard devices and use Pathfinder instead.
Revision history (2)
Initial publication — 10 February 2026
Initial release.
Update A — 23 February 2026
Updated category type in product tree.
VDE-2025-073
Phoenix Contact: Security Advisory for TC ROUTER and CLOUD CLIENT Industrial mobile network routers
Risk evaluation
A code injection vulnerability at the upload-config endpoint in the firmware of TC ROUTER and CLOUD CLIENT Industrial Mobile network routers has been discovered that can be exploited by an high privileged attacker.
Mitigation summary
As this vulnerability can only be exploited by an authenticated high privileged user, Phoenix Contact recommends to strictly restrict administrative access to the device. The administrative use shall only import configuration files from trusted sources.
Revision history (1)
Initial publication — 13 January 2026
Initial Revision
VDE-2025-071
Phoenix Contact: Multiple Vulnerabilities in FL SWITCH 2xxx Firmware
Published
9 December 2025
Last update
12 January 2026
Linked CVEs
Affected sectors
Risk evaluation
Multiple vulnerabilities have been identified in the FL SWITCH 2xxx firmware prior to version 3.50. Two of these (CVE-2025-41692 and CVE-2025-41696) enable an attacker to access the device's file system. Two other vulnerabilities (CVE-2025-41693 and CVE-2025-41694) are related to Denial of Service (DoS) attacks, which partly limit the device's functionality. Another vulnerability (CVE-2025-41697) allows an unauthenticated physical attacker to access a login shell via an undocumented UART port. Furthermore, there are multiple vulnerabilities relating to reflected cross-site scripting in the web-based management of the device. All vulnerabilities have been resolved in firmware version 3.50.
Mitigation summary
Phoenix Contact strongly recommends to upgrade to firmware 3.50 which addresses this vulnerability and is available for download for all affected devices.
Revision history (2)
Initial publication — 9 December 2025
Initial release.
Update A — 12 January 2026
Version range specifier and product idfentification helper added to firmware branch of product tree.
VDE-2025-074
Phoenix Contact: Security Advisory for CHARX SEC-3xxx charging controllers
Risk evaluation
A vulnerability in the firmware of CHARX SEC-3xxx charging controllers has been discovered.
Mitigation summary
This product was designed for use in closed industrial networks. Phoenix Contact strongly recommends operating network-capable devices in closed networks or protected with a suitable firewall. For detailed information on our recommendations for measures to protect network-capable devices, please refer to our [application note](https://dam-mdc.phoenixcontact.com/asset/156443151564/0a870ae433c19148b80bd760f3a1c1f2/107913_en_03.pdf).
Revision history (2)
Initial publication — 8 July 2025
Initial Revision
Update A — 15 October 2025
Updated the reporting credits, corrected reference token for one product, fixed typo in Document notes
Published
14 October 2025
Last update
14 October 2025
Affected sectors
Risk evaluation
Multiple vulnerabilities were discovered in the firmware of QUINT4-UPS EIP devices that can be used by an unauthenticated remote attacker to perform Denial of Service attacks and to gather login credentials for the Webfrontend.
Mitigation summary
This product was designed for use in closed industrial networks. Phoenix Contact strongly recommends operating network-capable devices in closed networks or protected with a suitable firewall. For detailed information on our recommendations for measures to protect network-capable devices, please refer to our [application note](https://dam-mdc.phoenixcontact.com/asset/156443151564/0a870ae433c19148b80bd760f3a1c1f2/107913_en_03.pdf). In the industrial sector it is common practice to use Modbus/TCP without authentication.
Revision history (1)
Initial publication — 14 October 2025
Initial revision.
VDE-2018-003
PHOENIX CONTACT: addressing Meltdown and Spectre vulnerabilities
Published
23 March 2018
Last update
1 October 2025
Linked CVEs
Affected sectors
Risk evaluation
Several CPUs manufactured by Intel, AMD or based on ARM technology may leak information due to their internal operation if attacked by specifically written software executed on the affected systems. The information in this advisory is based on the statements of respective manufacturers.
Mitigation summary
On Industrial PCs and HMIs that operate with user installable or upgradable operating systems (mainly Windows) the latest version or update may be installed if required in the use case. As the update may have a performance impact, the application should be tested accordingly.
Revision history (3)
Initial publication — 23 March 2018
Initial revision.
Update A — 14 May 2025
Fix: added distribution
Update B — 1 October 2025
Expressions errors were corrected in the acknowledgements.
VDE-2025-077
Phoenix Contact: Two vulnerabilities in the jq JSON processor utilized by FL MGUARD 110x devices
Published
9 September 2025
Last update
9 September 2025
Linked CVEs
Affected sectors
Risk evaluation
The jq JSON processor, which is used to migrate firmware configurations in the product, contains 2 vulnerabilities that can be exploited by an authenticated attacker.
Mitigation summary
Phoenix Contact strongly recommends upgrading affected mGuard devices to firmware version 1.8.1 or higher which fixes this vulnerability.
Revision history (1)
Initial publication — 4 August 2025
Initial revision.
VDE-2025-064
Phoenix Contact: Products utilizing WIBU-SYSTEMS CodeMeter Runtime Windows Installer have a privilege escalation
Published
9 September 2025
Last update
9 September 2025
Linked CVEs
Affected sectors
Control centres
Risk evaluation
A local privilege escalation vulnerability in Phoenix Contact products utilizing WIBU-SYSTEMS CodeMeter Runtime allows users to gain admin rights on freshly installed systems. The CodeMeter Control Center starts with elevated privileges and retains them until restarted, enabling unauthorized access to admin tools like cmd.exe.
Mitigation summary
PHOENIX CONTACT strongly recommends affected users to upgrade to CodeMeter V8.30a, which fixes these vulnerabilities. WIBU-SYSTEMS has already published this update for CodeMeter on their homepage. Since this current version of CodeMeter V8.30a has not yet been incorporated into Phoenix Contact products, we strongly recommend to download and install the current CodeMeter version directly from the WIBU-SYSTEMS homepage. Additional Recommendations: Regularly check the product's official webpage for updated release versions that support CodeMeter V8.30a. Update the Activation Wizard to version 1.8 as soon as it becomes available on the product's download page.
Revision history (1)
Initial publication — 9 September 2025
Initial
VDE-2024-022
Phoenix Contact: Security Advisory for CHARX-SEC3xxx Charge controllers
Published
13 August 2024
Last update
27 August 2025
Linked CVEs
Affected sectors
Risk evaluation
Start sequence for firewall service allows attack during the boot process. Password is reset to default when the device undergoes a firmware upgrade.
Mitigation summary
Phoenix Contact strongly recommends upgrading affected charge controllers to firmware version 1.6.3 or higher which fixes these vulnerabilities.
Revision history (4)
Initial publication — 13 August 2024
initial revision
Update A — 14 March 2025
Fix: typo in version
Update B — 22 May 2025
Fix: added distribution, quotation mark
Update C — 27 August 2025
Update: CWE from CVE-2024-6788, Revision History
Published
10 September 2024
Last update
27 August 2025
Linked CVEs
Affected sectors
Risk evaluation
Confidential data in HTTP query string of user requests. Incomplete sanitation of user input in administrative web interface.
Mitigation summary
Read access to the device via administrative interfaces should be granted only to trustworthy users.
Revision history (4)
Initial publication — 10 September 2024
Initial revision.
Update A — 6 November 2024
Fix: correct certvde domain, added self-reference
Update B — 10 April 2025
Fixed csaf reference URL
Update C — 27 August 2025